Installation manual

11

RR+RQ71+10 RR+RQ7 RR+RQ71~12

RR+RQ71B2W1B

Split System air conditioners

4PW23689-1C

When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the knock-out hole.

(See figure 6)

When you do not use a wire conduit, be sure to protect the wires
with vinyl tubes to prevent the edge of the knock-out hole from
cutting the wires.

Follow the electric wiring diagram for electrical wiring works.

Form the wires and fix the cover firmly so that the cover may be
fit in properly.

Precautions on wiring of power supply and inter-unit wiring

Use a round crimp-style terminal for
connection to the power supply terminal
board. In case it cannot be used due to
unavoidable reasons, be sure to
observe the following instruction.
-

Do not connect wires of different 
gauge to the same power supply terminal. (Looseness in the 
connection may cause overheating.)

-

When connecting wires of the same gauge, connect them 
according to the figure below.

Use the correct screwdriver to tighten the terminal screws.
Small screwdrivers can damage the screw head and prevent
appropriate tightening.

Over-tightening the terminal screws can damage the screws.

See the table below for tightening torques for the terminal
screws.

Refer to the installation manual attached to the indoor unit for
wiring of indoor units, etc.

Attach an earth leakage breaker and fuse to the power supply
line. 

(See figure 8)

In wiring, make certain that prescribed wires are used, carry out
complete connections, and fix the wires so that outside forces
are not applied to the terminals.

Specifications of standard wiring components

Point for attention regarding quality of the public electric power
supply

This equipment complies with EN/IEC 61000-3-11

(1)

  provided that

the system impedance Z

sys

  is less than or equal to Z

max

  at the

interface point between the user's supply and the public system. It is
the responsibility of the installer or user of the equipment to ensure,
by  consultation with the distribution network operator if necessary,
that the equipment is connected only to a supply with a system
impedance Z

sys

 less than or equal to Z

max

.

A

Inside

B

Outside

1

Wire

2

Bush

3

Nut

4

Frame

5

Hose

Tightening torque (N•m)

M4

(X1M)

1.2~1.8

M5

(X1M)

2.0~3.0

M5

(EARTH)

3.0~4.0

I

Pair

II

Twin

III

Triple

M

Master

S

Slave

1

Earth leakage breaker

2

Fuse

3

Remote controller

Power supply

Model

Field 

fuse 

Wire type

(1)

(1) Only in protected pipes, use H07RN-F when protected pipes are not used.

Size

Wire type 

of wiring 

between the 

units

RR71B8V3B

32 A

H05VV-U3G

Wiring size 

must comply 

with the 

applicable 

local and 

national code

H05VV-U4G2.5

RR71B2V3B

RQ71B8V3B

RQ71B2V3B

RR100B8V3B

40 A

RQ100B8V3B

RR71B8W1B

16 A

H05VV-U5G

RR71B2W1B

RQ71B8W1B

RQ71B2W1B

RR100B8W1B

RQ100B8W1B

RR125B8W1B

20 A

RQ125B8W1B

(1) European/International Technical Standard setting the limits for voltage 

changes, voltage fluctuations and flicker in public low-voltage supply 
systems for equipment with rated current 

75 A.

Z

max

 (

)

RR71B8V3B

0.07

Equipment complying with 

EN/IEC 61000-3-12

(1)

(1) European/International Technical Standard setting the limits for harmonic 

currents produced by equipment connected to public low-voltage systems 
with input current >16 A and 

75 A per phase.

RR71B2V3B

0.07

RR100B8V3B

0.04

RQ71B8V3B

0.07

RQ71B2V3B

0.07

RQ100B8V3B

0.04

RR71B8W1B

0.41

RR71B2W1B

0.41

RR100B8W1B

0.36

RR125B8W1B

0.31

RQ71B8W1B

0.41

RQ71B2W1B

0.41

RQ100B8W1B

0.36

RQ125B8W1B

0.31

Summary of Contents for RQ100B8V3B

Page 1: ...INSTALLATION MANUAL RR71B8V3B RR71B2V3B RR100B8V3B RR71B8W1B RR71B2W1B RR100B8W1B RR125B8W1B RQ71B8V3B RQ71B2V3B RQ100B8V3B RQ71B8W1B RQ71B2W1B RQ100B8W1B RQ125B8W1B Split System air conditioners...

Page 2: ...1 2 4 5 2 4 5 9 7 6 6 8 3 3 1 3 2 4 5 A B A E B C D H H1 L1 H1 H2 L3 L1 L2 H1 H2 L4 L1 L3 L2 A A B2 B2 B2 C C D1 D1 D1 D2 D2 D2 D2 D2 E E H H L1 L1 L1 L2 L2 L2 A A B1 B1 B1 B1 B1 B1 B2 B2 B2 C C D1 D1...

Page 3: ...ttaen m r yksi 14 za dodr en ustanoven p edpisu 15 prema odredbama 16 k veti a z 17 zgodnie z postanowieniami Dyrektyw 18 n urma prevederilor 19 ob upo tevanju dolo b 20 vastavalt n uetele 21 22 laika...

Page 4: ...the power supply circuit or improper electrical construction may lead to electric shocks or fire Make sure that all wiring is secure using the specified wires and ensuring that external forces do not...

Page 5: ...contains high levels of salt such as that near the ocean Where voltage fluctuates a lot such as that in factories In vehicles or vessels Where acidic or alkaline vapour is present BEFORE INSTALLATION...

Page 6: ...e please install a waterproof plate within 150 mm of the underside of the unit in order to prevent the invasion of water from the lower direction 6 When installing the unit in a place frequently expos...

Page 7: ...ld comply with relevant local and national regulations The minimal pipe thickness for R410A piping must be in accordance with the table below O Annealed 1 2H Half hard Suction side obstacle Obstacle i...

Page 8: ...piping kit Install the branch pipes horizontally with a maximum inclination of 15 or vertically Length of branch pipe to the indoor unit should be as short as possible Try to keep lengths of both bra...

Page 9: ...e deformed if only a torque wrench is used when loosening or tightening flare nuts always lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do...

Page 10: ...t coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before tightening firmly After completing the installation carry out a gas leak inspection of the...

Page 11: ...rs and bring the system to 100 7 kPa After keeping the system under that condition for more than one hour check if the vacuum gauge rises or not If it rises the system may either contain moisture insi...

Page 12: ...mount R R1 R2 1 00 0 30 1 30 kg Example 2 1 G1 L1 5 m G2 L2 L3 L4 17 17 20 54 2 Over 30 m a G1 5 m R1 0 0 kg b G1 G2 30 5 54 30 29 6 4 R2 0 90 kg 3 Refrigerant charge amount R R1 R2 0 0 0 9 0 9 kg Tot...

Page 13: ...ground wire to the shut off valve attachment plate so that it does not slide 2 Secure the ground wire to the shut off valve attachment plate one more time along with the electric wiring and the inter...

Page 14: ...d wiring components Point for attention regarding quality of the public electric power supply This equipment complies with EN IEC 61000 3 11 1 provided that the system impedance Zsys is less than or e...

Page 15: ...For a missing phase in case of W1 units E0 or E6 will be displayed on the remote controller of the indoor unit Operation will be impossible with either one of these phenomena If this happens turn off...

Page 16: ...Q2M Thermo switch M1F M2F Q1RP Phase reverse circuit R1T Thermistor air R2T Thermistor coil R3T Thermistor discharge RC Signal receiver circuit S1PH Pressure switch HIGH S1PL Pressure switch LOW SD S...