FA ROTEX A1 BOe - 02/2014
4
x
Set-up and installation
The cross-section of the installation shaft must be sized so
that
between the external wall of the flue gas line
and the
internal face of the installation shaft
the following
mini-
mum distance
must be maintained:
– with a rectangular shaft cross-section:
2 cm
– with round shaft cross-section:
3 cm
.
The rear ventilation opening must not be in rooms where a
positive pressure is generated (e.g. by controlled apartment
ventilation, a tumble-drier etc.).
Ɣ
Pull off the air supply hose at the air supply connecting
manifold of the boiler body and connect the separate air
supply line.
Set-up version 3
– The combustible air supply from the outside runs through a
separate air supply line through the external wall.
– The flue gas discharge to the outside runs through the chim-
ney or through an installation shaft (as in set-up version 1).
Set-up version 8
The ROTEX A1 BO is connected by the
SET A
or
SET B
to a
ceramic chimney.
– The combustible air supply from the outside runs through a
separate air supply line through the external wall.
– Ceramic chimney for flue gas removal must be moisture-
insensitive (Class W) and suitable for overpressure operation
(Class P1 or H1), as well as having an appropriate construc-
tional approval or CE approval with a declaration of conform-
ity.
– If the ceramic chimney for the flue gas discharge does not
have an approval for overpressure operation, it must be pos-
sible to prove, using a flue gas calculation, that there is neg-
ative pressure in the shaft when the flue gas enters.
4.2.3 Ambient air dependent operation
The ROTEX A1 BO can also be connected in a manner de-
pendent on ambient air. Thereby, only the inner flue gas pipe
(plastic pipe Ø 80 mm) of the concentric air-flue gas pipe is con-
nected to the flue gas line. The device sucks the combustible air
from the installation room through the ring-shaped gap of the
jacket pipe.
For the flue gas routing to the outdoors, the shaft sizing and the
rear ventilation, the same conditions apply as in section 4.2.2.
A
ventilation opening
to the outside of
150 cm
2
is
imperative
.
Set-up version 2
– Combustion air supply from the installation room.
– Flue gas dissipation to the outdoors is via the chimney or an
installation shaft (such as Set-up version 1).
Set-up version 7
The ROTEX A1 BO is connected by the
SET A
or
SET B
to a
ceramic chimney.
– Combustion air supply from the installation room.
– Ceramic chimney for flue gas removal must be moisture-
insensitive (Class W) and suitable for overpressure operation
(Class P1 or H1), as well as having an appropriate construc-
tional approval or CE approval with a declaration of conform-
ity.
– If the ceramic chimney for the flue gas discharge does not
have an approval for overpressure operation, it must be pos-
sible to prove, using a flue gas calculation, that there is neg-
ative pressure in the shaft when the flue gas enters.
4.3 Transport and delivery
The ROTEX A1 BO is delivered on a pallet. All industrial trucks,
such as lifting trucks and forklift trucks, are suitable for trans-
porting it.
Scope of delivery
– ROTEX A1 BO (preassembled),
– Document pack,
– Toolkit (cleaning brush and scraper, burner chamber span-
ner, hexagonal spanner for burner and heat exchanger,
burner setting gauge).
Recommended accessory
– Safety group (
SGB A1,
15 60 18
) with pressure gauge,
safety valve, automatic bleeding, filling cock, connection fit-
tings).
– Connection kit A1 (
VSA1,
15 48 22
), for hydraulic con-
nection of a heat exchanger (storage tank temperature sen-
sor, 3-way diverter valve with actuating motor, connection fit-
tings).
– External temperature sensor (
RoCon OT1,
15 60 70
), for
weather-controlled regulation.
Additional accessories see ROTEX price list.
In some cases, the resonance in the flue system can
amplify the noise at the mouth of the flue gas pipe. The
noise level can be effectively reduced with the applica-
tion of a silencer (
E8 MSD,
15 45 78
bzw.
E11 MSD,
15 45 79
).
Air suction noises are generated during ambient air-
dependent operation. The noise level can be effectively
reduced with the application of a silencer (
G ZLSD,
15 45 77
).
CAUTION!
Lifting or pushing the Oil condensing boiler on the
cladding can damage the unit.
Ɣ
Lift the ROTEX A1 BO only on the carrying straps
provided for this purpose.