![background image](http://html1.mh-extra.com/html/daikin/rkh50qrv16/rkh50qrv16_removal-procedure_2459833015.webp)
Si001409EB
Thermistor ASSY
Removal Procedure
13
5. Thermistor ASSY
Warning
Be sure to wait for 10 minutes or more after turning off all power supplies before
disassembling work.
Step
Procedure
Points
1
Detach the holder and
pull out the outdoor
temperature thermistor.
The shape of the protection
net varies depending on the
model.
2
3
Remove the 5 screws
of the right side panel.
Remove the right side
panel.
When reassembling, insert
the 2 lower hooks and the
upper hook of the back.
4
Release the discharge
pipe thermistor.
Be careful not to lose the
fixture for the thermistor.
Holder
Outdoor
temperature
thermistor
(R20620)
Right side panel
(R20621)
Discharge pipe
thermistor
(R22583)
(R20430)
Fixture