10. Standard Operation Limits
RWEYQ72PTJU / RWEYQ84PTJU
3D066042
Notes:
1. This figure shows the operation range when
the water volume is 13.2~39.6 gal/min (50~150 l/min)
This value shows the volume of water per one heat source unit.
2. Design in the following condition range:
water temperature : 67~95°F (19.4~35°C)
water volume: 15.9 gal/min (60.2 l/min)
3. When cooling load is small, the indoor unit may initiate thermostat-off for freeze protection;
this is only for a limited amount of time.
4. Hold ambient conditions at 35~95°F, (1.6~35°C)~80%RH.