background image

32

3P362438-3H English

Perform the test procedure as described in 15.4.2. Test operation on 

page 39.

 INFORMATION

• 

When a malfunction is detected during the procedure (e.g., in case 
of closed stop valve), a malfunction code will be displayed. In that 

case, refer to 15.5. Malfunction code list on page 40 and solve 

the malfunction accordingly. Resetting the malfunction can be done 
by pushing BS3. The procedure can be restarted from 6b).

• 

Aborting the manual refrigerant charge is possible by pushing BS3. 
The unit will stop and return to idle condition.

Information which may occur during additional refrigerant charging 
procedures:

P8: Indoor unit freeze up prevention

Action:

 Close valve A immediately. Reset malfunction by pushing 

BS1. Retry auto charge procedure.

P2: Abnormal low pressure drop

Action:

 Close valve A immediately. Reset malfunction by pushing 

BS1. Check following items before retry auto charge procedure:

 

- Check if the gas pipe stop valve is opened correctly.

 

- Check if the valve of the refrigerant cylinder is opened.

 

- Check if the air inlet and outlet of the indoor units are not ob-

structed.

E-2

:

 Indoor temperature is out of range.

E-3

:

 Outdoor temperature is out of range.

E-5

:  An indoor unit which is not compatible with automatic refrigerant 

charge functionality is installed (e.g., Mini-split indoor unit, etc.)

Other malfunction code: close valve A immediately. Confirm the mal

-

function code and take corresponding action, 15.5. Malfunction code 

list on page 40.

14 .3 .3 .  Final charge adjustment

It is not necessary to do this final adjustment normally, but perform the 

following operation only when if the most adequate refrigerant for the 
best performance is required.
The outdoor temperature must be between 60°F (16°C) and 97°F 

(36 °C).

Purge gauge lines. Connect service gauge manifold to the service 
port between the compressor and the reversing valve in each outdoor 
unit. Run the system for 30 minutes in cooling by the forced operation 

using the field setting mode [2-6] (value 0: OFF, 1:ON) (Refer to 15.2. 
Monitoring function and field settings.) to allow pressures to stabilize, 

then check subcooling as detailed in the following sections.

Subcooling = Sat. Liquid Temp. – Liquid Line Temp.

Temporarily install a thermometer on the liquid line between the 

coil and the EV in each outdoor unit. Ensure the thermometer 

makes adequate contact and is insulated for best possible read-
ings. Use liquid line temperature to determine sub cooling.

Check subcooling for each outdoor unit and calculate the average 
subcooling of the outdoor unit. Systems should have a subcooling 
of 11±3°F (6±2°C). 
a.   If average subcooling is low, add charge to raise subcooling to 

11±3°F (6±2°C) (The maximum additional charge is 4.4 lbs. 

(2kg))

b.   If average subcooling is high, remove charge to lower the sub-

cooling to 11±3°F (6±2°C)

14 .3 .4 .  Checks after adding refrigerant

• 

Are all stop valves open?

• 

Is the amount of refrigerant, that has been added, recorded on the 
refrigerant charge label?

 NOTE

Make sure to open all stop valves after (pre-) charging the refrigerant. 
Operating with the stop valves closed will damage the compressor.

15 . 

Start-up and configuration

 INFORMATION

It is important that all information in this chapter is read sequentially by 

the installer and that the system is configured as applicable.

 DANGER: ElECTRICAl SHOCk

See Safety considerations on page i.

15 .1 .  Checks before initial start up

After the installation of the unit, first check the following items. Once all 
below checks are fulfilled, the unit must be closed, only then can the 

unit be powered up.

Installation
Check that the unit is properly installed, to avoid abnormal noises 
and vibrations when starting up the unit.

Field wiring

Be sure that the field wiring has been carried out according to the 
instructions described in 9. Field wiring on page 18, according to 

the wiring diagrams and according to the applicable legislation.

Power supply voltage
Check the power supply voltage on the local supply panel. The 

voltage must correspond to the voltage on the identification label 

of the unit.

Ground wiring
Be sure that the ground wires have been connected properly and 
that the ground terminals are tightened.

Insulation test of the main power circuit
Using a megatester for 500 V, check that the insulation resistance 

of 1 MΩ or more is attained by applying a voltage of 500 V DC 

between power terminals and ground. Never use the megatester 
for the transmission wiring.

Fuses, circuit breakers, or protection devices
Check that the fuses, circuit breakers, or the locally installed pro-

tection devices are of the size and type specified in 9. Field wiring 
on page 18. Be sure that neither a fuse nor a protection device 

has been bypassed. 

Internal wiring

Visually check the control box and the inside of the unit on loose 

connections or damaged electrical components.

Pipe size and pipe insulation
Be sure that correct pipe sizes are installed and that the insulation 

work is properly executed.

Stop valves
Be sure that all stop valves are open.

10 

Damaged equipment
Check the inside of the unit on damaged components or squeezed 
pipes.

01_EN_3P362438-3H.indb   32

1/14/2015   10:20:22 AM

Summary of Contents for REYQ72TTJU

Page 1: ...REYQ264TTJU REYQ288TTJU REYQ312TTJU REYQ336TTJU REYQ360TTJU REYQ384TTJU REYQ408TTJU REYQ432TTJU REYQ456TTJU REYQ72TYDN REYQ96TYDN REYQ120TYDN REYQ144TYDN REYQ168TYDN REYQ192TYDN REYQ216TYDN REYQ240TYD...

Page 2: ...ING Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric sho...

Page 3: ...away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the a...

Page 4: ...ize 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limitations 11 8 Precautions on refrigerant piping 14 8 1 Caution for brazing 14 8 2 Connecting the refrigerant piping 14 8 3...

Page 5: ...1 REYQ120TTJU TYDN 1 REYQ144TTJU TYDN 1 72 96 120 144 168 REYQ168TTJU TYDN 1 REYQ192TTJU TYDN 1 1 REYQ216TTJU TYDN 1 1 REYQ240TTJU TYDN 1 1 REYQ264TTJU TYDN 1 1 REYQ288TTJU TYDN 2 REYQ312TTJU TYDN 1...

Page 6: ...accessories is shown in the figure below Accessories assy piping Accessories assy operation and installation manual NOTE Do not throw away any of the accessories until installation is complete They ar...

Page 7: ...e reasonable protection against such interference However there is no guarantee that inter ference will not occur in a particular installation It is therefore recommended to install the equipment and...

Page 8: ...nopy 2 Construct a pedestal NOTE When operating the unit in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the drainholes of the unit free by usi...

Page 9: ...a Front side Suction side b h2 2 or more Service space h1 2 or more h1 b a 59 in 1500 mm b 19 5 8 in 500 mm In case of an installation site where sides A B C D have obsta cles the wall heights of sid...

Page 10: ...y attention to the position of the unit s center of gravity NOTE Use a belt sling of 3 4 in 20 mm wide that adequately bears the weight of the unit A forklift can only be used for transport as long as...

Page 11: ...0 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi system See 1 2 2 Outdoor unit co...

Page 12: ...r other contamination Foreign materials inside pipes including oils for fabrication must be 0 14 gr 10 ft 30 mg 10 m or less Use the following items for the refrigerant piping Material Jointless phosp...

Page 13: ...e on page 9 When using REFNET joints at the first branch from the outdoor unit choose from the following table in accordance with the capacity of the outdoor unit example REFNET joint a see 7 3 Select...

Page 14: ...i connection piping kit must always be installed horizontally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping Example of connection 8 indoor units ar...

Page 15: ...t 40 m From indoor unit to indoor unit Height difference From outdoor unit to outdoor unit Height difference Height difference between outdoor units H3 16 ft 5 m Allowable length after branch 3 Actual...

Page 16: ...8 A G p Indoor unit 1 8 j k BS BS BS BS BS BS BS 2 s r q b c d e f g p 130 ft 40 m From outdoor unit to the farthest indoor unit 9 From outdoor unit to the nearest indoor unit 1 2 The total piping len...

Page 17: ...gh with Dry Nitrogen prevents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and p...

Page 18: ...cting with the burner flame Liquid pipe stop valve Suction gas pipe stop value Protective plate Stop valve mounting plate High Low pressure gas pipe stop valve 5 Cut off the lower part of the smaller...

Page 19: ...ions to the branch kits are the responsibility of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor unit system To connect the piping between o...

Page 20: ...branches either horizontally or vertically Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 50...

Page 21: ...installed by a licensed elec trician and must comply with relevant local and national regulations Be sure to use a dedicated power circuit Never use a power supply shared by another appliance Never in...

Page 22: ...61 9A 61 9A 43 0A 43 0A 43 0A 38 0A 43 0A 61 9A 38 0A 55 0A 61 9A 55 0A 55 0A 55 0A 55 0A 55 0A 61 9A 15 2A 21 1A 21 1A 31 9A 36 1A 15 2A 21 1A 21 1A 21 1A 21 1A 31 9A 21 1A 31 9A 31 9A 31 9A 31 9A 3...

Page 23: ...11 BS unit 12 Indoor unit 13 Indoor unit Cooling only The Outdoor unit that connect the transmission wiring to BS unit is Master unit of the multi system And the other units are Sub unit In this figur...

Page 24: ...230 V 60 Hz 2 Branch switch Overcurrent breaker 3 Ground wire 4 Control box 5 Only REYQ TYDN Control box 2 6 Only REYQ TYDN Do not open the control box 2 cover There are no work when installation 7 At...

Page 25: ...connect it using a conduit Choose an appropriate knockout hole for conduit size suitable for the power and ground line to be used Transmission line Connect it using a conduit in the knockout hole on t...

Page 26: ...uge rises or not If it rises the system may either contain moisture inside or have leaks NOTE During the rainy season moisture might enter the piping If working during a rainy season and the work take...

Page 27: ...To access you can remove the front inspection door of the front panel see figure Now you can open the inspection door of the control box front panel see figure You can see 3 push buttons and 3 seven s...

Page 28: ...situation is the amount of indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function pus...

Page 29: ...efriger ant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The re...

Page 30: ...REYQ120TTJU BS units BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 2 36 1 54 1 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 20 ft r f1 2 10 ft b f...

Page 31: ...r refrigerant to reach R Q Step 4b Close valve B R Q Step 5 Open all outdoor unit stop valves Step 6 Proceed with automatic or manual charge A Automatic charge B Manual charge Step 6a Push BS2 once 88...

Page 32: ...des appear E 2 indoor temperature out of range and E 3 outdoor temperature out of range In this case perform automatic charging procedure again See figure Location of valves next page for more informa...

Page 33: ...ns to be taken see 14 3 1 Flow chart on page 28 To speed up the process of pre charging refrigerant for large systems it is recommended to first charge a portion of the refrigerant before performing a...

Page 34: ...he unit indicates E 2 or E 3 the ambient conditions are NOT favorable to execute the test run Push BS1 to finish the automatic charging procedure INFORMATION In case a malfunction code occurred during...

Page 35: ...ing for each outdoor unit and calculate the average subcooling of the outdoor unit Systems should have a subcooling of 11 3 F 6 2 C a If average subcooling is low add charge to raise subcooling to 11...

Page 36: ...nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable an automatic low n...

Page 37: ...onsumption limitation conditions when an external signal is sent to the unit this setting should be changed This setting will only be effective when the optional external control adaptor DTA104A61 62...

Page 38: ...efines the level power consumption limitation that will be applied continuously The level is according to the table Default value 0 OFF Value 2 32 Restriction reference 0 Function not active default 1...

Page 39: ...ing is used in conjunction with setting 2 9 For more information and advice about the impact of these settings see 15 3 Energy saving and optimum operation 15 3 Energy saving and optimum operation Thi...

Page 40: ...ion or undershoot during cooling operation is allowed compared to the requested refrigerant tem perature in order to achieve the required room temperature very fast The overshoot is allowed from the s...

Page 41: ...erature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46...

Page 42: ...sts stand by periods etc INFORMATION Note that during the first running period of the unit required power in put may be higher This phenomenon originates from the compressor that requires a 50 hour ru...

Page 43: ...ting the abnormality press BS3 to reset the malfunction code and retry operation The malfunction code which is displayed on the outdoor unit will indi cate a main malfunction code and a sub code The s...

Page 44: ...r malfunction R14T A1P X19A Check connection on printed circuit board or actuator J5 01 03 05 Temperature sensor malfunction R12T A8P X15A Check connection on printed circuit board or actuator 18 19 2...

Page 45: ...V1 voltage power shortage or open phase Check if power supply is within range Correct phase order 02 09 12 INV1 reversed or open power supply phase Check if power supply is within range Correct phase...

Page 46: ...3P362438 3H EM14A006B 1502 HT...

Reviews: