background image

OM 931-6 • MicroTech III Unit Controller for WSHP 

www.DaikinApplied.com

General Use and Information

The MicroTech III unit controller is provided with two 

drive terminals, R (24VAC), and C (0VAC) that can be 

used to drive the thermostat inputs (G, Y1, Y2, W1, and 

W2) and control inputs (U, E and O). Any combination of 

or single board drive terminal (R, or C) may be used to 

operate the MicroTech III’s unit controller or thermostat 

inputs. Some of the control inputs are used within the 

Water Source Heat Pump and not accessible to the end 

user without a field service tool (laptop with appropriate 

software).
Typically the MicroTech III unit controller's R (24VAC) 

terminal is used to drive the board’s thermostat inputs 

and control inputs by connecting it to the R terminal of 

an industry standard thermostat. The control outputs 

of the standard thermostat are then connected to the 

MicroTech III unit controller's thermostat inputs and 

control inputs as needed. Any remaining board input(s) 

may be operated by additional thermostat outputs or 

remote relays (dry contacts only).
All MicroTech III unit controller inputs must be operated 

by dry contacts powered by the control board’s power 

terminals. No solid state devices (Triacs) may be used 

to operate MicroTech III unit controller inputs. No outside 

power sources may be used to operate MicroTech III. 

All units must be properly grounded per local code 

requirements. See the Installation and Maintenance 

bulletin specific to your Water Source Heat Pump.

Occupied Operation

Board LED Status – Occupied

Yellow

Green

Red

Off

On

Off

The board will be in occupied mode if the unoccupied 

terminal (U) is open.

Thermostat Inputs (G, Y1, Y2, W1 

and W2)

Thermostat inputs used during occupied operation are 

G, Y1, and W1, which when energized will activate the 

Fan Only, Cooling Mode, and Heating Mode respectively. 

Input W2 and Y2 work the same as W1 and Y1 

respectively for single circuit units in occupied mode. For 

information on W2 and Y2 for dual circuit units, refer to 

"Dual Circuit Units" on page 

17

.

The MicroTech III unit controller is configured so that 

when either the Y1 or W1 input is energized the unit fan 

is also activated with Cooling or Heating Modes. In other 

words, energizing Y1 and G together will have the same 

effect as energizing just Y1. The W1 input has priority 

over the Y1 input. In situations when both inputs W1 and 

Y1 become energized (unlikely) in any order the unit will 

go into the Heating Mode as described below: 

1 . 

If the unit is in Cooling Mode, Y1 is energized. If 

W1 becomes energized and remains energized, the 

following will occur:

• The compressor de-energizes.
• The compressor restarts at 360 seconds

(compressor minimum off timer).

• The reversing valve output energizes within 5

seconds of the compressor being energized

(Heating Mode position).

2 . 

If the unit is in Cooling Mode, Y1 is energized. If 

W1 becomes energized momentarily, the controller 

de-energizes the compressor for 360 seconds 

(compressor minimum off timer) and then returns to 

the cooling mode.

3 . 

However, if the unit is in Heating Mode, W1 is 

energized. If Y1 becomes energized the unit 

remains in Heating Mode.

4 . 

Y2 is the second stage cooling, and applies to dual 

compressor units.

Control Inputs (HP, LP, SLTS, COF, 

U, E, O)

The control inputs are High Pressure (HP), Low 

Pressure (LP), Suction Line Temperature Sensor (SLTS), 

Condensate Overflow (COF), Unoccupied (U), and 

Remote Shutdown (E). The control inputs are in normal 

states during occupied mode. The state of each control 

in occupied mode during normal operation is as follows:

High / Low Pressure (HP, LP): energizes, switch is

closed (no fault).

• Suction Line Temperature Sensor (SLTS):

temperature sensor on the suction line which

provides low temperature protection.

• Condensate Overflow(COF):sensing no condensate

water in the condensate drain pan (no fault).

Unoccupied (U): open (no signal).

• Remote Shutdown (E): open (no signal).
• Tenant Override (O): has no effect in occupied mode.

M

ICro

t

eCh

 III u

nIt

 C

ontroller

Summary of Contents for MicroTech III

Page 1: ...ion Maintenance Manual MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH CCW VFC VFW MHC MHW LVC LVW OM 931 6 Group WSHP Part Number 910157590 Date September...

Page 2: ...al Equipment 15 Appendix A 15 Operation and Maintenance of I O Expansion Module 15 Start up 16 Initial Power up 16 Operation 17 Electric Heat Controls 17 Multiple Speed Fan Control 17 Circuit Two Addi...

Page 3: ...ump LonWorks Communication Module IM 928 MicroTech III Water Source Heat Pump Unit Controller BACnet MS TP Communication Module IM 933 LonWorks Plug In Software for use with MicroTech III Unitary Cont...

Page 4: ...put H7 1 1 No Connection H7 2 No Connection MicroTech III Unit Controller H7 3 Red LED Output H7 4 Green LED Output H7 5 Yellow LED Output H7 6 Red Green Yellow LED Common H8 1 1 Isolation Valve Pump...

Page 5: ...M 931 6 MicroTech III Unit Controller for WSHP 5 www DaikinApplied com MicroTech III Unit Controller MicroTech III Unit Controller Connections Figure 1 MicroTech III Unit Controller Terminal Locations...

Page 6: ...ed Service Test Mode Fan Operation JP2 Open Continuous Fan Operation On when not operating in the unccupied mode Shorted Cycling Fan Operation Auto Loop Fluid JP3 see warning Open Water Loop Fluid wat...

Page 7: ...1 and Y1 respectively for single circuit units in occupied mode For information on W2 and Y2 for dual circuit units refer to Dual Circuit Units on page 17 The MicroTech III unit controller is configur...

Page 8: ...hen the Y1 terminal is de energized the following occurs 1 The compressor de energizes 2 The fan de energizes unless the G terminal is energized 24VAC or JP2 is open 3 The IV PR H8 control output ener...

Page 9: ...unit operation No faults or modes have higher priority than a brownout fault condition Remote shutdown and brownout conditions have the same level of priority See Priority of Faults and Modes on page...

Page 10: ...r LP circuit is closed the unit does not return to normal operation until the control board is reset The unit is locked out in this manner until the unit can be serviced The control board is reset by...

Page 11: ...ers an automatic lockout on the 3rd fault The retry count is reset to zero every 24 hours Refer to Table 3 Faults Tenant Override Note It is recommended that the Occupied Opera tion on page 7 and Unoc...

Page 12: ...figured with mode and fault priorities Table 4 illustrates that the lower the priority level number the higher the priority of the fault or mode There are some exceptions to this priority list For exa...

Page 13: ...y adhere to field wiring procedures regarding proper lockout and tagout of components Figure 6 MicroTech III Unit Controller LED Status and Faults Troubleshooting Reference Flash Yellow LED Read Outpu...

Page 14: ...pressor wiring for defective wiring or loose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal wind...

Page 15: ...evice to drive a mechanical relay not supplied by Daikin then use the mechanical relay s dry contacts to drive the desired MicroTech III unit controller input The MicroTech III unit controller s valve...

Page 16: ...R Dehumidification JP2 JP2 Open None default JP2 Shorted Hot Gas Water Reheat HGR Secondary Heating Options JP3 JP4 JP3 Open None JP4 Open JP3 Shorted Supplemental Electric Heat JP4 Open JP3 Open Boil...

Page 17: ...xpansion Module and no electric heat it is possible to configure the I O Expansion Module for a two speed fan If there is a call for continuous fan compressor off the fan motor runs in low speed If th...

Page 18: ...in 6 H8 Pin 1 Dual compressor compressor 2 normally open output all others fan medium speed normally open Pin 2 24 VAC common Pin 3 No connection Pin 4 Dual compressor reversing valve for circuit 2 al...

Page 19: ...nit mounted return air discharge air and leaving water temperature sensor Wall mounted temperature sensors include setpoint adjustment and tenant override The user has the capability of substituting t...

Page 20: ...he range 0 127 Four green status LEDs on the communication module indicate communication activity on the MS TP communication network and with the unit controller Figure 10 MicroTech III BACnet MS TP S...

Page 21: ...emperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS Condensate Ov...

Page 22: ...ering Water Temperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS...

Page 23: ...d Entering Water Temperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor...

Page 24: ...d with ECM and or Secondary Electric Heat Table B 208V RED 230V ORG 460V BLK RED Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS Conden...

Page 25: ...able B 208V RED 230V ORG Notes Transformer Unused wire to be capped Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow...

Page 26: ...alve Capability Short Cycle Protection Random Start Unoccupied Mode Override Mode Pump Restart Loadshed Brownout Protection Unit Shutdown Condensate Overflow Protection Remote Reset 1 Intelligent Rese...

Page 27: ...OM 931 6 MicroTech III Unit Controller for WSHP 27 www DaikinApplied com This page left intentionally blank...

Page 28: ...o its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go...

Reviews: