Daikin RRDQ220V1 Operation Manual Download Page 1

【Please read this manual before operation】

REFRIGERANT

 RECYCLE  EQUIPMENT

RRDQ220V1

OPERATION MANUAL

【Original operation manual】

English

Summary of Contents for RRDQ220V1

Page 1: ... Please read this manual before operation REFRIGERANT RECYCLE EQUIPMENT RRDQ220V1 OPERATION MANUAL Original operation manual English ...

Page 2: ... 7 Preparation Before Operation 7 Recycle Operation 8 Description of Auto Stop Timer 13 Oil Discharge Procedure Oil Separator 15 Oil Discharge Procedure Electrostatic Filter System 15 Warm Up Operation 16 MAINTENANCE INSPECTION 17 Maintenance 17 Replace Molecular Sieve Replacement Kit 17 In Case of Recycle Other Refrigerant 18 INSPECTION BEFORE WORK 18 LOADING UNLOADING OF THE UNIT 20 EU DECLARATI...

Page 3: ...ration or when disconnecting hoses Refrigerant gas may cause frostbite or damage your eye sight Do not close the valves of the unit and the hoses when they are full of liquid refrigerant Do not operate or store the unit at temperature above 35 When the recycle operation is done operate the purge procedure to prevent the liquid refrigerant from expanding which may cause an explosion Use a scale to ...

Page 4: ...assemble The unit should only be repaired by an authorized repair person Do not operate the unit with the cover removed It may cause injury or damage Various safety devices are built into this unit Always carry out pre start inspection according to page 18 INSPECTION BEFORE WORK before using If any abnormality is found in the unit please stop using it immediately and contact your dealer or our sal...

Page 5: ... If an abnormal condition strange smell vibration strange noise is noticed stop operation immediately and refer to page 21 in the manual BEFORE REQUESTING REPAIR OR SERVICE Request repair or service instead of disassembling the unit Contact the store where the unit was purchased Use our cylinders that are expressly made for recycling Use cylinders that match the type of refrigerant being recycled ...

Page 6: ...l Lamp Start Switch Power Switch Breaker Auto Manual Shut off Mode Setting Auto Stop Timer Oil Discharge Port for Electrostatic Filter System Suction Port Filter TF011 Discharge Port Sight Glass ES603 Labels are required by law for safety and the warnings are placed on the recycle unit If the label comes off the unit or became dirty and unreadable request us for new label Replace the label at the s...

Page 7: ...0 Applicable cylinder Refrigerant Recycle Cylinder minimum working pressure of 400 psi Recycle rate R410A R32 R134a Liquid g min 220 100 100 Vapor g min 90 90 90 Recycled refrigerant R410A R32 R134a Performance standard AHRI 740 Moisture ppm 20 20 20 Total residue on evaporation 0 01 0 01 0 01 Results of the recycle varies depending on the contamination of the refrigerant to be recycled Descriptio...

Page 8: ...ion Do not operate at temperature under 5 and over 35 Filter provided as standard accessory must be installed on Suction Port when operating the unit Do not recycle following refrigerant with the unit The purity of recycled refrigerant is low and it may cause damage to the unit Refrigerant charged in a system which the compressor has been burned out Refrigerant which may be mixed with other type o...

Page 9: ...ter open the package to avoid spoiling the quality of Molecular Sieve CAUTION CAUTION Please check if elapsed time of the timer has reached 20hours In R32 R134a recycle press Reset Key of Auto Stop Timer at first automatic stop to initialize the timer and replace Molecular Sieve Replacement Kit and Filter at second automatic stop 40 hours Please replace Molecular Replacement Kit and Filter and pre...

Page 10: ...w pressure gauge becomes vacuum Turn Suction Valve V1 to PURGE position Turn Switching Valve V2 to PURGE position Continue until low pressure gauge becomes vacuum Close the discharge hose ball valve Turn off the vacuum pump power switch Connect discharge hose to liquid side port of collection cylinder 2 Evacuation of the recycle unit and the hoses Operation time Suction Discharge Cylinder OPEN Vap...

Page 11: ... CLOSE 8 CLOSE Low pressure side High pressure side OFF Power O N Start OFF Power O N Auto Shut off Manual AutoShut off 2 ON 3 OFF 7 kg MED RESOLUTION Cylinder Scale RRDQ220V1 CLOSE Vapor valve Liquid valve CLOSE CLOSE Ball valve SLOWLY OPEN 4 CLOSE 6 OPEN Ball valve Ball valve AutoShut off 2 Warm up the unit when ambient temperature is under 10 Refer to page 16 Warm Up Operation A scale must be use...

Page 12: ...e is 10 or higher Liquid R134a accumulates in Oil Separator and the full tank sensor unit Connect Liquid Charge Adapter 1 4 A and Filter B between the suction hose and the manifold center port Warm up the unit every time regardless of temperature Refer to page 16 Warm Up Operation If the pressure of the recycled R134a is low if the temperature is low warm the R134a in the cylinder with a heater to...

Page 13: ... initialize the timer to replace Molecular Sieve Replacement Kit and Filter at the second automatic stop 40 hours 4 If the surface of Filter connected to the manifold becomes frozen during recycling and it stops recycling replace or clean Filter according to the following procedure and then restart recycling 1 Set Auto Shut off Manual Mode Switch to Auto Shut off and close the high pressure side v...

Page 14: ...et Value Display Set Value 1 2 Indicator Operation Key Up Keys 1 to 4 Down Key 1 to 4 Key Protect Indicator Use Unused Operation possible The timer measures ON time of Power Switch and it is set to stop automatically after 20 hours have elapsed The setting value is locked by Key Protect do not change it The function of mark in right figure is not used mark parts are used as a display function mark...

Page 15: ...e Connect the hose of the discharge side to an evacuated cylinder to recover all refrigerant in the recycle unit and the hose 4 Refrigerant Discharge Purge Procedure Operation time Suction Discharge rs of t ed kg MED RESOLUTION Cylinder Scale OPEN Liquid valve CLOSE Vapor valve Cylinder Manifold CLOSE Ball valve OPEN Ball valve Suction Valve PURGE Switching Valve OPEN Discharge Valve 2 CLOSE CLOSE...

Page 16: ...Open the valve slowly and discharge the oil into another container The oil tank capacity is 2L Close the valve and cap of Oil Discharge Port after discharging the oil Check every 100 hours of operation for any oil or contamination in the Electrostatic Filter System Oil Discharge Procedure Oil Separator Oil Discharge Procedure Electrostatic Filter System Oil Discharge Port for Oil Separator Force S...

Page 17: ...ve SLOWLY OPEN 6 At 0 2MPa 29psi Maintain 4 AutoShut off 2 Auto Shut off Manual Connect hoses as above after carry out Page 9 2 Evacuation of the recycle unit and the hoses Set the Auto Shut off Manual Mode Setting to Auto Shut OFF position Set Power Switch to ON position Adjust suction pressure around 0 2MPa 29psi by opening the ball valve of the suction hose from the manifold and keep operating u...

Page 18: ... Stop Timer R32 R134a Every 40 hours every other automatic stop by Auto Stop Timer Replace Filter TF011 together with Molecular Sieve at the same time Prepare Molecular Sieve Replacement Kit AR338 and replace three Filters and Molecular Sieve Two O rings will be replaced later on Set Mesh Plate and Spring in Dry Filter Cartridge and close the lid Properly set two new O rings from AR338 on Dry Filt...

Page 19: ...er surface of each hose Confirm that all gaskets on the hoses are worn or exhausted Confirm the unit starts normally when Power Switch is turned on Confirm the unit stops when Power Switch is turned off Inspection in General Periodically inspect and clean the unit according to following Please correct or replace if necessary INSPECTION BEFORE WORK Remove cap of Suction Port and Discharge Port Turn...

Page 20: ...e High Pressure Shut off function makes the unit stop automatically and Warning Lamp is turned on Inspection of High Pressure Switch Function Lighting 4 Warning Lamp Refrigerant Recycle Equipment RR 220 RR 220 Refrigerant Recycle Equipment Refrigerant Recycle Equipment Remove cap of Suction Port and Discharge Port Turn Suction Valve V1 to OPEN position Turn Switching Valve V2 to RECYCLE position T...

Page 21: ... the above referenced product is in conformity with the provisions of the following standards and is in accordance with the following directives Applicable Directives 2014 30 EU EMC 2014 35 EU LVD 2011 65 EU RoHS2 Applicable Standards EN61000 6 2 2005 EMC EN61000 6 3 2007 A1 2011 EMC EN60335 1 2012 A11 2014 LVD IEC60335 2 104 2003 LVD CE Implementation Date July 01 2019 Manufacturer LOADING UNLOAD...

Page 22: ...he unit does not recycle The suction hose is connected to the vapor port Connect it to the liquid port Filter TF011 is clogged Clean or replace Filter TF011 The pressure in the cylinder to be charged is high Cool the cylinder The hose has a core depressor Remove the core depressor in the hose The refrigerant in the cylinder is condensing at low temperature Wait until operating temperature is reach...

Page 23: ... switch is out of order Repair The purity of the recycled refrigerants is not good enough Molecular Sieve is contaminated Replace Molecular Sieve Replacement Kit AR338 referring to page 17 and Filter TF011 The O ring in Dry Filter Housing is damaged Replace Molecular Sieve Replacement Kit AR338 referring to page 17 Refrigerants leak from the unit The charging hose and the hose gasket are not in go...

Page 24: ...ressure Switch Safety Relief Valve Check Valve Purge Recycle Purge Molecular Sieve Low Pressure Switch Compressor Condenser Suction Pressure Gauge Low Electrostatic Filter System Oil Separator Double Pipe Heat Exchanger Discharge Port Open V1 V2 V3 Bold line Oil discharge line Solid line Piping Dry Filter Sight Glass User installs Filter User installs Discharge Pressure Gauge High PIPING DIAGRAM ...

Page 25: ...itch Compressor Condenser Suction Pressure Gauge Low Discharge Pressure Gauge High Electrostatic Filter System Oil Separator Double Pipe Heat Exchanger Discharge Port Open V1 V2 V3 Dry Filter Valve close Valve open Bold line Oil discharge line Solid line Refrigerant recycle line Dashed line Line not related to recycle Sight Glass User installs Filter User installs Oil Discharge Port for Electrosta...

Page 26: ...ow Pressure Switch Compressor Condenser Suction Pressure Gauge Low Electrostatic Filter System Oil Separator Double Pipe Heat Exchanger Discharge Port Open V1 V2 V3 Dry Filter Valve close Valve open Bold line Oil discharge line Solid line Dashed line Line unrelated to purge flow Purge flow line Sight Glass User installs Filter User installs Discharge Pressure Gauge High Oil Discharge Port for Electr...

Page 27: ...26 RRDQ220V1 ...

Page 28: ...Zandvoordestraat 300 8400 Oostende Belgium IM0496 Ver 01 10 July 2019 Copyright 2019 DAIKIN ...