background image

8

English

•  When piping work is complete, it is necessary to perform a pressure test 

and evacuate system with a vacuum pump.

•  If using additional refrigerant, purge the air from the refrigerant pipes and 

indoor unit using a vacuum pump, then charge additional refrigerant.

•  Use a hexagonal wrench (3/16 inch (4mm)) to operate the stop valve rod.
•  All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

Compound 
pressure gauge

Pressure 
meter

High-pressure 
valve

Low-pressure 
valve

Vacuum pump

Service port

Liquid 
stop 
valve

Valve caps

Gas stop valve

Charging 
hoses

Gauge 
manifold

1) Pressurize the liquid pipe and gas pipe from the service ports of each stop valve to 550psi (3.8MPa) (do not pressurize 

more than 550psi (3.8MPa)) for 1 hour minimum, 24 hours recommended. If there is a pressure drop, check for leaks, 
make repairs and perform the pressure test again.

2) Connect the gauge manifold’s charging hose to the gas stop valve’s service port.
3) Fully open the low-pressure valve (Lo) on the gauge manifold and fully close the high-pressure valve (Hi).                      

 (High-pressure valve will require no further operation.)

4) 

Evacuate system using vacuum pump to below 500 microns for 1 hour minimum.

5) Close the low-pressure valve (Lo) on the gauge manifold and stop vacuum pumping. 

(Maintain this condition for a few minutes to make sure that the compound pressure gauge pointer does not swing 
back.)*

1

6) Remove the valve caps from the liquid stop valve and gas stop valve.
7) To open the liquid stop valve, turn the rod of the valve 90° counter-clockwise using a hexagonal wrench. 

Close it after 5 seconds, and check for gas leakage. 

Using soapy water, check for gas leakage from the indoor unit’s flare and outdoor unit’s flare and valve rods.

 

After the check is complete, wipe all soapy water off.

8) Disconnect the charging hoses from the service port for the gas stop valve, then fully open the liquid and gas stop valves. 

(Do not attempt to turn the valve rods further than they can go.)

9) 

Tighten the valve caps and service port caps for the liquid and gas stop valves with a torque wrench to the specified 

torques. 
Refer to 

“4. Refrigerant piping” on page 6 for details.

*

1

  If the compound pressure gauge pointer swings back, the refrigerant may have water content or there may be a loose 

pipe joint. 
Check all pipe joints and retighten nuts as needed, then repeat steps 3) through 5).

6. 

Refilling refrigerant

Check the type of refrigerant to be used on the machine nameplate.
Precautions when adding R410A
Fill from the liquid pipe in liquid form.
R410A is a mixed refrigerant, so adding it in gas form may cause the refrigerant composition to change, preventing normal 
operation.

• 

Before filling, check whether the cylinder has a siphon attached or not. (It should have something like “liquid filling siphon 

attached” displayed on it.)

Filling a cylinder with an attached siphon

Stand the cylinder upright when filling.

There is a siphon pipe inside, so the cylinder 

need not be upside-down to fill with liquid.

Filling other cylinders

Turn the cylinder 

upside-down when filling.

•  Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering.

English

01_EN_3P572321-3.indd   8

2019/06/19   14:17:27

Summary of Contents for RK09NMVJU

Page 1: ...18NMVJU RXN24NMVJU RK09NMVJU RK12NMVJU RK18NMVJU RK24NMVJU RKN09NMVJU RKN12NMVJU RKN18NMVJU RKN24NMVJU RXL09QMVJU RXL12QMVJU RXL12QMVJU9 RXL15QMVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalación Manuel dinstallation ...

Page 2: ...hyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing severe injury or death If refrigerant gas leaks during installation ventil...

Page 3: ...m getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the p...

Page 4: ...containing sulfate gas corrosion may shorten the life of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspended from a ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described bel...

Page 5: ...vibration may occur depending on how the unit is installed and the environment in which it is used 10ft 3m O D 1 2 inch 12 7mm O D 5 8 inch 15 9mm RX18 RXN18 RK18 RKN18 RXL15 RX24 RXN24 RK24 RKN24 RX09 12 RK09 12 RXL09 12 RXN09 12 RKN09 12 65 5 8ft 20m 98 1 2ft 30m Min allowable piping length X Foot bolt hole centers From unit s side Z Footbolt hole centers Y Allow 11 13 16 300mm of work space bel...

Page 6: ...ing one side More than 1 15 16 50 More than 1 15 16 50 Top view More than 3 15 16 100 Walls facing two sides More than 13 3 4 350 09 12 class 15 18 24 class When installed as in the figure on the left it is recommended to either change the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately More than 3 15 16 100 More than 13 3 4 150 When installed ...

Page 7: ...with the cut surface facing downward so that the filings do not enter the pipe 3 Put the flare nut on the pipe 4 Flare the pipe 5 Check that the flaring has been done correctly Check The flare s inner surface must be flaw free When flaring do not over tighten and crack The pipe end must be evenly flared in a perfect circle Make sure that the flare nut is fitted Set exactly at the position shown below Fl...

Page 8: ...ns as below Gas side Piping size O D 3 8 inch 9 5mm O D 1 2 inch 12 7mm O D 5 8 inch 15 9mm O D 1 4 inch 6 4mm 1 3 16 inch 30mm or more 1 9 16 inch 40mm or more 1 15 16 inch 50mm or more 1 3 16 inch 30mm or more 0 031 inch 0 8mm C1220T O 0 039 inch 1 0mm C1220T O 0 031 inch 0 8mm C1220T O I D 15 32 19 32 inch 12 15mm I D 9 16 5 8 inch 14 16mm I D 5 8 13 16 inch 16 20mm I D 5 16 13 32 inch 8 10mm 1...

Page 9: ...alve 7 To open the liquid stop valve turn the rod of the valve 90 counter clockwise using a hexagonal wrench Close it after 5 seconds and check for gas leakage Using soapy water check for gas leakage from the indoor unit s flare and outdoor unit s flare and valve rods After the check is complete wipe all soapy water off 8 Disconnect the charging hoses from the service port for the gas stop valve t...

Page 10: ... A A When connecting the inter unit wires to the terminal block using a single core wire be sure to curl the end of the lead Improper work may cause heat and fire Strip wire end to this point Excessive strip length may cause electric shock or current leakage Stripping wire at terminal block Good Wrong Good Wrong Do not turn on the circuit breaker until all work is completed 1 Strip the insulation ...

Page 11: ...its original position 1 2 3 1 2 3 1 2 3 Screws Conduit mounting cover Screws Protection plate Power supply terminal block Shape wires so that the protection plate and conduit mounting plate fit securely Conduit Lock nut Conduit mounting plate L1 L2 15 18 24 class Method of mounting conduit 1 Dismount the service lid by removing the 2 screws 2 Pass wires through the conduit and secure them with a lo...

Page 12: ...CAUTION When pressing the switch do not touch the terminal block It has a high voltage and touching it could cause electric shock In order to protect the environment be sure to pump down when relocating or disposing of the unit 1 Remove the valve cap from the liquid stop valve and gas stop valve 2 Begin forced cooling operation 3 After 5 to 10 minutes close the liquid stop valve with a hexagonal w...

Page 13: ... temperature 80 F Cool Test Operation Press the On Off button within 10 seconds For wireless remote controller 1 Press and select the COOL operation 2 Press twice Test is displayed 3 Press within 10 seconds and the forced cooling operation starts Forced cooling operation will stop automatically after about 15 minutes To stop the operation press Trial Operation and Testing 1 Trial operation and tes...

Page 14: ...Two dimensional bar code is a manufacturing code 3P572321 3 M18B313 1907 HT ...

Reviews: