15
Refrigerant Recycle Equipment
Discharge the oil when Tank Full Lamp is on ( ①~⑧)or after daily operation(⑤~⑧).
① Close the suction hose ball valve from the
manifold.
② In Auto Shut-off mode, start the unit by pushing
Force Start Switch.
* The switch will release unless you keep it
depressed.
③ The unit stops automatically when Suction
Pressure reaches - 0.03MPa(- 4.4psi).
④ Set Power Switch to [OFF] position.
⑤ Adjust Suction Pressure between 0.1MPa
(14.5psi) ~ 0.2 MPa(29psi) by opening the
suction hose ball valve from the manifold.
⑥ Remove the cap of Oil Discharge Port on the
back of the unit.
⑦ Open the valve slowly and discharge the oil
into another container.
* The oil tank capacity is 2L.
⑧ Close the valve and cap of Oil Discharge Port
after discharging the oil.
Check every 100 hours of operation for any oil or contamination in the Electrostatic Filter System.
Oil Discharge Procedure (Oil Separator)
Oil Discharge Procedure (Electrostatic Filter System)
Oil Discharge Port
for Oil Separator
Force Start Switch
Oil Discharge Port for
Electrostatic Filter System
① Adjust Suction Pressure between 0.1MPa
(14.5psi) ~ 0.2MPa (29psi) by opening the
suction hose ball valve from the manifold.
② Remove cap of Oil Discharge Port.
③ Open the valve slowly and discharge the oil
into another container.
④ Close the valve and cap of Oil Discharge Port
after discharging the oil.
HOW TO USE