background image

Installation Manual

EDUS04-906_b

34

Room Air Conditioners H-Series

• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the 

installation guidelines below.

• For any of the below installation patterns, the wall height on the exhaust side should be 47-3/16 inch 

(1200mm) or less.

Outdoor Unit Installation Drawings

Installation Guidelines

Precautions on Installation

• Ensure the strength and level of the installation  will not cause any operating vibration or noise after installed.
• In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. (Prepare 

four sets of 3/8 inch (M10) or 7/16 inch (M12) foundation bolts, nuts and washers each which are available 
on the market.)

• It is best to screw in the foundation bolts until their length are 3/4 inch (20mm) from the foundation surface.

Top view

Unit: inch (mm)

More than 
5-7/8 (150)

More than 
11-13/16 (300)

More than 
1-15/16 (50)

Walls facing three sides

More than 
1-15/16 (50)

More than 
1-15/16 (50)

More 
than 
5-7/8 
(150)

Top view

More 
than 
3-15/16 
(100)

Walls facing two sides

More than 1-15/16 (50)

More than 3-15/16 (100)

Side view

47-3/16 
(1200)
or less

Wall facing one side

Wrap the insulation pipe with 
the finishing tape from bottom 
to top.

In sites with poor drainage, use 
block bases for outdoor unit.  
Adjust foot height until the unit 
is leveled.  Otherwise, water 
leakage or pooling of water may 
occur.

22-5/8 (574)

(Foot bolt-hole centers)

(From unit’

s side)

Where there is a danger of the unit 
falling, use foot bolts, or wires.

(Foot bolt-hole 

centers)

12-1/4 (311)

Unit: inch (mm)

How to remove the stop valve cover.

Remove the screw on the 
stop valve cover.
Slide the lid downward 
to remove it.

How to attach the stop valve cover.

Insert the upper part of the 
stop valve cover into the 
outdoor unit to install.
Tighten the screws.

Stop valve cover

O.D. 3/8 inch (9.5mm)

Gas pipe

Liquid pipe

O.D. 1/4 inch (6.4mm)

26ft (8m)

32ft (10m)

Max. allowable length

Max. allowable height

*

 No refrigerant needs to be added if the piping does not 

exceed the maximum length. 

4-1/8 (105.5)

Allow space for piping 
and electrical servicing.

9-7/8” (250mm) from w

all

Allow 11-13/16 inch 
(300mm) of work space 
below the ceiling surface.

3/4” (20mm)

Summary of Contents for Quaternity H-Series

Page 1: ...EDUS04 906_b H Series Heat Pump...

Page 2: ...city Tables 9 7 1 Heat Pump 9 8 Operation Limit 15 9 Sound Level 16 9 1 Measuring Location 16 9 2 Octave Band Level 17 10 Electric Characteristics 19 11 Installation Manual 20 11 1 Indoor Units 20 11...

Page 3: ...06_b 2 Room Air Conditioners H Series 1 Power Supply Note Power Supply Intake Outdoor Unit Indoor Units Outdoor Units Power Supply Quaternity FTXG09HVJU RXG09HVJU 1 208 230V 60Hz FTXG12HVJU RXG12HVJU...

Page 4: ...t Control Auto Fan Speed Timer Weekly Timer Indoor Unit Quiet Operation 24 Hour ON OFF Timer Night Quiet Mode Automatic Count Up down ON OFF Timer OFF only Outdoor Unit Quiet Operation Manual Night Se...

Page 5: ...hable Mildew Proof Removable Washable Mildew Proof Running Current Rated A 0 12 0 14 0 14 0 15 Power Consumption Rated W 24 26 29 31 Power Factor 87 80 7 90 1 89 9 Temperature Control Microcomputer Co...

Page 6: ...orizontal Downward Air Filter Removable Washable Mildew Proof Running Current Rated A 0 15 0 16 Power Consumption Rated W 33 35 Power Factor 95 7 95 1 Temperature Control Microcomputer Control Dimensi...

Page 7: ...D SPACE REAR WALL HOLE LIQUID PIPE 1 4 6 4 Cut AIR PURIFYING INDIVIDUAL OPERATION SPACE FOR PERFORMANCE GEAR CASE UNIT FIXED SCREWS INSIDE PANEL INCLUDING MOUNTING PLATE LEFT SPACE FOR PERFORMANCE THE...

Page 8: ...PRINTED CIRCUIT BOARD R1T R2T CONNECTOR OPERATION SWITCH TERMINAL STRIP SWING MOTOR M1S M4S F1U M1F H2P H3P S1 S403 CN1 FG X1M S1W THERMISTOR A1P A5P MULTI MONITOR H1P LIMIT SWITCH FOR PANEL S1C LIMI...

Page 9: ...OOR TEMPERATURE THERMISTOR 7 9 CuT FIELD PIPING 7 9 CuT COOLING GAS STOP VALVE M MOTOR OPERATED VALVE OUTDOOR UNIT FOUR WAY VALVE ON HEATING 1 2 12 7 CuT 3 8 9 5 CuT HEAT EXCHANGER 3 8 9 5 CuT 6 4 CuT...

Page 10: ...7 96 0 48 8 80 7 78 0 52 8 64 7 71 0 54 8 39 7 61 0 57 7 97 7 44 0 61 64 4 77 0 10 06 8 72 0 44 9 64 8 56 0 48 9 22 8 39 0 53 9 05 8 33 0 54 8 80 8 23 0 57 8 38 8 07 0 61 67 0 80 0 10 27 9 37 0 44 9 8...

Page 11: ...e them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass...

Page 12: ...9 01 0 82 11 18 8 86 0 85 10 62 8 62 0 92 64 4 77 0 13 41 10 15 0 67 12 85 9 92 0 73 12 29 9 69 0 79 12 07 9 60 0 82 11 73 9 46 0 86 11 17 9 24 0 92 66 9 80 1 13 69 10 80 0 67 13 13 10 57 0 73 12 57...

Page 13: ...e them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass...

Page 14: ...48 1 10 13 98 10 28 1 15 13 28 9 97 1 24 64 4 77 0 16 76 11 80 0 90 16 07 11 49 0 99 15 37 11 19 1 07 15 09 11 07 1 11 14 67 10 89 1 16 13 97 10 60 1 24 67 0 80 0 17 11 12 45 0 90 16 41 12 15 0 99 15...

Page 15: ...e them with around values in direct proportion 5 Capacities are based on the following conditions Corresponding refrigerant piping length 25ft 7 5 m Level difference 0ft 6 Airflow rate AFR and Bypass...

Page 16: ...nce Continuous operation 4 50 Outdoor temp FWB 68 50 68 4 FDB 68 0ft Outdoor temp FDB Air flow rate High 77 77 86 82 4 50 Cooling 5 75 32 Indoor temp FDB Indoor temp FWB 25ft 14 32 109 86 Notes 23 59...

Page 17: ...1 Operation sound is measured in an anechoic chamber 2 The data are based on the conditions shown in the table below Indoor Unit Outdoor Unit Cooling Heating Piping Length Indoor 80 FDB 67 FWB Outdoo...

Page 18: ...30 50 40 63 OCTAVE BAND CENTER FREQUENCY Hz 125 250 500 1000 2000 4000 8000 OCTAVE BAND SOUND PRESSURE LEVEL dB 0dB 0 0002 bar THRESHOLDHEARING APPROXIMATE FORCONTINUOUS NOISE POWER SOURCE JIS STANDA...

Page 19: ...NC 60 NC 40 NC 50 NC 20 NC 30 60Hz 208 230V 49 208 230V 60Hz Cooling NC 20 NC 50 NC 60 NC 30 NC 40 48 60Hz 208 230V 208 230V 60Hz Heating 3D063011 COOLING NC 40 NC 30 NC 50 NC 60 NC 20 POWER SOURCE J...

Page 20: ...0 15 Symbols Note MCA MIN CIRCUIT AMPS A 1 RLA is based on the following conditions Indoor temp 80 FDB 67 FWB 26 7 CDB 19 4 CWB Outdoor temp 95 FDB 35 CDB 2 Maximum allowable voltage variation between...

Page 21: ...such as nails and other metal or wood parts including plastic packing materials used for transportation may cause injuries or death by suffocation Only qualified personnel must carry out the installa...

Page 22: ...n be connected Normal operation is not possible when connected to other units Remote controller wireless kit transmitting distance can be shorter than expected in rooms with electronic fluorescent lam...

Page 23: ...odorizing filter for streamer 1 Remote controller holder 1 Mounting plate fixing screws 3 16 1 L M4 25mm 9 Titanium apatite photocatalytic air purifying filter 1 Dry batteries AAA LR03 alkaline 2 Fixi...

Page 24: ...ation pipe with the finishing tape from bottom to top Install the hose with a downward slope Cut thermal insulation pipe to an appropriate length and wrap it with tape making sure that no gap is left...

Page 25: ...panel air filter and upper panel 2 Fully open the top and bottom horizontal louvers See Fig 1 3 Remove the 3 screws in the front grille 4 Lift the hooks 3 locations on the front grille with a flathead...

Page 26: ...nd tighten with included indoor unit fixing screw 6 How to set the different addresses When 2 indoor units are installed in 1 room the 2 wireless remote controllers can be set for different addresses...

Page 27: ...pull out if bending up the wire edge in advance 3 To connect the inter unit wiring after hooking the unit onto the mounting plate connect the inter unit wiring as shown in the figure at right A A A B...

Page 28: ...he pipes If it is difficult to do remove the front panel first 5 Wrap the insulation on the piping with insulation tape If you are not replacing the drain hose store it in the location shown below 4 3...

Page 29: ...necting to the HA system 6 Shape the wires so that the service lid fits securely then close service lid WARNING 1 Do not use tapped wires strand wires extension cords or starburst connections as they...

Page 30: ...ischarge the tab 3 4 2 Pull up the electric parts box cover slowly discharge the tab 4 slide up and discharge the tab 5 5 Insert the connection cord into the HA connector S21 6 Lay the connection cord...

Page 31: ...as a joint 8 Improving installation strength We recommend screwing the indoor unit onto a mounting plate in order to improve the installation strength 1 Remove the front grille 2 Screw in the indoor u...

Page 32: ...serve the following 1 Insulation material Polyethylene foam Heat transfer rate 0 041 to 0 052W mK 0 024 to 0 030 Btu fth F 0 035 to 0 045 kcal mh C Choose heat insulation materials that are designed f...

Page 33: ...erly on solid bases Fall vibration noise Did you install the deodorizing filter for the streamer and the titanium apatite photocatalytic air purifying filter Noise water leakage Have you performed a g...

Page 34: ...than 10 feet 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Do not place moi...

Page 35: ...15 16 50 More than 5 7 8 150 Top view More than 3 15 16 100 Walls facing two sides More than 1 15 16 50 More than 3 15 16 100 Side view 47 3 16 1200 or less Wall facing one side Wrap the insulation pi...

Page 36: ...of the units 3 Never use piping which has been used for previous installations Only use parts which are delivered with the unit 4 Do never install a drier to this R410A unit in order to guarantee its...

Page 37: ...e of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure va...

Page 38: ...gas and liquid refrigerant pipes Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering 6 Refilling the refrigerant Check the type of refrigerant to be used on the...

Page 39: ...he circuit by adding drain pump or other electrical equipment to unit terminals Doing so may cause electric shock or fire 3 Be sure to install an earth leak detector One that can handle higher harmoni...

Page 40: ...tip Place the round crimp style terminals on the wires up to the covered part and secure in place Test items Incomplete cooling heating function No refrigerant gas leaks Draining line is properly ins...

Page 41: ...eath Be sure to ventilate the room sufficiently to avoid this hazard Safely dispose of the packing materials Packing materials such as nails and other metal or wooden parts may cause stabs or other in...

Page 42: ...as they can cut and cause injury Do not place objects in direct proximity of the outside unit Do not let leaves and other debris accumulate around the unit Leaves are a hotbed for small animals which...

Page 43: ...t there are no obstacles close to the outside unit Obstacles close to the outside unit may drop the performance of the outside unit or increase the operating sound of the outside unit Consult your dea...

Page 44: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 43 QUATERNITY DRYING DRY COOLING YELLOW The lamp color also changes according to the optional function...

Page 45: ...Operation Manual EDUS04 906_b 44 Room Air Conditioners H Series Ground terminal...

Page 46: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 45 DRY button...

Page 47: ...Operation Manual EDUS04 906_b 46 Room Air Conditioners H Series...

Page 48: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 47...

Page 49: ...Operation Manual EDUS04 906_b 48 Room Air Conditioners H Series...

Page 50: ...ries 49 DRY COOLING Operation Note on Dry Cooling operation DRY COOLING may raise humidity temporarily Hi Std Lo Constant DRY operation Note on Dry Operation The operation mode change from COOLING to...

Page 51: ...Operation Manual EDUS04 906_b 50 Room Air Conditioners H Series...

Page 52: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 51...

Page 53: ...Operation Manual EDUS04 906_b 52 Room Air Conditioners H Series...

Page 54: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 53 COOLING or DRY COOLING operation the A FLASH STEAMER AIR PURIFYING individual operation B DRY COOLING COOLING C HEATING...

Page 55: ...Operation Manual EDUS04 906_b 54 Room Air Conditioners H Series COOLING BREEZE operation is for COOLING DRY COOLING AND FLASH STREAMER AIR PURIFYING operation...

Page 56: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 55...

Page 57: ...Operation Manual EDUS04 906_b 56 Room Air Conditioners H Series 1 8 F 1 C 3 6 F 2 C...

Page 58: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 57...

Page 59: ...Operation Manual EDUS04 906_b 58 Room Air Conditioners H Series COOLING or DRY COOLING mode or...

Page 60: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 59...

Page 61: ...Operation Manual EDUS04 906_b 60 Room Air Conditioners H Series...

Page 62: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 61...

Page 63: ...Operation Manual EDUS04 906_b 62 Room Air Conditioners H Series...

Page 64: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 63...

Page 65: ...Operation Manual EDUS04 906_b 64 Room Air Conditioners H Series...

Page 66: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 65...

Page 67: ...Operation Manual EDUS04 906_b 66 Room Air Conditioners H Series...

Page 68: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 67...

Page 69: ...Operation Manual EDUS04 906_b 68 Room Air Conditioners H Series...

Page 70: ...EDUS04 906_b Operation Manual Room Air Conditioners H Series 69...

Page 71: ...Operation Manual EDUS04 906_b 70 Room Air Conditioners H Series 3P226009 1...

Page 72: ...pter for Time Clock Remote Control 2 Normal Open Pulse Contact Normal Open Contact KRP413A1S 3 Central Remote Controller Fahrenheit 1 DCS302C71 4 Central Remote Controller Celsius 1 DCS302CA61 5 Unifi...

Page 73: ...d in this manual Be sure to follow instructions Be sure to perform grounding work Never attempt After installation is complete test the unit to confirm that it is working properly and instruct the own...

Page 74: ...Indoor unit Adaptor case Install the adaptor case assy as close to the indoor unit as possible Removing case front Adaptor PCB Case front Screw Screw cover Remove the screw cover one of the screws an...

Page 75: ...relay contacts Manufacturer Type Coil rated voltage Coil resistance Omron MY relay 12 V DC 160 ohm 10 Matsushita HC relay 12 V DC 160 ohm 10 4 Connection with Remote Controller Example connections wi...

Page 76: ...s OFF Always Off ON Off if operation was in Off mode before power failure On if operation was in On mode before power failure Instantaneous contact Normal contact S1 1 S2 1 OPEN CLOSE S1 1 S1 2 Pulse...

Page 77: ...re can be monitored from the Ve up controller 2 Component Parts and Separately Sold Parts which are Required This kit includes the following components Check to ensure that none of these are missing 1...

Page 78: ...ON OFF control is rejected operate stop timer prohibition NOTE 2 During a forced stop all remote controller actions are prohibited Last command priority Contact Open to close air condition stops forc...

Page 79: ...ed to the louver First temporarily attach the louver with 4 screws then check that the angle is correct and finally tighten the screws fully 1 Install so that a short circuit is prevented 2 For the us...

Page 80: ...ct conforms tot he applicable standards and is suitable for use in the region where the product will be used This statement does not purport to exclude restrict or modify the application of any local...

Reviews: