10
English
Wiring
WARNING
Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical
•
shock, or
fi
re.
Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
•
terminal block.) Doing so may cause electric shock or
fi
re.
Be sure to install a ground fault circuit interrupter breaker. (One that can handle higher harmonics.)
•
(This unit uses an inverter, which means that it must be used a ground fault circuit interrupter breaker capable handling
harmonics in order to prevent malfunctioning of the ground fault circuit interrupter breaker itself.)
Use an all-pole disconnection type breaker with at least 1/8 inch (3mm) between the contact point gaps.
•
When carrying out wiring connection, take care not to pull at the conduit.
•
Do not connect the power wire to the indoor unit. Doing so may cause electric shock or
fi
re.
•
Do not turn on the safety breaker until all work is completed.
•
1) Strip the insulation from the wire (3/4inch (20mm)).
Connect the connection wires between the
2)
indoor and outdoor units so that the terminal
numbers match. Tighten the terminal screws
securely. We recommend a
fl
athead
screwdriver be used to tighten the screws.
<Work before wiring>
A protection plate is
fi
xed for protection from the high-voltage section.
Before staring wiring work, dismount the protection plate by removing the 2 screws and dismount the conduit mounting cover
by removing the 2 screws.
<Method of mounting conduit>
Pass wires through the conduit and secure them with a lock nut.
1)
After completing the work, reattach the conduit mounting cover and the protection plate to its original position.
2)
1
2
3
1
2
3
Power supply
terminal block
Conduit
Lock nut
Conduit
mounting
plate
Shape wires so
that the protection
plate and conduit
mounting plate fit
securely.
Screw
Screw
Protection plate
Observe the notes mentioned following when wiring to the power supply
terminal board.
Precautions to be taken for power supply wiring.
Use a round crimp-style terminal for connection to the power supply terminal
board. In case it cannot be used due to unavoidable reasons, be sure to
observe the following instruction.
Place the round crimp-style terminals on the wires up to the covered part and
secure in place.
1
2
3
1 2 3
L
1
L
2
Safety
breaker
20A
Ground fault
circuit interrupter
breaker
Ground
If the length of a connection wire is
33ft (10m) or more, use AWG14 wire.
Outdoor unit
Indoor
unit
Power
supply
60Hz 208-230V
Use AWG 14 wires.
Stranded wire
Round crimp-style
terminal