Table 2: Physical Data—Standard Units DPS 003 through 028
Model
Small cabinet
Medium cabinet
Large cabinet
003
004
005
006
007
010
012
015
016
018
020
025
028
Cooling only performance
Gross cooling capacity (tons)
3
4
5
6
7 .5
10
12
15
15 .5
17 .5
20.1
25
27 .5
Nominal airflow (cfm)
1125
1500
1875
2100
2450
3500
4200
5250
5900
6600
7600
9500
10400
EER
1, 7
13 .5
12 .4
13.0
11 .6
12 .5
12 .4
11 .6
11.0
12 .2
11 .9
11 .3
11 .3
10.5
IEER
1, 7
or SEER
16 .9
17.0
18.5
19.8
20.6
19 .3
18.0
18.0
21.0
20.8
20.4
18.3
17 .9
Heat pump performance
4
High temperature capacity @ 47°F (MBh)
32
43
54
64
78
105
134
164
158
172
218
—
—
COP @ 47°F or HSPF
5
9 .2
8.9
8.5
3 .69
3 .66
3 .42
3 .33
3 .64
3 .67
3 .6
3.40
—
—
Low temperature capacity @ 17°F (MBh)
20
24
33
39
47
61 .5
77
91
93
104
132
—
—
COP @ 17°F
5
N/A
N/A
N/A
2 .54
2 .42
2.38
2 .32
2 .25
2 .34
233
2.20
—
—
Electric heat performance
Control options
2/4 stage/SCR
4 stage/SCR
4 stage/SCR
kW (low/medium/high heat)
6/12/18/24/30
18/36/54/72
10, 20, 30, 45, 60, 72 90, 120, 150
Gas heating performance
Input capacity (MBh)
80/120/160
200/300/400
300, 450, 600
Number of stages (staged option)
2
2
4
Turndown (modulating options)
5:1
5:1, 10:1
12:1
Gas connection size (mpt)
1/2"
3/4"
3/4"
Steady state efficiency
81%
81%
81%
Heating coil
Type
Hot water
Hot water
Hot water
Rows/FPI (high heat/low heat)
(2/10) / (1/8)
(2/10) / (1/8)
1/12, 2/12, 3/13
Face area (sq. ft.)
2 .5
5 .4
12 .3
Compressors
Quantity/type
(1) Inverter scroll
(1) Inverter scroll,
(1) Fixed speed scroll
(1) Inverter scroll on 16–20,
(1) Inverter (1) Fixed speed scroll
Number of stages
Modulating
Modulating
Modulating
Refrigerant
R-410A
R-410A
R - 410A
Indoor coil
Rows/FPI
3/16
4/16
4/14
4/14
3/15
4/15
4/15
6/12
4/15
4/15
4/15
4/15
4/15
Face area (sq. ft.)
4.8
4.8
6.0
6.0
14.0
15 .4
15 .4
15 .4
18.9
18.9
21 .4
21 .4
21 .4
Capacity control
Electronic Expansion Valve (EEV)
Electronic Expansion Valve (EEV)
Electronic Expansion Valve (EEV)
Outdoor coil
Type: non-heat pump/heat pump
6
Aluminum microchannel/copper tube-aluminum fin
Rows/FPI — heat pump
2/16
3/16
3/16
4/16
4/16
4/16
3/16
3/16
4/16
—
—
Rows/FPI — non-heat pump
1/21
3/16
1/21
1/21
4/16
1/21
1/23
Outdoor fan and motor
HP/Quantity
0.5/1
1.0/1
1.0/2
3.5/1
Fan Diameter (in)/quantity
27/1
27/1
27/2
39/1
Indoor fan
Type
Centrifugal airfoil (SWSI)
Centrifugal airfoil (SWSI)
Centrifugal airfoil (SWSI)
Quantity/diameter
2
(1) 12", (1) 14", (1) 16"
(1) 14"
(1) 16"
(1) 22"
(1) 22"
1/20 or 1/24
1/24
Quantity/diameter
3
(1) 12", (1) 14", (1) 16"
(1) 14", (1) 16", (1) 22"
1/16 or 1/20
Drive type
Direct drive
Direct drive
Direct drive
Motor HP range
1.3 / 2.3 / 4.0
4.0 / 8.0
2.0 / 3.0 / 5.0 / 7.5 / 10.0 / 15.0 / 20.0
Hot gas reheat coil
Coil type
Microchannel
Microchannel
Microchannel
Control type
Modulating
Modulating
Modulating
Temperature rise
20°
20°
20°
Filters
Type
2", 4"
2", 4"
2" (MERV8), 4" (MERV14)
Area (sq. ft.)
7 .1
18
27.0
Qty. - size
4 – 16 × 16
6 – 18 × 24
9 – 18 x 24
NOTE:
1. EER and IEER/SEER for cooling only VAV, 460 volt unit, largest SAF
2 . Mixed outside air and return air units
3. 100% outside air unit only
4. Heat pump performance for units with back up electric heat
5. HSPF for 3-5 ton units only
6. Size 5 and 6 non-heat pump models use copper tube aluminum fin
7. Down discharge
IM-1125-13 • REBEL ROOFTOPS
12
www.DaikinApplied.com