11
Refrigerant Recycle Equipment
■ Prepare the following accessories in advance. (Optional accessories)
■ Warm up
Operation procedure of R134a recycle
Operation time
Suction
Discharge
OPEN
CLOSE
Low
pressure side
High
pressure side
OPEN
Suction Valve
RECYCLE
Switching Valve
CLOSE
Discharge Valve
OPEN
5
OPEN
Liquid valve
CLOSE
Vapor valve
Cylinder
Manifold
OPEN
Ball valve
OFF
Power
O N
Start
ON
3
kg
MED
RESOLUTION
Cy Scale
RRDQ220V1
OPEN
8
CLOSE
Vapor valve
Liquid valve
CLOSE
SLOWLY
OPEN
6
CLOSE
Ball valve
At 0.2MPa (29psi)
Maintain
4
START
Liquid Charge Adapter 1/4”
Filter
Auto Shut-off
2
Auto
Shut-off
Manual
● In case of recycling R134a, the efficiency of the heat exchanger in Oil Separator is not adequate
even if the ambient temperature is 10℃ or higher.
Liquid R134a accumulates in Oil Separator and the full tank sensor unit.
● Connect Liquid Charge Adapter 1/4" (A) and Filter (B) between the suction hose and the manifold
center port.
● Warm up the unit every time regardless of temperature. (Refer to page 16 "Warm Up Operation".)
● If the pressure of the recycled R134a is low (if the temperature is low), warm the R134a in the
cylinder with a heater to increase the pressure.
(A) Code No. Y41123
Liquid Charge Adapter 1/4 "
1 piece
(B) Code No. TF011
Filter
1 piece
■ Operation method
① Connect hoses as above after carrying out procedure on Page 9 " 2) Evacuation of the recycle
unit and the hoses".
② Set Auto Shut-off/Manual Mode Setting to [Auto Shut -off] position.
③ Set Power Switch to [ON] and press Start Switch once.
④ Adjust Suction Pressure between 0.1MPa (14.5psi) ~ 0.2MPa (29psi) by opening the suction hose
ball valve from the manifold and keep operating until discharge pressure becomes 1.0MPa (145psi).
HOW TO USE