background image

Installation manual

17

RMXS112~160D7V3B

Super Multi Plus System air conditioner

4PW19516-1B

Error codes on the remote controller:

11.5. Temperature adjustment operation confirmation

After the test run is over, operate the unit normally. (Heating is not
possible if the outdoor temperature is 24°C or higher.)

Make sure the indoor and outdoor units are operating normally
(If a knocking sound can be heard in the liquid compression of
the compressor, stop the unit immediately and then energize the
heater for a sufficient length of time before restarting the
operation.)

Run each indoor unit one at a time and make sure the
corresponding outdoor unit is also running.

Check to see if cold (or hot) air is coming out of the indoor unit.

Press the fan direction and fan strength buttons on the indoor
unit to see if they operate properly.

12. S

ERVICE

 

MODE

 

OPERATION

After turning on the power supply, the unit can not be started untill the
H2P initialisation led, indicating that the unit stil is under preparation,
goes off (maximum 12 minutes).

Vacuuming method

At the first installation, this vacuuming is not required. It is required
only for repair purposes.

1

When the unit is at standstill and under the setting mode 2, set
the required function B (refrigerant recovery operation/
vacuuming operation) to 

 (ON).

-

After this is set, do not reset the setting mode 2 until the 
vacuuming is finished.

-

The H1P led is on and the remote controller indicates 

 

(test operation) and 

 (external control) and the 

operation will be prohibited.

2

Vacuum the system with a vacuum pump.

3

Press the 

 button and reset the setting mode 2.

Refrigerant recovery operation method 

by a refrigerant reclaimer.

1

When the unit is at standstill and in setting mode 2, set the
required function B (refrigerant recovery operation/vacuuming
operation) to 

 (ON).

-

Expansion valves of BP unit and outdoor unit will fully open 
and some solenoid valves will open.

-

The H1P led is on and the remote controller indicates 

 

(test operation) and 

 (external control) and the 

operation will be prohibited.

2

Cut off the power supply to the BP units and the outdoor unit
with the circuit breaker. After the power supply to one side is cut
off, cut off the power supply to the other side within 10 minutes.
Otherwise, the communication between the BP unit and outdoor
unit may become abnormal and the expansion valves will be
completely closed again.

3

Recover the refrigerant using a refrigerant reclaimer. For details,
see the operation manual delivered with the refrigerant
reclaimer.

Installation error

Malfunction 

code

Remedial action

The stop valve of an 
outdoor unit is left 
closed.

E3

Open the stop valve on both the gas 
and liquid side.

Refrigerant overcharge

Recalculate the required amount of 
refrigerant from the piping length and 
correct the refrigerant charge level by 
recovering any excessive refrigerant 
with a refrigerant recovery machine.

The stop valve of an 
outdoor unit is left 
closed.

E4
F3

Open the stop valve on both the gas 
and liquid side.

The operation mode on 
the remote controller 
was changed before the 
check run.

Set the operating mode on all indoor 
unit remote controllers to "cooling".

Insufficient refrigerant

Check if the additional refrigerant 
charge has been finished correctly.
Recalculate the required amount of 
refrigerant from the piping length and 
add an adequate amount of refrigerant.

Refrigerant overcharge

F6

Recalculate the required amount of 
refrigerant from the piping length and 
correct the refrigerant charge level by 
recovering any excessive refrigerant 
with a refrigerant recovery machine.

The check operation is 
not performed.

U3

Perform the check operation.

No power is supplied to 
the BP unit.

U4

Check if the power wiring for the BP unit 
is connected correctly.

Incorrect transmission 
wiring between indoor 
unit and BP unit.

Connect the interconnections (1, 2, 3) 
between indoor unit and BP unit 
correctly.

Improper type of indoor 
units or BP units are 
connected.

UA

Check the type of indoor units and BP 
units that are currently connected. If 
they are not proper, replace them with 
proper ones.

The piping and wiring of 
the specified indoor unit 
are not connected 
correctly to the BP unit.

UF

Confirm that the piping and wiring of the 
specified indoor unit are connected 
correctly to the BP unit.

Incorrect transmission 
wiring between outdoor 
unit and BP unit(s).

UJ

Connect interconnections F1 and F2 of 
the connected BP unit correctly to the 
outdoor unit's PC board (TO BP UNIT)

UH

Wiring of the connected BP unit is 
correct, but interconnections F1 and F2 
of other BP unit(s) need to be 
connected correctly to the outdoor unit's 
PC board (TO BP UNIT).

Cautions for normal operation check

Once stopping, the compressor will not restart in
about 5 minutes even if the Run/Stop button of an
indoor unit in the same system is pressed.

When the system operation is stopped by the remote
controller, the outdoor units may continue operating
for further 5 minutes at maximum.

After the test run, when handling the unit over to the
customer, make sure the electric box lid, the service
lid and the unit casing are all attached properly.

ON

BS1  MODE

ON

Summary of Contents for RMXS112D7V3B

Page 1: ...INSTALLATION MANUAL RMXS112D7V3B RMXS140D7V3B RMXS160D7V3B System air conditioner Super Multi Plus ...

Page 2: ...0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 1000 1000 1000 1000 500 500 1000 500 1000 1000 300 300 300 250 300 300 500 200 1000 1000 1000 1000 1000 1250 1500 1500 1000 1000 100 5 4 4 3 2 1 7 8 9 10 A D C B 5 6 11 7 2 1 6 1 2 3 4 5 6 7 9 8 12 13 10 1...

