Installation
Installation of Outdoor Units
44
1-5 Electrical specifications (1)
2.
MAIN COMPONENTS
For main components and function of the main compo-
nents, refer to the
Engineering Data Book
.
3.
SELECTION OF LOCATION
This unit, both indoor and outdoor, is suitable for instal-
lation in a commercial and light industrial environment. If
installed as a household appliance it could cause electro-
magnetic interference.
The VRV OUTDOOR units should be installed in a location
that meets the following requirements
:
1.
The foundation is strong enough to support the weight of
the unit and the floor is flat to prevent vibration and noise
generation.
2.
The space around the unit is adequate for servicing and the
minimum space for air inlet and air outlet is available.
Refer to figure 1
, and choose a pattern.
1.
Front side
2.
No limit to wall height
3.
Suction side
3.
Ensure that water cannot cause any damage to the location
in case it drips out the unit (e.g. in case of a blocked drain
pipe).
4.
The piping length between the outdoor unit and the indoor unit
may not exceed the allowable piping length. See Section 6-3,
Example of Connection
on Page 49.
5.
Select the location of the unit in such a way that neither the
discharged air nor the sound generated by the unit disturb
anyone.
6.
Make sure that the air inlet and outlet of the unit are not
positioned towards the main wind direction. Frontal wind
will disturb the operation of the unit. If necessary, use a
windscreen to block the wind.
DANGER
•
Do not install unit in an area where flammable materials
are present due to risk of explosion resulting in serious in-
jury or death.
•
Refrigerant is heavier than air and replaces oxygen. A
massive leak could lead to oxygen depletion, especially in
basements, and an asphyxiation hazard could occur lead-
ing to serious injury or death. Refer to Section 9.
Caution
NOTE
for Refrigerant Leaks
.
•
An inverter air conditioner may cause electronic noise
generated from AM broadcasting. Examine where to in-
stall the main air conditioner and electric wires, keeping
proper distances away from stereo equipment, personal
computers, etc.
Refer to figure 2.
1.
indoor unit
2.
Branch switch, overcurrent breaker
3.
remote controller
4.
COOL / HEAT selector
5.
personal computer or radio
•
If the electric wave of AM broadcasting is particularly
weak, keep distances of 10 ft. or more and use conduit
tubes for power and transmission lines. In heavy snowfall
areas, select an installation site where snow will not affect
operation of the unit.
CAUTION
Do not install in the following locations.
•
Locations such as kitchens which contain a lot of min-
eral oil or steam in the atmosphere or where oil may
splatter on the unit.
Resin parts may deteriorate, causing the unit to fall or
leak.
•
Locations where sulfurous acids and other corrosive
gases may be present in the atmosphere.
Copper piping and soldered joints may corrode, caus-
ing refrigerant to leak.
•
Locations where equipment that produces electromag-
netic waves is found.
The electromagnetic waves may cause the control sys-
tem to malfunction, preventing normal operation.
4.
INSPECTING AND HANDLING THE UNIT
At delivery, the package should be checked and any dam-
age should be reported immediately to the carrier claims
agent.
When handling the unit, take into account the following:
•
Fragile, handle the unit with care.
Keep the unit upright in order to avoid compressor
damage.
•
Choose the path along which the unit is to be brought in
ahead of time.
•
If a forklift is to be used, pass the forklift arms through the
large openings on the bottom of the unit.
Model
REYQ72/
96MTJU
REYQ144/168/
192MTJU
Power supply
Phase
-
3~
3~
Frequency
Hz
60
60
Voltage
V
208-230
208-230
Voltage tolerance
%
±10
±10
Recommended fuses
A
60
60+60
Compressor
Phase
-
3~
3~
Frequency
Hz
60
60
Voltage
V
208-230
208-230
Nominal running current
A
10.1+13.1
(10.1+13.1)+(10.1+13.1)
Model
REYQ72/
96MTJU
REYQ144/168/
192MTJU
Control and fan motor
Type
Voltage
V
208-230
208-230
_