s
ysTem
m
aInTenanCe
www.DaikinApplied.com 89
IOM 1242-2 • PATHFINDER
®
MODEL AWV CHILLERS
Figure 78: Preventative Maintenance Schedule
Operation
Weekly
Monthly
(Note 1)
Annual
(Note 2)
General
Complete unit log and review (Note 3)
X
Inspect unit for loose or damaged components and visible leaks
X
Inspect thermal insulation for integrity
X
Clean and paint as required
X
Electrical ( * including the VFDs)
Sequence test controls *
X
Check contactors for pitting, replace as required *
X
Check terminals for tightness, tighten as necessary *
X
Clean control panel interior *
X
Clean control box fan filter * (Note 7 )
X
Visually inspect components for signs of overheating *
X
Verify compressor and oil heater operation
X
Megger compressor motor
X
Refrigeration/Lubricant
Leak test
X
Check liquid line sight glasses for clear flow
X
Check compressor oil sight glass for correct level (lubricant charge)
X
Check filter-drier pressure drop (Note 6)
X
Perform compressor vibration test (optional)
X
Perform oil analysis test on compressor oil
X
Condenser (air-cooled)
Clean condenser coils (Note 4)
X
Check fan blades for tightness on shaft (Note 5)
X
Check fans for loose rivets and cracks, check motor brackets
X
Check coil fins for damage and straighten as necessary
X
NOTE:
1 Monthly operations include all weekly operations.
2 Annual (or spring startup) operations include all weekly and monthly operations.
3 Log readings can be taken daily for a higher level of unit observation.
4 Coil cleaning can be required more frequently in areas with a high level of airborne particles.
5 Be sure fan motors are electrically locked out.
6 Replace the filter if pressure drop exceeds 20 psi.
7 The weekly fan filter cleaning schedule can be modified to meet job conditions. It is important that the filter allows full
air flow.
Summary of Contents for Pathfinder AWV Series
Page 4: ......