![background image](http://html1.mh-extra.com/html/daikin/rweyq-p/rweyq-p_engineering-data_2459892057.webp)
Standard Operation Limits
EDUS30-900-R
56
RWEYQ-P Water Cooled Inverter Series
3D066043
Notes:
1. This figure shows the operation range when
the water volume is 13.2~39.6 gal/min (50~150 l/min)
This value shows the volume of water per one heat source unit.
2. Design in the following condition range:
water temperature : 67~95°F (19.4~35°C)
water volume: 15.9 gal/min (60.2 l/min)
3. When the cooling load is small, the indoor unit may initiate thermostat-off for freeze
protection; this is only for a limited period of time.
4. Hold ambient conditions at 35~95°F, (1.6~35°C)~80%RH.