Performance
EDUS30-900-R
8
RWEYQ-P Water Cooled Inverter Series
2. Performance
The VRV-WIII RWEYQ condensing unit shall perform as indicated below.
The tested system EER and COP values reflect “full load” efficiency only and are the results from testing to the
“Alternate Test Method” (ATM) guidelines provided by the U.S. Department of Energy (DOE) in the Federal
Register / Vol. 74, No. 68 / Friday April 10, 2009 / Notices / Pages 16373 – 16377. All tested values surpass the
minimum efficiency levels regulated in the DOE Code of Federal Regulation 10 CFR Ch. II § 431.97.
Performance Conditions
Cooling: indoor temp. of 67°F (37°C) WB. 85°F(29.4°C) inlet water and 25.4 gpm water volume.
Heating: indoor temp. of 70°F (21.1°C) DB. 70°F(21.1°C) inlet water and 25.4 gpm water volume.
Equivalent piping length: 25ft
(7.5 m)
Model Number
Cooling Capacity
(Btu/h)
Power Input
(Watts)
EER
(full load)
RWEYQ72PTJU
72,000
4,200
15.3
RWEYQ84PTJU
84,000
5,600
13.7
RWEYQ144PTJU
144,000
8,400
15.3
RWEYQ168PTJU
168,000
11,200
13.7
RWEYQ216PTJU
216,000
12,600
15.3
RWEYQ252PTJU
252,000
16,800
13.7
Model Number
Heating Capacity
(Btu/h)
Power Input
(Watts)
COP (full
load)
RWEYQ72PTJU
81,000
4,000
5.3
RWEYQ84PTJU
94,500
5,400
4.7
RWEYQ144PTJU
162,000
8,000
5.3
RWEYQ168PTJU
189,000
10,800
4.7
RWEYQ216PTJU
243,000
12,000
5.3
RWEYQ252PTJU
283,500
16,200
4.7