9

English

Wiring

WARNING

•  Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, electric shock, or fire.
• 

Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the 

terminal block.) Doing so may cause electric shock or fire.

• 

The circuit must be protected with safety devices in accordance with local and national codes, i.e. a circuit breaker.

• 

Use an all-pole disconnection type circuit breaker with at least 1/8 inch (3mm) between the contact point gaps.

• 

When carrying out wiring, take care not to pull at the conduit.

•  Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

• 

Do not turn on the circuit breaker until all work is completed.

1) Strip the insulation from the wire (3/4 inch (20mm)).
2) Connect the inter-unit wires between the indoor and outdoor units so that the terminal numbers match. Tighten the 

terminal screws securely. It is recommended that a slot-head screwdriver be used to tighten the screws.  
The screws are packed with the terminal block.

1

2

3

1 2 3

Follow local codes for wiring 

and safety devices between 

outdoor unit and power 

source.

Ground

Firmly fix the wires with 
the te

rminal screws.

Recommend using AWG14, stranded and insulated 

wire for connections between indoor and outdoor units.

Local code always supersedes recommendation.

Outdoor unit

Indoor 
unit

Power supply
60Hz 208-230V

Firmly fix the 
wires with the 

terminal screws.

L

1

 L

2

Note: Take care to ensure that all wiring between 
indoor unit and outdoor unit has a consistent 

connection. Any splices can cause communication 
errors.

RX09/12/15/18

20A

15A

RX24

09/12 class

[Method of mounting conduit]

•  A protection plate is fixed for protection from the high-voltage section.

1) Dismount the stop valve cover by removing the screw.
2) Dismount the protection plate by removing the 2 screws.
3) Dismount the conduit mounting cover by removing the 2 screws.
4) Pass wires through the conduit and secure them with a lock nut.
5) After completing the work, reattach the stop valve cover, the conduit mounting cover, and the protection plate to its 

original position.

1

2

3

1

2

3

1

2

3

Screws

Conduit
mounting
cover

Screws

Protection plate

Power supply
terminal block

Shape wires so 
that the protection 
plate and conduit 

mounting plate fit 

securely.

Conduit

Lock nut

Conduit 
mounting 
plate

L

1

L

2

01_EN_3P500432-2B.indd   9

10/30/2018   11:53:03 AM

Summary of Contents for RX09RMVJU

Page 1: ...X09RMVJU RX12RMVJU RX15RMVJU RX18RMVJU RX24RMVJU RX09RMVJU9 RX12RMVJU9 RX18RMVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de...

Page 2: ...hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting i...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...ble gas leaks in the surrounding area 7 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditioner 8 Since water will...

Page 5: ...lt in reduced performance The suggested shortest pipe length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit i...

Page 6: ...all facing one side Walls facing two sides Top view Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15...

Page 7: ...vice life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is...

Page 8: ...ssure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose to the gas stop valve s service port 3 Fully open the gauge manifold s low pres...

Page 9: ...insulation materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to...

Page 10: ...2 3 1 2 3 Follow local codes for wiring and safety devices between outdoor unit and power source Ground Firmly x the wires with the terminal screws Recommend using AWG14 stranded and insulated wire fo...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...tion In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out forced cooling o...

Page 13: ...ter about 30 minutes To stop the operation press Trial Operation and Testing 1 Trial operation and testing Refer to the installation manual for the indoor unit 2 Test items Test items Symptom Check In...

Page 14: ...Two dimensional bar code is a manufacturing code 3P500432 2B M17B180B 1810 HT...

Reviews: