Figure 51: Typical Chimney Flue Assembly
NOTE:
A cabinet – Ships Factory Installed
B cabinet – Refer to Figure above. Note that section B must be affixed to
cabinet before installing sections A & D
C cabinet - Ships uninstalled, but secure in condenser section
Warranty Exclusion
Warranty is void if the furnace is operated in the presence of
chlorinated vapors, if the airflow through the furnace is not in
accordance with rating plate, or if the wiring or controls have
been modified or tampered with.
WARNING
Hot surface hazard. Can cause severe equipment damage,
personal injury, or death.
Allow burner assembly to cool before
servicing equipment.
WARNING
Units equipped with gas heating must not be operated
in an atmosphere contaminated with chemicals which
will corrode the unit such as halogenated hydrocarbons,
chlorine, cleaning solvents, refrigerants, swimming pool
exhaust, etc. Exposure to these compounds may cause
severe damage to the gas furnace and result in improper
or dangerous operation .
Operation of the gas furnace in such
a contaminated atmosphere constitutes product abuse and will void all
warranty coverage by the manufacturer. Questions regarding specific
contaminants should be referred to your local gas utility.
Horizontal Installations
WARNING
For installation on non-combustible floors only.
DPS 016–028 Rebel units are available with horizontal heat.
Ventilation & Flue Pipe Requirements
The Rebel rooftop unit is equipped with an outdoor air hood to
supply adequate combustion air. The unit also has a flue outlet
assembly and requires no additional chimney, flue pipe, Breidert
cap, draft inducer, etc.
CAUTION
Snow levels must be controlled to prevent moisture and air flow blockage to
the furnace enclosure and combustion air stream.
Installation
IMPORTANT
Connect this unit only to gas supplied by a commercial
utility . This furnace must be installed by an experienced
professional installation company that employs fully
trained and experienced technicians . Install the gas
piping in accordance local codes and regulations of the
local utility company. In the absence of local codes, follow
the National Fuel Gas Code, ANSI Z223.1/NFPA 54, or the
CSA B149.1, Natural Gas and Propane Installation Code –
latest editions. Note: The use of flexible gas connectors
is not permitted .
WARNING
Sharp edges hazard. Can cause personal injury or death.
Sheet metal parts, self-tapping screws, clips, and similar items inherently
have sharp edges, and it is necessary that the installer exercise caution
when handling these items.
IM-1125-13 • REBEL ROOFTOPS
48
www.DaikinApplied.com
Optional Gas Heat