Outdoor Unit Installation

3. 

Flaring the pipe end 

Cut the pipe end with a pipe cutter.

1) 

Remove burrs with the cut surface facing 

2) 

downward so that the chips do not enter the pipe.
Put the 

fl

 are nut on the pipe.

3) 

Flare the pipe.

4) 

Check that the 

fl

 aring is properly made.

5) 

  

WARNING

Do not use mineral oil on 

fl

 ared part.

• 

Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.

• 

Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.

• 

Do never install a drier to this R410A unit in order to guarantee its lifetime.

• 

The drying material may dissolve and damage the system.

• 

Incomplete 

fl

 aring may cause refrigerant gas leakage.

• 

Refrigerant piping

4. 

  

CAUTION

Use the 

fl

 are nut 

fi

 xed to the main unit. (To prevent cracking of the 

fl

 are nut by aged deterioration.)

• 

To prevent gas leakage, apply refrigeration oil only to the inner surface of the 

fl

 are. (Use refrigeration oil for R410A.)

• 

Use torque wrenches when tightening the 

fl

 are nuts to prevent damage to the 

fl

 are nuts and gas leakage.

• 

Flare nut tightening torque

Liquid side

1/4 inch (6.4mm)

10.4-12.7ft • lbf

(14.2-17.2N • m)

Gas side

1/2 inch (12.7mm)

36.5-44.5ft • lbf

(49.5-60.3N • m)

Valve cap tightening torque

Liquid side

1/4 inch (6.4mm)

15.9-20.2ft • Ibf

(21.6-27.4N • m)

Gas side

1/2 inch (12.7mm)

35.5-44.0ft • Ibf

(48.1-59.7N • m)

 

Service port cap tightening torque

 

7.9-10.8ft • lbf

 

 

(10.8-14.7N • m)

Do not apply refrigeration 
oil to the outer surface.

Flare nut

Apply refrigeration oil to 
the inner surface of the 
flare.

Do not apply refrigeration 
oil to the flare nut avoid 
tightening with over torque.

[Apply oil]

• Align the centers of both flares and tighten the flare 

nuts 3 or 4 turns by hand. Then tighten them fully with 
the torque wrenches. 

(Cut exactly at 

right angles.)

 Remove burrs.

Set exactly at the position shown below.

A

Flaring

Die

Check

Flare’s inner surface 
must be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

A

0-0.020 inch 

(0-0.5mm)

Clutch-type

Flare tool for R410A

0.039-0.059 inch 

(1.0-1.5mm)

Clutch-type (Rigid-type)

0.059-0.079 inch 

(1.5-2.0mm)

Wing-nut type (Imperial-type)

Conventional flare tool

01_EN_3P273470-2.indd   6

01_EN_3P273470-2.indd   6

1/6/2011   12:04:45 PM

1/6/2011   12:04:45 PM

Summary of Contents for RKN15KEVJU

Page 1: ...nstallation S rie split R410A Manual de instalaci n Serie Split R410A INSTALLATION MANUAL R410A Split Series Models RXN15KEVJU RKN15KEVJU RXN18KEVJU RKN18KEVJU RXN24KEVJU RKN24KEVJU 00_CV_3P273470 2 i...

Page 2: ...not play with them Children playing with plastic bags face the danger of death by suffocation Do not install unit in an area where flammable materials are present due to risk of explosion resulting i...

Page 3: ...nd fault circuit interrupter breaker may result in electrically shocks or fire personal injury CAUTION Do not install the air conditioner where gas leakage would be exposed to open flames If the gas l...

Page 4: ...10ft 3m away depending on radio wave conditions In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 8 Since drain flows out of t...

Page 5: ...height Min allowable length Max allowable length 98 4ft 30m 4 92ft 1 5m 65 6ft 20m Liquid pipe Gas pipe O D 1 4 inch 6 4mm O D 1 2 inch 12 7mm 0 21oz ft 20g m Additional refrigerant required for refr...

Page 6: ...urely by means of the foundation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their leng...

Page 7: ...damage to the flare nuts and gas leakage Flare nut tightening torque Liquid side 1 4 inch 6 4mm 10 4 12 7ft lbf 14 2 17 2N m Gas side 1 2 inch 12 7mm 36 5 44 5ft lbf 49 5 60 3N m Valve cap tightening...

Page 8: ...1MPa 1 3 Close gauge manifold s low pressure valve Lo and stop vacuum pump 4 Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back 2 Remove caps...

Page 9: ...ending Selection of copper and heat insulation materials 7 2 When using commercial copper pipes and fittings observe the following Insulation material Polyethylene foam 1 Heat transfer rate 0 041 to 0...

Page 10: ...operation to stop press the indoor unit ON OFF switch Using the indoor unit s remote controller Press MODE button and select the cooling mode 1 Press ON OFF button to turn on the system 2 Press both o...

Page 11: ...o tighten the screws Work before wiring A protection plate is fixed for protection from the high voltage section Before staring wiring work dismount the protection plate by removing the 2 screws and d...

Page 12: ...start back up once the temperature rises again Remove the 3 screws on the side and remove the top plate of the outdoor unit 1 Remove the drip proof cover 2 Cut the jumper J6 of the PCB inside 3 J5 J7...

Page 13: ...ion in accordance with the operation manual to ensure that all functions and parts 1 3 such as fin movement are working properly The air conditioner requires a small amount of power in its standby mod...

Page 14: ...3P273470 2 M10B141 1102 HT Two dimensional bar code is a code for manufacturing 00_CV_3P273470 2 indd 2 00_CV_3P273470 2 indd 2 12 15 2010 2 29 23 PM 12 15 2010 2 29 23 PM...

Reviews: