5.2.4 Level "DHW Configuration"
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Circl-Pump DHW
Setting for activating a circulation pump.
Off: Optional circulation pump operates according to the timer programme [Circulation Time].
On: The optional circulation pump operates synchronously with the switching timer program
activated for generation of hot water.
E
E
Off
On
Off
-
Circl-Pump Interval
Setting the interval control for an optional circulation pump.
Off: Deactivated The circulation pump operates continuously throughout the enabled time of
the assigned switching timer program (parameter [Circl-Pump DHW]).
Otherwise: The circulation pump runs cyclically (duty ratio: pump running time = set value eve-
ry 15 min).
E
E
Off,
1 - 15 min
Off
1 min
Anti-Legionella day
Setting the day for the thermal disinfection of the circulating tank.
Off: No thermal disinfection
Monday - Sunday Day for thermal disinfection
Mon - Sun: Daily thermal disinfection
E
E
Off,
Monday
...
Sunday,
Mon - Sun
Off
-
Anti-Legionella time Setting the start time of the thermal disinfection of the hot water circulating tank (format
hh:mm).
N
E
00:00 - 23:45
03:30
15 min
Anti-Legionella temp Setting the hot water target temperature during thermal disinfection of the hot water circulating
tank (format hh:mm).
N
E
60 - 70 °C
65 °C
1 °C
Max DHW loading
time
Setting limits the time period for hot water generation to the set target value [T-DHW Setpoint].
After expiry of this time period, the controller automatically returns to the previously active op-
erating mode. The hot water generation takes place at the actual set value.
N
E
0 - 240 min
60 min
10 min
DHW Off Time
Setting the block time following completion or interruption of a hot water generation cycle. New
demand of hot water generation is satisfied only after expiry of this block time.
N
E
0 - 180 min
30 min
10 min
Tab. 5-4 Parameter in rotary switch setting "Configuration" level "DHW Configuration"
5.3
Rotary switch setting: DHW Install
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
1x Hot Water
Start of the one-off heating up of the hot water and the set value [T-DHW Setpoint 1], inde-
pendent of the heating programmes.
E
E
Off
On
Off
-
Hyst HP
Switching threshold hot water charging
Setting of the temperature difference to which the temperature in the domestic hot water stor-
age tank compared to the current target hot water temperature [T-DHW Setpoint] can drop be-
fore the heat pump is switched on to provide hot water.
E
E
2 - 20 K
5 K
1 K
Timer BOH
Delay time after which the reserve heating may support the heat pump in hot water charging
(see chapter 3.6.7).
E
E
20 - 95 min
50 min
1 min
Tab. 5-5 Parameter in rotary switch setting "DHW Install"
5.4
Rotary switch setting: Operating Mode
Parameter
Designation
Access
Setting range
Min / Max
Factory
setting
Increment
BE
HF
Standby
In this operating mode, all internal functions are turned off. Frost protection remains active and
a blocking protection for the pump is guaranteed.
All controllers integrated in the RoCon system via the CAN bus are also switched at a higher
level to the operating mode when this setting is selected.
Outputs are not always free of voltage.
E
E
-
Reducing
The internal heating circuit provides continuous (24 h per day) regulation to the parametrised
setback temperature. The hot water generation takes place according to [DHW Program 1].
E
E
-
Heating
The internal heating circuit provides continuous (24 h per day) regulation to the parametrised
day set room temperature (heating). The hot water generation takes place according to
[DHW Program 1].
E
E
-
Cooling
The internal heating circuit provides continuous (24 h per day) regulation to the parametrised
day room temperature set (cooling). The hot water generation takes place according to
[DHW Program 1].
Frost protection remains active and a blocking protection for the pump is guaranteed.
E
E
-
Summer
The internal heating circuit is turned off. Frost protection remains active and a blocking
protection for the pump is guaranteed. The hot water generation takes place according to
[DHW Program 1].
All controllers integrated in the RoCon system via the CAN bus are also switched at a higher
level to the operating mode when this setting is selected.
E
E
-
Automatic 1
The internal heating circuit regulates according to the parametrised timer programme [HC Pro-
gram 1] with the individual day room temperatures set. The hot water generation takes place
according to [DHW Program 1].
E
E
-
Automatic 2
The internal heating circuit regulates according to the parametrised timer programme [HC Pro-
gram 2] with the individual day room temperatures set. The hot water generation takes place
according to [DHW Program 2].
E
E
-
Tab. 5-6 Parameter in rotary switch setting "Operating Mode"