background image

 

 

 

Installation manual

 

3

 

R(Y)(P)71~125B7

Split System air conditioners

4PW10931-1B

 

I

 

NSTALLATION

 

 

 

SERVICING

 

 

 

SPACE

 

The numerical figures used herein represent the dimensions for the
models R(Y)(P)71 to 125. Figures in (  ) indicate the dimensions for
the models R(Y)(P)100 and 125. (Unit: mm)

(Refer to 

"Precautions on installation" on page 2

)

 

Precaution

 

When installing link of multiple outdoor units, leave a space of
200 mm or more between the casing of one unit and the stop valves
of the other unit.

 

(A) In case of non-stacked installation 

 

(See figure 1)

 

(B) In case of stacked installation

 

1.

 

In case obstacles exist in front of the outlet side.

 

2.

 

In case obstacles exist in front of the air inlet.

Do not stack more than one unit.

About 100 mm is required as the dimension for laying the upper
outdoor unit's drain pipe. Get the portion A sealed so that air from the
outlet does not bypass.

 

(C) In case of multiple-row installation (for roof top use, etc.)

 

1.

 

In case of installing one unit per row.

 

2.

 

In case of installing multiple units (2 units or more) in lateral
connection per row.

Relation of dimensions of H, A and L are shown in the table below.

 

R

EFRIGERANT

 

PIPE

 

SIZE

 

AND

 

ALLOWABLE

 

PIPE

 

LENGTH

1.

Refrigerant pipe size

Pair system 

(See figure 2)

Simultaneous operation system

Twin and triple operation system (twin: see 

figure 3

, triple:

see 

figure 4

)

The pipes between the outdoor unit and the branch (L1) should have
the same size as the outdoor connections. The pipes between the
branch and the indoor units (L2~L4) should have the same size as
the indoor connections. Branch: see marking '

' on figures

figure 3

~

figure 4

.

2.

Allowable pipe length

See the table below concerning lengths and heights. Refer to

figure 2

~

figure 4

. Assume that the longest line in the figure

corresponds with the actual longest pipe, and the highest unit in the
figure corresponds with the actual highest unit.

Suction side obstacle

Discharge side obstacle

Left side obstacle

Right side obstacle

Top side obstacle

Obstacle is present

L

A

L

H

0 < L 

 1/2 H

150 (250)

1/2H < L

200 (300)

H < L

Installation impossible

All field piping must be installed by a licensed refrigeration
technician and must comply with relevant local and
national regulations.

Refrigerant pipe size

Gas pipe

Liquid pipe

R(Y)(P)71

ø 15.9 x t1.0

ø 9.5 x t0.8

R(Y)(P)100,125

ø 19.1 x t1.0

R407C

R22

Maximum allowable piping 
length (Parenthesized 
figure represents 
equivalent length)

Pair

L1

70 m 

(90 m)

50 m 

(70 m)

Twin / 
Triple

L1+L2

Maximum total one-way 
pipe length

Twin

L1+L2+L3

80 m

60 m

Triple

L1+L2+L3
+L4

Maximum branch pipe 
length

Twin / 
Triple

L2

20 m

20 m

Maximum difference 
between branch lengths

Twin

L2-L3

10 m

10 m

Triple

L2-L4

Maximum height between 
indoor and outdoor

All

H1

30 m

30 m

Maximum height between 
indoors

Twin / 
Triple

H2

0.5 m

0.5 m

Summary of Contents for R71B7V1

Page 1: ...oners English R71B7V1 R71B7W1 R100B7V1 R100B7W1 R125B7W1 RP71B7V1 RP71B7W1 RP71B7T1 RP100B7V1 RP100B7W1 RP100B7T1 RP125B7W1 RP125B7T1 RY71B7V1 RY71B7W1 RY100B7V1 RY100B7W1 RY125B7W1 RYP71B7V1 RYP71B7W...

Page 2: ...timuksia edellytt en ett niit k ytet n ohjeidemme mukaisesti following the provisions of Directives as amended gem den Vorschriften der Direktiven gem nderung conform ment aux stipulations des Directi...

Page 3: ...1250 500 1000 1000 1000 1000 150 150 50 100 150 500 500 500 50 100 150 250 L1 H H L1 L H L H 500 L1 L2 L1 L2 L2 L1 L1 L2 L2 L1 500 750 1000 0 L1 1 2H 1 2H L1 1000 50 100 100 200 L2 H H L2 L2 L1 500 50...

Page 4: ...onal when used as the outdoor unit for the simultaneous operation system Refer to catalogues for details Never operate the unit without the thermistor R3T burning of the compressor may result Be sure...

Page 5: ...locks etc the height of the foundation should be maximum 150 mm 5 If you install the unit on a frame please install a waterproof plate within 150 mm of the underside of the unit in order to prevent th...

Page 6: ...ion system twin see figure 3 triple see figure 4 The pipes between the outdoor unit and the branch L1 should have the same size as the outdoor connections The pipes between the branch and the indoor u...

Page 7: ...nitially tighten by hand before tightening firmly Make sure to flow nitrogen gas through the pipe when brazing Take measures against contamination when installing pipes Prevent foreign materials like...

Page 8: ...of vacuum break and vacuum drying Then after leaving the system in vacuum for 1 hour confirm that the vacuum gauge does not rise Leak test 1 Evacuate the pipes and check vacuum No pressure increase f...

Page 9: ...dedicated power circuit Do not share a common source with other equipment Fix cables so that cables do not make contact with the pipes especially on high pressure side For W1 and T1 models Make sure...

Page 10: ...T1 MODEL PHASE REVERSE CIRCUIT Q1L Q2L THERMO SWITCH M1F M2F Q3E EARTH LEAK DETECTOR R1T THERMISTOR AIR R2T THERMISTOR COIL R3T THERMISTOR DISCHARGE R4C R5C V1 MODEL RESISTOR RC SIGNAL RECEIVER CIRCUI...

Page 11: ...2 R407C 8 6 5 4 2 1 3 9 7 A B 3 3 1 2 4 5 5 1 5 4 A B 2 3 V1 1 50Hz 230V L N N L 3 2 1 3 2 1 P2 P1 3 2 1 P2 P1 3 2 1 P2 P1 W1 3N 50Hz 400V L3 N N L3 L2 L1 L1 L2 T1 3 50Hz 230V L2 L3 L3 L2 L1 L1 l ll l...

Page 12: ...DaikinZandvoordestraat 300 B 8400 Oostende Belgium 4PW10931 1B...

Reviews: