Parameter settings
Daikin RoCon HP
Daikin Control
008.1420844 – 05/2014
Operating instructions
33
Air Purge
Activation of automatic bleeding of the Daikin Altherma EHS(X/H) and the connected
heating circuit (see chapter 3.6.10).
Off: Deactivated
On: Start of Air Purge
N
E
Off
On
Off
-
PWM Config
Max Perform Pump
Upper limit for modulation of the pump output
N
E
20 - 100 %
100 %
1 %
Min Perform Pump
Lower limit for modulation of the pump output
N
E
10 - 100 %
50 %
1 %
Sensor Config
Outside Config
Configuration of the optional external temperature sensor RoCon OT1:
Off: No sensor evaluation
On: Sensor evaluation activates (if an outdoor temperature sensor is not connected, a
fault message is generated.)
N
E
Off
On
Off
-
Storage Config
Configuration of water heating:
inactive; no function for hot water generation.
Sensor: Function for hot water generation is activated. A circulating tank temperature
sensor is evaluated for hot water generation (if no circulating tank temperature sensor is
connected, a fault message is generated).
Thermostat: Function for hot water generation is activated. A thermostatic switch (On /
Off) is evaluated for hot water generation, and where "Open brackets" are evaluated as
"No demand".
N
E
Inactive
Sensor
Thermostat
Sensor
-
Pressure Config
Configuring the sensor for assessment of the system water pressure:
Off: No sensor evaluation
On: Sensor evaluation activated (if no pressure sensor is connected, a fault message is
generated.)
N
E
Off
On
On
-
Outside Temp Adap Individual adapting for the measured value of the outdoor temperature relevant for the
Control.
N
E
-5.0 to +5.0 K
0.0 K
0.1 K
Terminaladress
Setting the data bus address for system access. The set value must be applicable for the
entire system. Confirmation of this parameter using the rotary switch reinitialises the con-
troller.
N
E
Off, 0 - 9
Off
1
System Config
System configuration of the unit, consisting of the sensor configuration and bus configu-
ration. If you answer "Yes" to the enquiry about using the standard configuration when
starting the unit for the first time, the basic configuration for the installed heat generator
will be activated automatically.
Confirmation of this parameter setting as
"Inactive"
or
"Delete"
using the rotary switch
reinitialises the controller. A fault message follows. After this the rotary switch must be
set to the position
"Info"
. Use the rotary switch to select the required menu item.
N
E
Inactive
Active
Delete
Active
-
HC Assignment
Display only on connected
room station:
Allocation of the room station to the heating circuit to be operated.
The direct heating circuit of the Daikin Altherma EHS(X/H) is set as standard to "0"
(see section 5.12, parameter [Unmixed Circ Config])
N
E
Off, 0 - 15
Off
1
Tab. 5-1 Parameter in rotary switch setting "Configuration" level "Setup"
Sub-
le
vel
Parameter
Description
Access
Setting range
Min / Max
Factory
setting
Increment
BE