I
nsTallaTIon
and
a
pplICaTIon
C
onsIderaTIons
www.DaikinApplied.com 11
IOM 1242-2 • PATHFINDER
®
MODEL AWV CHILLERS
Figure 12: Case 2 - Power Increase
Case 3: Three or More Units, Side-by-Side
For all models, there must be a minimum of 8 feet between
any units placed side-by-side; however, performance may be
affected at this distance.
Figure 14
and
Figure 15
depict Case
3 performance adjustments as the distance between units
increases.
NOTE:
Data in
Figure 14
and
Figure 15
is for the middle unit
with a unit on each side. See Case 2 adjustment
factors for the two outside units.
Figure 13: Three or More Units, Side-by-Side
Figure 14: Case 3 - Full Load Capacity Reduction
Figure 15: Case 3 - Power Increase
1.0
2.0
3.0
4.0
5.0
6.0
7.0
6
8
10
12
%
P
ow
er
In
cr
ease
Distance Between Units (ft)
Full Load Power Increase
AWV008
AWV010
AWV012
AWV014
AWV016
AWV018
AWV020
AWV022
AWV024
AWV026
AWV028
AWV030
1.0
2.0
3.0
4.0
5.0
6.0
7.0
8
12
16
20
%
C
ap
ac
ity
R
ed
uc
tio
n
Distance Between Units
Full Load Capacity Reduction
AWV008
AWV010
AWV012
AWV014
AWV016
AWV018
AWV020
AWV022
AWV024
AWV026
AWV028
AWV030
2.0
3.0
4.0
5.0
6.0
7.0
8.0
9.0
8
12
16
20
%
P
ow
er
In
cr
ease
Distance Between Units (ft)
Full Load Power Increase
AWV008
AWV010
AWV012
AWV014
AWV016
AWV018
AWV020
AWV022
AWV024
AWV026
AWV028
AWV030
Summary of Contents for Pathfinder AWV Series
Page 4: ......