Page 3: ...8 2 1 1 1 2 3 4 4 1 50 Hz 1 50 Hz 8 NOTES ...

Page 4: ...11 11 9 16 V 230 V 230 V 1 2 3 2 3 4 1 4 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 4 5 7 1 2 2 C H SELECTOR TO BP UNIT TO OUT D UNIT A1P 3 13 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N 14 1 2 3 4 5 4 6 12 F1 F2 1 E 3 2 4 5 A 1 3 2 5 B E 1 2 4 3 5 C E E 1 2 3 4 D E 9 10 11 15 12 13 14 ...

Page 5: ...rd e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 20 on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele 21 съответстват на следните стандарт...

Page 6: ...NSIDERATIONS The precautions listed here are divided into the following two types Both cover very important topics so be sure to follow them carefully RMXS112D7V3B RMXS140D7V3B RMXS160D7V3B System air conditioner Installation manual Super Multi Plus READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQ...

Page 7: ...all drain piping according to this installation manual to ensure good drainage and insulate the pipe to prevent condensation Improper drain piping may cause water leakage and make the furnitures get wet Install the indoor units BP units and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depending on the radio wav...

Page 8: ...th the discharge pipe thermister R3T suction pipe thermister R2T and pressure sensors S1NPH S1NPL removed Such operation may burn out the compressor Be sure to confirm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the tightening torque does not exceed 4 1 N m 3 3 Handling As shown in t...

Page 9: ...talling the unit in a place frequently exposed to snow pay special attention to the following Elevate the foundation as high as possible Remove the rear suction grille to prevent snow from accumulating on the rear fins 7 If you install the unit on a building frame please install a waterproof plate within 150 mm of the underside of the unit or use a drain plug kit option in order to avoid the drain...

Page 10: ...downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case of non stacked installation See figure 4 B In case of stacked installation 1 In case obstacles exist in front of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installi...

Page 11: ...er to 9 3 How to use the shut off valve on page 8 Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant to leak Always use the supplied copper gasket when connecting the gas pipe supplied with the unit See 9 Refrigerant piping on page 7 8 1 Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying out nitrogen repl...

Page 12: ... the figure Since the side boards may be deformed if only a torque wrench is used when loosening or tightening flare nuts always lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak Pipe size Tightening Torque N m A mm Flare shape Ø9 5 32 7 39 9 12 8 13 2 Ø15 9 61 8 75...

Page 13: ...t and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as shown in the figure below Also make sure the field piping does not touch the bolts or outer panels of the compressor When the outdoor unit is installed above the BP unit and indoor unit the following can occur The condensated wat...

Page 14: ...kit 5 m Example a 5 m Allowable height Between outdoor and indoor units Difference in height Difference in height between outdoor and indoor units H1 30 m Between outdoor and BP units Difference in height Difference in height between outdoor and BP units H2 30 m Between BP and BP units Difference in height Difference in height between BP and BP units H3 15 m Between indoor and indoor units Differe...

Page 15: ... 1 hour confirm that the vacuum gauge does not rise 9 9 Additional refrigerant charge See figure 6 Pipe size selection How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in units of 0 1 kg Piping size outer diameter x minimum thickness Symbol Gas pipe Liquid pipe Between outdoor and first refrigerant branch kit a Ø19 1x1 0 Ø9...

Page 16: ...stops within 30 minutes If the refrigerant charge cannot be finished within 30 minutes repeat step 2 If the operation stops immediately after restart there is a possibility that the system is overcharged The refrigerant cannot be charged more than this amount 4 After the refrigerant charge hose is removed make sure to fully open the liquid stop valve Otherwise the piping may burst due to blocked l...

Page 17: ...d lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which will have to be discharged with the grounding 10 3 Conn...

Page 18: ...frequency Voltage Recommended fuses Transmission line section RMXS112 1 N 50 Hz 230 V 32 A 0 75 1 25 mm2 RMXS140 RMXS160 NOTE Select the power supply cable in accordance with relevant local and national regulations Wire size must comply with the applicable local and national code Specifications for local wiring power cord and branch wiring are in compliance with IEC60245 WIRE TYPE H05VV Only in pr...

Page 19: ...0 m Total wiring length 300 m Maximum No of branches 9 Never connect the power supply to unit to unit cabling terminal block Otherwise the entire system may break down 1 Liquid pipe 2 Gas pipe 3 Interconnecting wiring 4 Insulator 5 Finishing tape WARNING ELECTRIC SHOCK Caution when performing service to inverter equipment Do not touch live parts for 10 minutes after the power supply is turned off ...

Page 20: ... A1P The figure shows state of the led indications when the unit is shipped from the factory Setting the mode The set mode can be changed with the button according to the following procedure For setting mode 1 Press the button once the led is off For setting mode 2 Press the button for 5 seconds the H1P led is on If the H1P led is blinking and the button is pushed once it will change to setting mo...

Page 21: ... items are automatically checked Check for miswiring Check if stop valves are open Check of refrigerant charge Automatic judgement of piping length 4 After the test operation maximum 30 minutes the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller 2 Corre...

Page 22: ...ration manual delivered with the refrigerant reclaimer Installation error Malfunction code Remedial action The stop valve of an outdoor unit is left closed E3 Open the stop valve on both the gas and liquid side Refrigerant overcharge Recalculate the required amount of refrigerant from the piping length and correct the refrigerant charge level by recovering any excessive refrigerant with a refriger...

Page 23: ...allest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result fall...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN19516 1B ...

Reviews: