RMXS112~160D7V3B
Super Multi Plus System air conditioner
4PW19516-1B

Installation manual

14

Performing cool/heat setting with the cool/heat selector

Connect the cool/heat selector remote controller (optional) to the A/
B/C terminals and set the cool/heat selector switch (DS1) on the
outdoor unit PC board (A1P) to OUT/D UNIT. 

(See figure 13)

.

The wiring from the BP units must be connected to the F1/F2
(In-Out) terminals on the PC board in the outdoor unit.

After installing the interconnecting wires inside the unit, wrap
them along with the on-site refrigerant pipes using finishing
tape, as shown in 

figure 14

.

For the above wiring, always use vinyl cords with 0.75 to 1.25 mm

2

sheath or cables (2 core wires). (3 core wire cables are allowable for
the cooler/heater changeover remote controller only.)

11. B

EFORE

 

OPERATION

11.1. Service precautions

11.2. Checks before initial start-up

After the installation, check the following before switching on the
circuit breaker:

1

Transportation fittings

Be sure that the transportation fittings are removed from the
compressor.

2

The position of the switches that require an initial setting

Make sure that switches are set according to your application
needs before turning the power supply on.

1

Cool/heat selector

For low-noise operation, it is necessary to get the optional
'External control adaptor for outdoor unit' (DTA104A61/62).

For details, see the installation manual attached to the
adaptor.

Be sure to follow the limits below. If the unit-to-unit
cables are beyond these limits, it may result in
malfunction of transmission.
Maximum wiring length: 200 m
Total wiring length: 300 m
Maximum No. of branches: 9

Never connect the power supply to unit-to-unit cabling
terminal block. Otherwise the entire system may
break down.

1

Liquid pipe

2

Gas pipe

3

Interconnecting wiring

4

Insulator

5

Finishing tape

WARNING: ELECTRIC SHOCK 

Caution when performing service to inverter
equipment

Do not touch live parts for 10 minutes after the power
supply is turned off because of high voltage risk.

Additionaly, measure the points as shown in the figure
with a tester and confirm that the voltage of the
capacitor in the main circuit is no more than 50 V DC.

Make sure that the power supply is turned off before
performing the maintenance work. The heater of the
compressor may operate even in stop mode.

Please note that some sections of the electric
component box are extremely hot.

In order to prevent damage to the PCB, first eliminate
static electricity by touching a metal part (e.g. stop
valve) with your hand. Then pull out the connector.

After measuring the residual voltage, pull out the
outdoor fan connector.

Make sure you do not touch a conductive section.

The outdoor fan may rotate due to strong backblow
wind, causing the capacitor to charge. This may result
in an electric shock.

After maintenance, make sure the outdoor fan connector is
connected again. Otherwise, the unit may break down.

Play it safe!

Touch a metal part by hand (such as the stop valve) in
order to eliminate static electricity and to protect the PCB
before performing service.

Make sure that the circuit breaker on the power supply
panel of the installation is switched off.

Attach the power wire securely.

Introducing power with a missing N-phase or with a
mistaken N-phase will break the equipment.

C+ C-

A3P

A2P

L1R

B

1

A

B

1

Fan connections of outdoor unit

A

Front view

B

View B

Summary of Contents for RMXS112D7V3B

Page 1: ...INSTALLATION MANUAL RMXS112D7V3B RMXS140D7V3B RMXS160D7V3B System air conditioner Super Multi Plus ...

Page 2: ...0 L2 1 2 H 1 2 H L2 H 0 L1 1 2 H 1 2 H L1 H 0 L2 1 2 H 1 2 H L2 H L2 H L2 H L2 H L2 H L2 H L2 H 150 500 500 500 500 750 100 100 100 100 200 300 200 100 250 250 500 1000 1000 1000 500 500 500 500 1000 1000 1000 1000 500 500 1000 500 1000 1000 300 300 300 250 300 300 500 200 1000 1000 1000 1000 1000 1250 1500 1500 1000 1000 100 5 4 4 3 2 1 7 8 9 10 A D C B 5 6 11 7 2 1 6 1 2 3 4 5 6 7 9 8 12 13 10 1...

Page 3: ...8 2 1 1 1 2 3 4 4 1 50 Hz 1 50 Hz 8 NOTES ...

Page 4: ...11 11 9 16 V 230 V 230 V 1 2 3 2 3 4 1 4 5 A B C A B C F1 F1 F2 F2 F1 F2 F1 F2 4 5 7 1 2 2 C H SELECTOR TO BP UNIT TO OUT D UNIT A1P 3 13 A B C A B C 1 DS1 1 2 3 4 OFF ON O U T I N 14 1 2 3 4 5 4 6 12 F1 F2 1 E 3 2 4 5 A 1 3 2 5 B E 1 2 4 3 5 C E E 1 2 3 4 D E 9 10 11 15 12 13 14 ...

Page 5: ...rd e sau alt e document e normativ e cu condiţia ca acestea să fie utilizate în conformitate cu instrucţiunile noastre 19 skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z našimi navodili 20 on vastavuses järgmis t e standardi te ga või teiste normatiivsete dokumentidega kui neid kasutatakse vastavalt meie juhenditele 21 съответстват на следните стандарт...

Page 6: ...NSIDERATIONS The precautions listed here are divided into the following two types Both cover very important topics so be sure to follow them carefully RMXS112D7V3B RMXS140D7V3B RMXS160D7V3B System air conditioner Installation manual Super Multi Plus READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE IMPROPER INSTALLATION OR ATTACHMENT OF EQ...

Page 7: ...all drain piping according to this installation manual to ensure good drainage and insulate the pipe to prevent condensation Improper drain piping may cause water leakage and make the furnitures get wet Install the indoor units BP units and outdoor units power wire and connecting wire at least 1 meter away from televisions or radios to prevent image interference or noise Depending on the radio wav...

Page 8: ...th the discharge pipe thermister R3T suction pipe thermister R2T and pressure sensors S1NPH S1NPL removed Such operation may burn out the compressor Be sure to confirm the model name and the serial no of the outer front plates when attaching detaching the plates to avoid mistakes When closing the service panels take care that the tightening torque does not exceed 4 1 N m 3 3 Handling As shown in t...

Page 9: ...talling the unit in a place frequently exposed to snow pay special attention to the following Elevate the foundation as high as possible Remove the rear suction grille to prevent snow from accumulating on the rear fins 7 If you install the unit on a building frame please install a waterproof plate within 150 mm of the underside of the unit or use a drain plug kit option in order to avoid the drain...

Page 10: ...downward The unit of numeric values is mm When routing the piping backward secure space of 250 mm on the right side of the unit A In case of non stacked installation See figure 4 B In case of stacked installation 1 In case obstacles exist in front of the outlet side 2 In case obstacles exist in front of the air inlet C In case of multiple row installation for roof top use etc 1 In case of installi...

Page 11: ...er to 9 3 How to use the shut off valve on page 8 Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant to leak Always use the supplied copper gasket when connecting the gas pipe supplied with the unit See 9 Refrigerant piping on page 7 8 1 Cautions for brazing Be sure to carry out a nitrogen blow when brazing Brazing without carrying out nitrogen repl...

Page 12: ... the figure Since the side boards may be deformed if only a torque wrench is used when loosening or tightening flare nuts always lock the shut off valve with a wrench and then use a torque wrench Do not place wrenches on the valve cover Do not apply force on the valve cover this may result in a refrigerant leak Pipe size Tightening Torque N m A mm Flare shape Ø9 5 32 7 39 9 12 8 13 2 Ø15 9 61 8 75...

Page 13: ...t and outdoor branch piping come into contact with the compressor terminal cover If the liquid side piping insulation might come into contact with it adjust the height as shown in the figure below Also make sure the field piping does not touch the bolts or outer panels of the compressor When the outdoor unit is installed above the BP unit and indoor unit the following can occur The condensated wat...

Page 14: ...kit 5 m Example a 5 m Allowable height Between outdoor and indoor units Difference in height Difference in height between outdoor and indoor units H1 30 m Between outdoor and BP units Difference in height Difference in height between outdoor and BP units H2 30 m Between BP and BP units Difference in height Difference in height between BP and BP units H3 15 m Between indoor and indoor units Differe...

Page 15: ... 1 hour confirm that the vacuum gauge does not rise 9 9 Additional refrigerant charge See figure 6 Pipe size selection How to calculate the additional refrigerant to be charged Additional refrigerant to be charged R kg R should be rounded off in units of 0 1 kg Piping size outer diameter x minimum thickness Symbol Gas pipe Liquid pipe Between outdoor and first refrigerant branch kit a Ø19 1x1 0 Ø9...

Page 16: ...stops within 30 minutes If the refrigerant charge cannot be finished within 30 minutes repeat step 2 If the operation stops immediately after restart there is a possibility that the system is overcharged The refrigerant cannot be charged more than this amount 4 After the refrigerant charge hose is removed make sure to fully open the liquid stop valve Otherwise the piping may burst due to blocked l...

Page 17: ...d lightning rods dangerous when struck by lightning due to abnormal rise in electrical potential in the grounding This unit uses an inverter and therefore generates noise which will have to be reduced to avoid interfering with other devices The outer casing of the product may take on an electrical charge due to leaked electrical current which will have to be discharged with the grounding 10 3 Conn...

Page 18: ...frequency Voltage Recommended fuses Transmission line section RMXS112 1 N 50 Hz 230 V 32 A 0 75 1 25 mm2 RMXS140 RMXS160 NOTE Select the power supply cable in accordance with relevant local and national regulations Wire size must comply with the applicable local and national code Specifications for local wiring power cord and branch wiring are in compliance with IEC60245 WIRE TYPE H05VV Only in pr...

Page 19: ...0 m Total wiring length 300 m Maximum No of branches 9 Never connect the power supply to unit to unit cabling terminal block Otherwise the entire system may break down 1 Liquid pipe 2 Gas pipe 3 Interconnecting wiring 4 Insulator 5 Finishing tape WARNING ELECTRIC SHOCK Caution when performing service to inverter equipment Do not touch live parts for 10 minutes after the power supply is turned off ...

Page 20: ... A1P The figure shows state of the led indications when the unit is shipped from the factory Setting the mode The set mode can be changed with the button according to the following procedure For setting mode 1 Press the button once the led is off For setting mode 2 Press the button for 5 seconds the H1P led is on If the H1P led is blinking and the button is pushed once it will change to setting mo...

Page 21: ... items are automatically checked Check for miswiring Check if stop valves are open Check of refrigerant charge Automatic judgement of piping length 4 After the test operation maximum 30 minutes the unit automatically stops Check the operation results by the outdoor unit led indication 5 Measure to be taken when operation finishes abnormally 1 Confirm the error code on the remote controller 2 Corre...

Page 22: ...ration manual delivered with the refrigerant reclaimer Installation error Malfunction code Remedial action The stop valve of an outdoor unit is left closed E3 Open the stop valve on both the gas and liquid side Refrigerant overcharge Recalculate the required amount of refrigerant from the piping length and correct the refrigerant charge level by recovering any excessive refrigerant with a refriger...

Page 23: ...allest room volume m3 In a case such as the following calculate the volume of A B as a single room or as the smallest room 3 Calculating the refrigerant density using the results of the calculations in steps 1 and 2 above If the result of the above calculation exceeds the maximum concentration level then make similar calculations for the second then third smallest room and so until the result fall...

Page 24: ...Zandvoordestraat 300 B 8400 Oostende Belgium 4PWEN19516 1B ...

Reviews: