background image

11

English

Facility Setting 

(cooling at low outdoor temperature)

This function is limited only for facilities (the target of air conditioning is equipment (such as computer)). 

Never use it in a residence or office (the space where there is a human).

 

„

 Cutting jumper 6 (J6)

 on the circuit board will extend the operation range to 14°F (–10°C). Installing an air direction 

adjustment grille (sold separately) will further extend the operation range to –4°F (–20°C). 

In these cases, the unit will 

stop operating if the outdoor temperature falls below –4°F (–20°C), restarting once the temperature rises above this level.

1)  Remove the top plate of the outdoor unit. (09/12 class: 3 screws, 15/18/24 class: 6 screws)
2)  Remove the front plate. (09/12 class: 4 screws, 15/18/24 class: 8 screws)
3)  Cut the jumper (J6) of the PCB inside. 

CAUTION

•  If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• 

Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.

•  Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used. 

 

A humidifier might cause dew jumping from the indoor unit outlet vent.

• 

Cutting jumper 6 (J6) sets the indoor fan tap to the highest position. Notify the user about this.

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 

1) Remove the valve cap from the liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) 

After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.

4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.
5) Attach the valve cap once procedures are complete.

Gas 
stop valve

Valve cap

Hexagonal 
wrench

Close

Liquid 
stop valve

Service port

Forced cooling operation

[For FFQ and FDMQ models]

 

„

Using the indoor unit’s remote controller

[For wired remote controller]

1) Set to COOL operation using the remote controller.
2) 

Press and hold the Cancel button for 4 seconds or longer. 

 

Service settings menu is displayed.

3) Select 

 Test Operation 

 in the service settings menu, and press 

the Menu/OK button. Basic screen returns and “Test Operation” is 
displayed at the bottom.

4) 

Press the On/Off button within 10 seconds, and the forced cooling 

operation starts.

• 

Forced cooling operation will stop automatically after about 15 
minutes. To stop the operation, press the On/Off button.

Basic screen

1)
2)

Cool

Return

Clean the filter

Set to

Cool

68

F

Press and hold the Cancel 
button for 4 seconds or 
longer during backlight lit. 

Service Settings 

menu screen

3)

Setting

1/3

Service Settings

Test Operation

Maintenance Contact
Field Settings
Energy Saving Options
Prohibit Buttons
Min Setpoints Differential

Press the Menu/OK button.

4)

Set temperature

80

°F

Cool

Test Operation

Press the On/Off button 
(within 10 seconds).

01_EN_3P500432-2B.indd   11

10/30/2018   11:53:03 AM

Summary of Contents for RX09RMVJU

Page 1: ...X09RMVJU RX12RMVJU RX15RMVJU RX18RMVJU RX24RMVJU RX09RMVJU9 RX12RMVJU9 RX18RMVJU9 DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de...

Page 2: ...hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting i...

Page 3: ...getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribut...

Page 4: ...ble gas leaks in the surrounding area 7 In coastal areas or other places with a salty atmosphere or one containing sulfate gas corrosion may shorten the life of the air conditioner 8 Since water will...

Page 5: ...lt in reduced performance The suggested shortest pipe length is 10ft 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit i...

Page 6: ...all facing one side Walls facing two sides Top view Top view More than 5 7 8 150 More than 11 13 16 300 More than 1 15 16 50 Walls facing three sides unit inch mm unit inch mm Top view More than 3 15...

Page 7: ...vice life The drying material may dissolve and damage the system Incomplete flaring may result in refrigerant gas leakage 4 Refrigerant piping CAUTION Use the flare nut fixed to the main unit This is...

Page 8: ...ssure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose to the gas stop valve s service port 3 Fully open the gauge manifold s low pres...

Page 9: ...insulation materials When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030Btu fth F 0 035 to...

Page 10: ...2 3 1 2 3 Follow local codes for wiring and safety devices between outdoor unit and power source Ground Firmly x the wires with the terminal screws Recommend using AWG14 stranded and insulated wire fo...

Page 11: ...r power supply wiring When using stranded wires make sure to use the round crimp style terminal for connection to the power supply terminal block Stranded wire Round crimp style terminal Arrow view Fl...

Page 12: ...tion In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Carry out forced cooling o...

Page 13: ...ter about 30 minutes To stop the operation press Trial Operation and Testing 1 Trial operation and testing Refer to the installation manual for the indoor unit 2 Test items Test items Symptom Check In...

Page 14: ...Two dimensional bar code is a manufacturing code 3P500432 2B M17B180B 1810 HT...

Reviews: