![background image](http://html1.mh-extra.com/html/daikin/rkm71pv16/rkm71pv16_service-manual-removal-procedure_2459841020.webp)
Compressor
Si001408EA
18
Removal Procedure
2
3
4
Pull out the compressor
lead wires.
Remove the overload
protector.
Remove the protection
bushing.
5
6
7
8
Heat up the brazed part
of the discharge side
pipe and disconnect it.
Heat up the brazed part
of the suction side pipe
and disconnect it.
Remove the 3 nuts.
Lift up the compressor
and remove it.
Step
Procedure
Points
Overload
protector
Protection bushing
V (yellow)
U (red)
W (blue)
(R20344)
Compressor
Nut
Brazed part of
discharge side pipe
Brazed part of
suction side pipe
(R20347)