19 Troubleshooting

Installer and user reference guide

53

RWEYQ8~1 RWEYQ8~14T9Y1B
VRV IV water-cooled system air conditioner
4P452191-1 – 2017.04

WARNING

Stop  operation  and  shut  off  the  power  if  anything
unusual occurs (burning smells etc.).

Leaving  the  unit  running  under  such  circumstances  may
cause breakage, electric shock or fire. Contact your dealer.

The system must be repaired by a qualified service person:

If  the  system  does  not  properly  operate  except  for  the  above
mentioned cases and none of the above mentioned malfunctions is
evident,  investigate  the  system  according  to  the  following
procedures.

Malfunction

Measure

If the system does not
operate at all.

▪ Check  if  there  is  no  power  failure.  Wait

until  power  is  restored.  If  power  failure
occurs  during  operation,  the  system
automatically  restarts  immediately  after
power is restored.

▪ Check if no fuse has blown or breaker is

activated.  Change  the  fuse  or  reset  the
breaker if necessary.

If the system goes into
fan only operation, but
as soon as it goes into
heating or cooling
operation, the system
stops.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the user interface display shows

 (time to clean the air filter). (Refer to

"18  Maintenance  and  service"  on
page 51

 and "Maintenance" in the indoor

unit manual.)

The system operates
but cooling or heating
is insufficient.

▪ Check  if  air  inlet  or  outlet  of  outdoor  or

indoor  unit  is  not  blocked  by  obstacles.
Remove  any  obstacles  and  make  sure
the air can flow freely.

▪ Check if the air filter is not clogged (refer

to  "Maintenance"  in  the  indoor  unit
manual).

▪ Check the temperature setting.

▪ Check the fan speed setting on your user

interface.

▪ Check for open doors or windows. Close

doors and windows to prevent wind from
coming in.

▪ Check if there are too many occupants in

the room during cooling operation. Check
if  the  heat  source  of  the  room  is
excessive.

▪ Check  if  direct  sunlight  enters  the  room.

Use curtains or blinds.

▪ Check if the air flow angle is proper.

If  after  checking  all  above  items,  it  is  impossible  to  fix  the  problem
yourself, contact your installer and state the symptoms, the complete
model name of the unit (with manufacturing number if possible) and
the installation date (possibly listed on the warranty card).

19.1

Error codes: Overview

In case a malfunction code appears on the indoor unit user interface
display,  contact  your  installer  and  inform  the  malfunction  code,  the
unit  type,  and  serial  number  (you  can  find  this  information  on  the
nameplate of the unit).

For  your  reference,  a  list  with  malfunction  codes  is  provided.  You
can, depending on the level of the malfunction code, reset the code
by pushing the ON/OFF button. If not, ask your installer for advice.

19.2

Symptoms that are NOT system
malfunctions

The following symptoms are NOT system malfunctions:

19.2.1

Symptom: The system does not operate

▪ The  air  conditioner  does  not  start  immediately  after  the  ON/OFF

button  on  the  user  interface  is  pressed.  If  the  operation  lamp
lights, the system is in normal condition. To prevent overloading of
the compressor motor, the air conditioner starts 5 minutes after it
is  turned  ON  again  in  case  it  was  turned  OFF  just  before.  The
same  starting  delay  occurs  after  the  operation  mode  selector
button was used.

▪ If  "Under  Centralized  Control"  is  displayed  on  the  user  interface,

pressing the operation button causes the display to blink for a few
seconds.  The  blinking  display  indicates  that  the  user  interface
cannot be used.

▪ The  system  does  not  start  immediately  after  the  power  supply  is

turned  on.  Wait  one  minute  until  the  micro  computer  is  prepared
for operation.

19.2.2

Symptom: Cool/Heat cannot be changed
over

▪ When  the  display  shows 

  (change-over  under  centralized

control), it shows that this is a slave user interface.

▪ When the cool/heat changeover remote control switch is installed

and  the  display  shows 

  (change-over  under  centralized

control), this is because cool/heat changeover is controlled by the
cool/  heat  changeover  remote  control  switch.  Ask  your  dealer
where the remote control switch is installed.

19.2.3

Symptom: Fan operation is possible, but
cooling and heating do not work

Immediately  after  the  power  is  turned  on.  The  micro  computer  is
getting  ready  to  operate  and  is  performing  a  communication  check
with  all  indoor  units.  Please  wait  12  minutes  maximally  until  this
process is finished.

19.2.4

Symptom: The fan strength does not
correspond to the setting

The  fan  speed  does  not  change  even  if  the  fan  speed  adjustment
button  is  pressed.  During  heating  operation,  when  the  room
temperature  reaches  the  set  temperature,  the  outdoor  unit  goes  off
and the indoor unit changes to whisper fan speed. This is to prevent
cold  air  blowing  directly  on  occupants  of  the  room.  The  fan  speed
will  not  change  even  when  another  indoor  unit  is  in  heating
operation, if the button is pressed.

19.2.5

Symptom: The fan direction does not
correspond to the setting

The  fan  direction  does  not  correspond  with  the  user  interface
display. The fan direction does not swing. This is because the unit is
being controlled by the micro computer.

19.2.6

Symptom: White mist comes out of a unit
(Indoor unit)

▪ When humidity is high during cooling operation. If the interior of an

indoor unit is extremely contaminated, the temperature distribution
inside  a  room  becomes  uneven.  It  is  necessary  to  clean  the
interior  of  the  indoor  unit.  Ask  your  dealer  for  details  on  cleaning
the unit. This operation requires a qualified service person.

Summary of Contents for RWEYQ8T9Y1B

Page 1: ...er and user reference guide VRV IV water cooled system air conditioner English Installer and user reference guide VRV IV water cooled system air conditioner RWEYQ8T9Y1B RWEYQ10T9Y1B RWEYQ12T9Y1B RWEYQ...

Page 2: ...refrigerant piping 23 6 4 4 To connect the refrigerant piping to the outdoor unit 23 6 4 5 To connect the multi connection piping kit 24 6 4 6 To connect the refrigerant branching kit 24 6 4 7 To pro...

Page 3: ...ymptoms that are NOT system malfunctions 53 19 2 1 Symptom The system does not operate 53 19 2 2 Symptom Cool Heat cannot be changed over 53 19 2 3 Symptom Fan operation is possible but cooling and he...

Page 4: ...tal above a certain concentration Possible chemical symbols are Pb lead 0 004 Waste batteries must be treated at a specialized treatment facility for reuse By ensuring waste batteries are disposed of...

Page 5: ...ou can collect all refrigerant from the system into the outdoor unit Possible consequence Self combustion and explosion of the compressor because of air going into the operating compressor Use a separ...

Page 6: ...ey do not come in contact with the piping and sharp edges Make sure no external pressure is applied to the terminal connections Make sure to install earth wiring Do NOT earth the unit to a utility pip...

Page 7: ...erview About the box This chapter describes what you have to do after the box with the outdoor unit is delivered on site It contains information about Unpacking and handling the outdoor unit Removing...

Page 8: ...as pipe Front connection a a b Top connection c d 8 25 4 25 4 25 4 19 1 10 22 2 12 28 6 14 High pressure Low pressure gas pipe Front connection a a b Top connection c d 8 25 4 25 4 25 4 15 9 10 19 1 1...

Page 9: ...for single or multi use Depending on the chosen type of unit some functionality will or will not exist It will be indicated throughout this installation manual and brought to your attention Certain fe...

Page 10: ...IV water cooled system can be combined with several types of indoor units and is intended for R410A use only For an overview which units are available you can consult the product catalogue for VRV IV...

Page 11: ...ed Instructions group or individual can be instructed for low noise operation and power consumption limitation operation PC configurator cable EKPCCAB You can make several commissioning field settings...

Page 12: ...piping may result in indoor water leakage and property damage 5 2 2 Securing safety against refrigerant leaks About safety against refrigerant leaks The installer and system specialist shall secure s...

Page 13: ...ly to the greenhouse effect if it is released Therefore pay special attention to check the tightness of the installation NOTICE The piping and other pressure containing parts shall be suitable for ref...

Page 14: ...ed downstream Do not let the connection piping exceed the refrigerant piping size chosen by the general system model name In case of heat pump mode Indoor unit capacity index Piping outer diameter siz...

Page 15: ...5T Concerning refnet headers choose from the following table in accordance with the total capacity of all the indoor units connected below the refnet header Indoor unit capacity index 2 pipes 3 pipes...

Page 16: ...up the liquid piping refer to 5 3 2 To select the piping size on page 13 for more information Activate the outdoor unit setting Refer to the service manual for more information The outdoor unit is pos...

Page 17: ...pe Maximum length actual equivalent Longest pipe from the outdoor unit or the last multi outdoor piping branch 1 2 1 3 4 1 3 5 6 1 3 5 7 100 m 120 m Longest pipe after the first branch 3 4 3 5 6 3 5 7...

Page 18: ...n 90 m size up the main liquid piping according to 5 3 2 To select the piping size on page 13 Connection with only VRV DX indoor units H3 1 5 H1 H2 3 2 4 a b b c d b b a Outdoor unit b VRV DX indoor u...

Page 19: ...ee carbon dioxide mg CO2 l 4 0 0 4 4 0 Stability index 6 0 7 0 a These items represent typical causes of corrosion and scale b In a condenser water circuit that uses a closed cooling tower the closed...

Page 20: ...mplete drainage of the water circuit Drainage Clogging Make sure that the water runs smoothly without any clogging by dirt Drainage Lateral length Lateral length of drainage should be as short as poss...

Page 21: ...flow rate B is directly related to the maximum flow rate of the system INFORMATION Some third party valves pumps have a maximum flow rate defined by the hardware of the system but a different maximum...

Page 22: ...mmended fuse capacity would be 80 A NOTICE When using residual current operated circuit breakers be sure to use a high speed type 300 mA rated residual operating current 6 Installation 6 1 Overview In...

Page 23: ...ossible risks Excessive refrigerant concentrations in a closed room can lead to oxygen deficiency Toxic gas may be produced if refrigerant gas comes into contact with fire WARNING Always recover the r...

Page 24: ...can be ensured 120 mm 500 mm 6 4 6 To connect the refrigerant branching kit For installation of the refrigerant branching kit refer to the installation manual delivered with the kit Mount the refnet...

Page 25: ...the stop valve cap 1 2 3 4 To close the stop valve 1 Remove the stop valve cover 2 Insert a hexagon wrench into the stop valve and turn the stop valve clockwise 3 When the stop valve cannot be turned...

Page 26: ...e Blow out any particles with compressed air 7 Wait until all oil is dripped out before continuing with the connection of the field piping in case the recovery was not complete 6 5 Checking the refrig...

Page 27: ...Open Valve D Open Liquid line stop valve Close Gas line stop valve Close High pressure low pressure gas line stop valve Close NOTICE The connections to the indoor units and all indoor units should al...

Page 28: ...higher than the indoor unit this must be prevented by sealing up the connections See below figure 3 a b a Insulation material b Caulking etc 6 7 Charging refrigerant 6 7 1 Precautions when charging re...

Page 29: ...5 mm 0 16 16 mm 0 18 19 1 mm 0 26 18 mm 0 24 22 2 mm 0 37 22 mm 0 35 Connection ratio requirements When selecting indoor units the connection ratio must comply with the following requirements For more...

Page 30: ...efrigerant charge mode Refer to 7 2 8 Mode 2 Field settings on page 38 for details Result The unit will start operation 9 Valve A can be opened Charging of remaining additional refrigerant can be done...

Page 31: ...LECTROCUTION WARNING All field wiring and components must be installed by a licensed electrician and must comply with the applicable legislation WARNING If NOT factory installed a main switch or other...

Page 32: ...d the transmission wiring separated from each other In order to avoid any electrical interference the distance between both wiring should always be at least 25 mm NOTICE Be sure to keep the power line...

Page 33: ...O IN D UNIT TO OUT D UNIT F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 F1 F2 j i i h h e a Unit A master outdoor unit b Unit B slave outdoor unit c Unit C slave outdoor unit d Outdoor unit PCB A1P e Master slave tra...

Page 34: ...the cup washer An improper earth connection may prevent a good earthing from being achieved The power supply must be clamped to the plastic bracket using field supplied clamp material The green and ye...

Page 35: ...sult in unintended forced thermo off conditions Example X3M X3M YLW a b c d e ORG RED BRN BLU BLU WHT WHT BLK BLK BLK TW1 IN TW2 OUT WHT BLU BLU BLU YLW ORG RED BRN 0 10 1 2 3 4 5 6 7 8 9 10 X2M b a X...

Page 36: ...mponent box to access the push buttons on the PCB and read out the 7 segment display s To access you can remove the front inspection cover of the front plate see figure Now you can open the inspection...

Page 37: ...push BS1 for more than 5 seconds you can select the wanted setting It is done by pushing BS2 Accessing the selected setting s value is done by pushing BS3 1 time To quit and return to the initial sta...

Page 38: ...tion 1 13 Shows the total number of connected outdoor units in case of multiple outdoor system It can be convenient to check if the total number of outdoor units which are installed matches the total...

Page 39: ...l is according to the table 2 30 Power consumption limitation approximately 1 60 2 65 3 default 70 4 75 5 80 6 85 7 90 2 30 Power consumption limitation approximately 8 95 2 31 Power consumption limit...

Page 40: ...unit but the connected indoor unit will operate as well Working on an indoor unit while performing a test operation is dangerous CAUTION Do not insert fingers rods or other objects into the air inlet...

Page 41: ...applicable legislation Make sure that following components are positioned at their correct places water filter air purge valve automatic water supply valve and expansion tank Water circuit Make sure...

Page 42: ...rant charge in kg 1000 9 1 Overview Maintenance and service This chapter contains information about Preventing electrical hazards when maintaining and servicing the system Cleaning the plate heat exch...

Page 43: ...gerant This should be done by a refrigerant reclaimer Follow the same procedure as for vacuuming method DANGER RISK OF EXPLOSION Pump down Refrigerant leakage If you want to pump down the system and t...

Page 44: ...ce guide 44 RWEYQ8 14T9V1B RWEYQ8 14T9Y1B VRV IV water cooled system air conditioner 4P452191 1 2017 04 mm 500 500 900 900 20 20 20 20 20 20 F mm 300 F Front side INFORMATION Further specifications ca...

Page 45: ...PL 4D108945A A Charge port B Stop valve with service port 7 9 mm flare connection C Cooling water inlet D Cooling water outlet Charge port Service port Filter Check valve Pressure relief valve Solenoi...

Page 46: ...e T 3 15 A 250 V F401U A2P Fuse T 6 3 A 250 V F402U A2P Fuse T 6 3 A 250 V F403U A2P Fuse T 6 3 A 250 V F410U A2P Fuse T 63 A 600 V F411U A2P Fuse T 63 A 600 V F412U A2P Fuse T 63 A 600 V F U A1P Fuse...

Page 47: ...s may happen For checking and adjusting the internal parts contact your dealer This operation manual will give a non exhaustive overview of the main functions of the system Detailed information on req...

Page 48: ...energy transfer to the outdoor unit s coil Heating capability decreases and the system needs to go into defrost operation to be able to deliver enough heat to the indoor units In case of Then RWEYQ16...

Page 49: ...49 for details To stop 4 Press the ON OFF button on the user interface once again Result The operation lamp goes out and the system stops operating NOTICE Do not turn off power immediately after the u...

Page 50: ...our room causing a decrease in the cooling or heating effect Be careful not to cool or heat too much To save energy keep the temperature setting at a moderate level Never place objects near the air in...

Page 51: ...tips and procedures for cleaning are provided in the installation operation manuals of dedicated indoor units Make sure to install cleaned air filters back in the same position Turn on the power at le...

Page 52: ...unit Depending on the model we recommend not starting and stopping the machine more than 6 times hour Operation of the unit is assumed to be 10 hours day and 2 500 hours year NOTICE The table indicat...

Page 53: ...he level of the malfunction code reset the code by pushing the ON OFF button If not ask your installer for advice 19 2 Symptoms that are NOT system malfunctions The following symptoms are NOT system m...

Page 54: ...e tone of operating noise changes This noise is caused by the change of frequency 19 2 12 Symptom Dust comes out of the unit When the unit is used for the first time in a long time This is because dus...

Page 55: ...t how to install configure operate and or maintain the product or application Accessories Labels manuals information sheets and equipment that are delivered with the product and that need to be instal...

Page 56: ...4P452191 1 2017 04 Copyright 2017 Daikin 4P452191 1 0000000K...

Reviews: