R(Y)(P)71~125B7
Split System air conditioners
4PW10931-1B

Installation manual

6

R22:

Complete charging of the refrigerant

When the entire refrigerant pipe length is within 30 meters (for
R407C) and 7.5 

meters (for R22), charge the refrigerant in

accordance with the amount mentioned in the nameplate, and when
the pipe length exceeds 30 meters (for R407C) and 7.5 meters (for
R22), the charging amount mentioned in the nameplate and that
required for additional charging are to be totalled as the net charging
amount.

Precaution for pumping-down operation

The outdoor unit is equipped with a low-pressure switch to protect the
compressor. Take the following steps to perform the pumping-down
operation.

1

Start the fan operation with the remote controller.

Confirm that stop valves both on the liquid and gas side are open.

2

Push the pumping-down button on the PC board of the outdoor
unit during more than 5 seconds.

Compressor and outdoor fan will start operation automatically.
If step 2 is performed before step 1, then the indoor fan may
automatically start running. Please pay attention to this.

3

Continue operation for 2 min. until operation condition stabilizes.

4

Close the stop valve on the liquid side securely. (See 

"Operating

stop valve: see figure 6" on page 4

)

Insecure closing of the valve may result in burning of the
compressor.

5

When the low-pressure switch is activated, the unit stops
working. At this time, close the stop valve on the gas side.

This is the end of pumping-down operation. After pumping-down
operation, the remote controller can show the following pattern:

-

"U4"

-

blank screen

-

indoor fan operates for about 30 seconds

even when ON button on the remote controller is pressed, and it will
not operate. Turn off the main power supply switch and turn it on
again in need of operation.

E

LECTRICAL

 

WIRING

 

WORK

All wiring must be performed by an authorized electrician.

All components procured on the site and all electric construction
should comply with the applicable local and national codes.

Be sure to use a dedicated power circuit.

Do not share a common source with other equipment.

Fix cables so that cables do not make contact with the pipes
(especially on high pressure side).

For W1 and T1 models
Make sure to connect power supply cables in normal phase. If
connected in reverse phase, the remote controller of indoor unit
indicates "U1" and the equipment cannot operate. Change any
two of the three power supply cables (L1, L2, L3) to correct
phase.
If the contact in the magnetic switch should be forcibly turned on
while the equipment is inoperative, the compressor will burn out.
Never try to forcibly turn on the contact.

Never squeeze bundled cables into a unit.

When cables are routed from the unit, a protection sleeve for the
conduits (PG-insertions) can be inserted at the installation hole.

(See figure 9)

Follow the electric wiring diagram for electrical wiring works.

Grounding resistance should be according to national
regulations.

Wiring of power supply and the units

Refer to the installation manual attached to the indoor unit for wiring
of indoor units, etc.

Attach an earth leak detector and fuse to the power supply line. 

(See

figure 10)

RY71~125

G = (L1-7.5 m) x 0.05 + L2 x A + L3 x A

R71~125

G = (L1-7.5 m) x 0.03 + L2 x A + L3 x A

Branched pipe

A

RY71~125

Ø 9.5

0.05 kg/m

Ø 6.4

0.03 kg/m

R71~125

Ø 9.5

0.03 kg/m

Ø 6.4

0.02 kg/m

Never short-circuit the low-pressure switch in this
operation.

In order to avoid electric shock, please put the insulation
sheet as follows. 

(See figure 8)

1

Switch box

2

PCB

3

Pump down button

4

Insulation sheet

5

Tape

A

Inside

B

Outside

1

Wire

2

Bush

3

Nut

4

Frame

5

Hose

I

Pair

II

Twin

III

Triple

M

Master

S

Slave

1

Earth leak detector

2

Fuse

3

Remote controller

Power supply

Model

Field 

fuse

Wire type

(1)

(1) Only in protected pipes, use HO7RN-F when protected pipes are not 

used.

Size

Wire type of 

wiring between 

the units

R(Y)(P)71V1

32 A

H05VV-U3G

Wiring size 

must comply 

with the 

applicable 

local 

and national 

code

H05VV-U4G2.5

R(Y)(P)100V1

40 A

H05VV-U3G

H05VV-U4G2.5

R(Y)(P)71W1

16 A

H05VV-U5G

H05VV-U4G2.5

R(Y)(P)100W1

16 A

H05VV-U5G

H05VV-U4G2.5

R(Y)(P)125W1

20 A

H05VV-U5G

H05VV-U4G2.5

R(Y)(P)71T1

20 A

H05VV-U4G

H05VV-U4G2.5

R(Y)(P)100T1

32 A

H05VV-U4G

H05VV-U4G2.5

R(Y)(P)125T1

32 A

H05VV-U4G

H05VV-U4G2.5

Summary of Contents for R71B7V1

Page 1: ...oners English R71B7V1 R71B7W1 R100B7V1 R100B7W1 R125B7W1 RP71B7V1 RP71B7W1 RP71B7T1 RP100B7V1 RP100B7W1 RP100B7T1 RP125B7W1 RP125B7T1 RY71B7V1 RY71B7W1 RY100B7V1 RY100B7W1 RY125B7W1 RYP71B7V1 RYP71B7W...

Page 2: ...timuksia edellytt en ett niit k ytet n ohjeidemme mukaisesti following the provisions of Directives as amended gem den Vorschriften der Direktiven gem nderung conform ment aux stipulations des Directi...

Page 3: ...1250 500 1000 1000 1000 1000 150 150 50 100 150 500 500 500 50 100 150 250 L1 H H L1 L H L H 500 L1 L2 L1 L2 L2 L1 L1 L2 L2 L1 500 750 1000 0 L1 1 2H 1 2H L1 1000 50 100 100 200 L2 H H L2 L2 L1 500 50...

Page 4: ...onal when used as the outdoor unit for the simultaneous operation system Refer to catalogues for details Never operate the unit without the thermistor R3T burning of the compressor may result Be sure...

Page 5: ...locks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit in order to prevent th...

Page 6: ...ion system twin see figure 3 triple see figure 4 The pipes between the outdoor unit and the branch L1 should have the same size as the outdoor connections The pipes between the branch and the indoor u...

Page 7: ...nitially tighten by hand before tightening firmly Make sure to flow nitrogen gas through the pipe when brazing Take measures against contamination when installing pipes Prevent foreign materials like...

Page 8: ...of vacuum break and vacuum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Leak test 1 Evacuate the pipes and check vacuum No pressure increase f...

Page 9: ...dedicated power circuit Do not share a common source with other equipment Fix cables so that cables do not make contact with the pipes especially on high pressure side For W1 and T1 models Make sure...

Page 10: ...T1 MODEL PHASE REVERSE CIRCUIT Q1L Q2L THERMO SWITCH M1F M2F Q3E EARTH LEAK DETECTOR R1T THERMISTOR AIR R2T THERMISTOR COIL R3T THERMISTOR DISCHARGE R4C R5C V1 MODEL RESISTOR RC SIGNAL RECEIVER CIRCUI...

Page 11: ...2 R407C 8 6 5 4 2 1 3 9 7 A B 3 3 1 2 4 5 5 1 5 4 A B 2 3 V1 1 50Hz 230V L N N L 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 W1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 T1 3 50Hz 230V L2 L3 L3 L2 L1 L1 l ll l...

Page 12: ...DaikinZandvoordestraat 300 B 8400 Oostende Belgium 4PW10931 1B...

Reviews: