26

3P362438-3H English

13 .2 .2 .  Operating the DIP switches 

By operating the DIP switches it is possible to:

What to do with DIP switch DS1

1

Cool/Heat selector  (refer to the manual of the Cool/
Heat selector switch)
OFF=not installed=factor  setting

2-4

NOT USED
DO NOT CHANGE THE FACTORY SETTING

What to do with DIP switch DS2

1-4

NOT USED
DO NOT CHANGE THE FACTORY SETTING

13 .3 . 

Connecting the PC configurator to the outdoor unit

Connection of the optional PC configurator cable to the outdoor unit 
has to be done on A1P. Connect the EKPCCAB* cable to the 5-pin 

blue connector X27A.

 CAUTION

Works executed on the outdoor unit are best done under dry weather 

conditions to avoid water ingress.

X27A

1

2

3

2

3

4

5

H

 J

S

T

X27A

A1P

1  PC

Cable (EKPCCAB*)

3  Outdoor unit main 

printed circuit board

14 .  Charging refrigerant

14 .1 .  Precautions

 NOTE

•  Refrigerant cannot be charged until field wiring has been completed.
• 

Refrigerant may only be charged after performing the leak test and 
the vacuum drying.

•  When charging a system, care shall be taken that its maximum 

permissible charge is never exceeded, in view of the danger of 

liquid hammer.

•  Charging with an unsuitable substance may cause explosions and 

accidents, so always ensure that the appropriate refrigerant R410A 
is charged.

• 

Refrigerant containers shall be opened slowly.

• 

Always use protective gloves and protect your eyes when charging 
refrigerant.

• 

When the refrigerant system is to be opened, refrigerant must be 
treated according to the applicable legislation.

 DANGER

See Safety considerations on page i.

• 

To avoid compressor breakdown. Do not charge the refrigerant 

more than the specified amount.

• 

This outdoor unit is factory charged with refrigerant and depending 
on pipe sizes and pipe lengths some systems require additional 
charging of refrigerant. See 14.2. Calculating the additional refriger-
ant charge. 

• 

In case recharge is required, refer to the nameplate of the unit.
It states the type of refrigerant and necessary amount.

14 .2 .  Calculating the additional refrigerant charge

 NOTE

The refrigerant charge of the system must be less than 210 lbs. 
(100 kg). This means that in case the calculated total refrigerant 
charge is equal to or more than 209 lbs. (95 kg) you must divide your 
multiple outdoor system into smaller independent systems, each 
containing less than 209 lbs. (95 kg) refrigerant charge. For factory 
charge, refer to the unit nameplate.

14 .2 .1 .  How to calculate the additional refrigerant to be charged

Additional refrigerant to be charged=R (lbs.). R should be rounded off 
in units of 0.1 lbs.

R=[(X

1

 

×

 

f

7/8) 

×

 0.249+(X

2

 

×

 

f

3/4) 

×

 0.175+(X

3

 

×

 

f

5/8) 

×

 0.121+(X

4

 

×

 

f

1/2) 

×

 0.081+(X

5

 

×

 

f

3/8) 

×

 0.040+(X

6

 

×

 

f

1/4) 

×

 0.015] 

×

 1.04+[A]+[B]+[C]

X

1...6

 =Total length (ft. (m)) of liquid piping size at 

f

a

* In units of 0.1 kg, additional refrigerant to be charged=R (kg).

R=[(X

1

 

×

 

f

22.2) 

×

 0.37+(X

2

 

×

 

f

19.1) 

×

 0.26+(X

3

 

×

 

f

15.9) 

×

 0.18+(X

4

 

×

 

f

12.7) 

×

 

0.12+(X

5

 

×

 

f

9.5) 

×

 0.059+(X

6

 

×

 

f

6.4) 

×

 0.022] × 1.04+[A]+[B]+[C]

Parameter [A]

Refrigerant amount for BS units

BS unit model

Refrigerant amount

BS4Q54T

0.7 lbs./unit (0.3 kg/unit)

BS6Q54T

0.9 lbs./unit (0.4 kg/unit)

BS8Q54T

1.1 lbs./unit (0.5 kg/unit)

BS10Q54T

1.5 lbs./unit (0.7 kg/unit)

BS12Q54T

1.8 lbs./unit (0.8 kg/unit)

BSQ36T

0.1 lbs./unit (0.05 kg/unit)

BSQ60T

0.2 lbs./unit (0.1 kg/unit)

BSQ96T

0.4 lbs./unit (0.2 kg/unit)

Parameter [B]

Refrigerant amount for outdoor units

Outdoor unit capacity type

Refrigerant amount

REYQ72T

0.0 lbs./unit (0.0 kg/unit)

REYQ96T

3.1 lbs./unit (1.4 kg/unit)

REYQ120T

3.3 lbs./unit (1.5 kg/unit)

REYQ144T

10.6 lbs./unit (4.8 kg/unit)

REYQ168T

10.8 lbs./unit (4.9 kg/unit)

Parameter [C]

Refrigerant amount by field piping length 

 

and indoor units capacity

Field 

piping 
length

Total 

indoor unit 

capacity 

connection 

ratio

Refrigerant amount

Total outdoor unit capacity type

REYQ72-

144T

REYQ168-

288T

REYQ312-

456T

< 295.3 ft. 

(90 m)

≤ 85%

0.0

>

 85%

The smaller of [D]  

or 5.51 lbs. (2.5 kg)

The smaller of [D]  

or 6.61 lbs. (3.0 kg)

The smaller of [D]  

or 7.50 lbs. (3.4 kg)

≥ 295.3 ft. 

(90 m)

≤ 85%

0.0

>

 85%

2.20 lbs. (1.0 kg)

01_EN_3P362438-3H.indb   26

1/14/2015   10:20:20 AM

Summary of Contents for REYQ72TTJU

Page 1: ...REYQ264TTJU REYQ288TTJU REYQ312TTJU REYQ336TTJU REYQ360TTJU REYQ384TTJU REYQ408TTJU REYQ432TTJU REYQ456TTJU REYQ72TYDN REYQ96TYDN REYQ120TYDN REYQ144TYDN REYQ168TYDN REYQ192TYDN REYQ216TYDN REYQ240TYD...

Page 2: ...ING Only qualified personnel must carry out the installation work Installation must be done in accordance with this installation manual Improper installation could result in water leakage electric sho...

Page 3: ...away from fluorescent lamps as much as possible Indoor units are for indoor installation only Outdoor units can be installed either outdoors or indoors This unit is for indoor use Do not install the a...

Page 4: ...ize 9 7 4 Selection of refrigerant branch kits 10 7 5 System piping length limitations 11 8 Precautions on refrigerant piping 14 8 1 Caution for brazing 14 8 2 Connecting the refrigerant piping 14 8 3...

Page 5: ...1 REYQ120TTJU TYDN 1 REYQ144TTJU TYDN 1 72 96 120 144 168 REYQ168TTJU TYDN 1 REYQ192TTJU TYDN 1 1 REYQ216TTJU TYDN 1 1 REYQ240TTJU TYDN 1 1 REYQ264TTJU TYDN 1 1 REYQ288TTJU TYDN 2 REYQ312TTJU TYDN 1...

Page 6: ...accessories is shown in the figure below Accessories assy piping Accessories assy operation and installation manual NOTE Do not throw away any of the accessories until installation is complete They ar...

Page 7: ...e reasonable protection against such interference However there is no guarantee that inter ference will not occur in a particular installation It is therefore recommended to install the equipment and...

Page 8: ...nopy 2 Construct a pedestal NOTE When operating the unit in a low outdoor ambient temperature with high humidity conditions make sure to take precautions to keep the drainholes of the unit free by usi...

Page 9: ...a Front side Suction side b h2 2 or more Service space h1 2 or more h1 b a 59 in 1500 mm b 19 5 8 in 500 mm In case of an installation site where sides A B C D have obsta cles the wall heights of sid...

Page 10: ...y attention to the position of the unit s center of gravity NOTE Use a belt sling of 3 4 in 20 mm wide that adequately bears the weight of the unit A forklift can only be used for transport as long as...

Page 11: ...0 mm above the foundation surface A A 13 16 in 20 mm NOTE There are restrictions on the refrigerant pipe connecting order between outdoor unit in the case of the multi system See 1 2 2 Outdoor unit co...

Page 12: ...r other contamination Foreign materials inside pipes including oils for fabrication must be 0 14 gr 10 ft 30 mg 10 m or less Use the following items for the refrigerant piping Material Jointless phosp...

Page 13: ...e on page 9 When using REFNET joints at the first branch from the outdoor unit choose from the following table in accordance with the capacity of the outdoor unit example REFNET joint a see 7 3 Select...

Page 14: ...i connection piping kit must always be installed horizontally paying attention to the installation restrictions indicated in 8 Precautions on refrigerant piping Example of connection 8 indoor units ar...

Page 15: ...t 40 m From indoor unit to indoor unit Height difference From outdoor unit to outdoor unit Height difference Height difference between outdoor units H3 16 ft 5 m Allowable length after branch 3 Actual...

Page 16: ...8 A G p Indoor unit 1 8 j k BS BS BS BS BS BS BS 2 s r q b c d e f g p 130 ft 40 m From outdoor unit to the farthest indoor unit 9 From outdoor unit to the nearest indoor unit 1 2 The total piping len...

Page 17: ...gh with Dry Nitrogen prevents the creation of large quantities of oxidized film on the inside of the piping An oxidized film ad versely affects valves and compressors in the refrigerating system and p...

Page 18: ...cting with the burner flame Liquid pipe stop valve Suction gas pipe stop value Protective plate Stop valve mounting plate High Low pressure gas pipe stop valve 5 Cut off the lower part of the smaller...

Page 19: ...ions to the branch kits are the responsibility of the installer field piping 8 2 4 Precautions when connecting piping between outdoor units multiple outdoor unit system To connect the piping between o...

Page 20: ...branches either horizontally or vertically Mount the REFNET header so that it branches horizontally 2 Installation of the multi connection piping kit A 1 B 1 C D 15 C 4 3 4 in 120 mm D 19 11 16 in 50...

Page 21: ...installed by a licensed elec trician and must comply with relevant local and national regulations Be sure to use a dedicated power circuit Never use a power supply shared by another appliance Never in...

Page 22: ...61 9A 61 9A 43 0A 43 0A 43 0A 38 0A 43 0A 61 9A 38 0A 55 0A 61 9A 55 0A 55 0A 55 0A 55 0A 55 0A 61 9A 15 2A 21 1A 21 1A 31 9A 36 1A 15 2A 21 1A 21 1A 21 1A 21 1A 31 9A 21 1A 31 9A 31 9A 31 9A 31 9A 3...

Page 23: ...11 BS unit 12 Indoor unit 13 Indoor unit Cooling only The Outdoor unit that connect the transmission wiring to BS unit is Master unit of the multi system And the other units are Sub unit In this figur...

Page 24: ...230 V 60 Hz 2 Branch switch Overcurrent breaker 3 Ground wire 4 Control box 5 Only REYQ TYDN Control box 2 6 Only REYQ TYDN Do not open the control box 2 cover There are no work when installation 7 At...

Page 25: ...connect it using a conduit Choose an appropriate knockout hole for conduit size suitable for the power and ground line to be used Transmission line Connect it using a conduit in the knockout hole on t...

Page 26: ...uge rises or not If it rises the system may either contain moisture inside or have leaks NOTE During the rainy season moisture might enter the piping If working during a rainy season and the work take...

Page 27: ...To access you can remove the front inspection door of the front panel see figure Now you can open the inspection door of the control box front panel see figure You can see 3 push buttons and 3 seven s...

Page 28: ...situation is the amount of indoor units which are con nected to the system Result mode 1 setting 10 is addressed and selected return value is monitored information To leave the monitoring function pus...

Page 29: ...efriger ant charge In case recharge is required refer to the nameplate of the unit It states the type of refrigerant and necessary amount 14 2 Calculating the additional refrigerant charge NOTE The re...

Page 30: ...REYQ120TTJU BS units BS4Q54T 1 BSQ60T 1 BSQ96T 1 Indoor units FXMQ type 18 1 24 2 36 1 54 1 FXFQ type 36 2 Other 48 1 Liquid piping a f3 4 60 ft e f1 4 15 ft i f3 8 20 ft m f3 8 20 ft r f1 2 10 ft b f...

Page 31: ...r refrigerant to reach R Q Step 4b Close valve B R Q Step 5 Open all outdoor unit stop valves Step 6 Proceed with automatic or manual charge A Automatic charge B Manual charge Step 6a Push BS2 once 88...

Page 32: ...des appear E 2 indoor temperature out of range and E 3 outdoor temperature out of range In this case perform automatic charging procedure again See figure Location of valves next page for more informa...

Page 33: ...ns to be taken see 14 3 1 Flow chart on page 28 To speed up the process of pre charging refrigerant for large systems it is recommended to first charge a portion of the refrigerant before performing a...

Page 34: ...he unit indicates E 2 or E 3 the ambient conditions are NOT favorable to execute the test run Push BS1 to finish the automatic charging procedure INFORMATION In case a malfunction code occurred during...

Page 35: ...ing for each outdoor unit and calculate the average subcooling of the outdoor unit Systems should have a subcooling of 11 3 F 6 2 C a If average subcooling is low add charge to raise subcooling to 11...

Page 36: ...nominal operating conditions Low noise operation can be set in mode 2 There are two methods to activate low noise operation of the outdoor unit system The first method is to enable an automatic low n...

Page 37: ...onsumption limitation conditions when an external signal is sent to the unit this setting should be changed This setting will only be effective when the optional external control adaptor DTA104A61 62...

Page 38: ...efines the level power consumption limitation that will be applied continuously The level is according to the table Default value 0 OFF Value 2 32 Restriction reference 0 Function not active default 1...

Page 39: ...ing is used in conjunction with setting 2 9 For more information and advice about the impact of these settings see 15 3 Energy saving and optimum operation 15 3 Energy saving and optimum operation Thi...

Page 40: ...ion or undershoot during cooling operation is allowed compared to the requested refrigerant tem perature in order to achieve the required room temperature very fast The overshoot is allowed from the s...

Page 41: ...erature evolution A B C D E F A Indoor unit set temperature B Operation start C Operating time D Mild E Quick F Powerful Example Automatic mode during cooling A B 100 70 E Tc C D 120 F 49 C F 115 F 46...

Page 42: ...sts stand by periods etc INFORMATION Note that during the first running period of the unit required power in put may be higher This phenomenon originates from the compressor that requires a 50 hour ru...

Page 43: ...ting the abnormality press BS3 to reset the malfunction code and retry operation The malfunction code which is displayed on the outdoor unit will indi cate a main malfunction code and a sub code The s...

Page 44: ...r malfunction R14T A1P X19A Check connection on printed circuit board or actuator J5 01 03 05 Temperature sensor malfunction R12T A8P X15A Check connection on printed circuit board or actuator 18 19 2...