OM 931-6 • MicroTech III Unit Controller for WSHP 

17 

www.DaikinApplied.com

o

peratIon

Dual Circuit Units

•  Provides standard lead / lag operation for two 

compressors in dual circuit units

•  The lag circuit will be enabled after the interstage 

timer has expired. The interstage timer defaults to 

300 seconds

•  HP, LP, SLTS fault for either circuit one or circuit two, 

will lockout the individual compressor.

Thermostat Inputs (Y2, W2)

•  The Y2 terminal which is cooling mode stage two, 

energizes the lag compressor

•  If Y1 and Y2 thermostat inputs are active at the same 

time, interstage timers will be used to stage the 

compressor up and down

•  The W2 terminal which is heating mode stage two, 

energizes the lag compressor.

•  If W1 and W2 thermostat inputs are active at the 

same time, interstage timers will be used to stage the 

compressors up and down

Electric Heat Controls

Boilerless Heat Coil Control

•  Turns on the factory installed heater when the water 

loop fluid entering water temperature is less than 

55°F. The fixed 55°F is used when jumper JP3 

setting is open

•  For geothermal applications (glycol loop fluid), 

the factory installed electric heater turns on when 

the entering water temperature is less than 28°F. 

The fixed 28°F is used when jumper JP3 setting is 

shorted

Note: 

In both cases the compressor is shut down.

Multiple Speed Fan Control

•  When the Water Source Heat Pump is equipped 

with an I/O Expansion Module and factory installed 

electric heat, three speed fan control is possible.

•  If the thermostat is calling for continuous fan 

operation and the compressor is not running the fan 

motor will run in low speed.

•  If there is a call for heating or cooling (compressor is 

running) the fan motor will run in medium speed.

•  If the electric heater is enabled the fan motor will run 

in high speed.

Note:  On units with an I/O Expansion Module and no 

electric heat, it is possible to configure the I/O 

Expansion Module for a two speed fan. If there is 

a call for continuous fan (compressor off) the fan 

motor runs in low speed. If there is a call for heat-

ing or cooling (compressor on) the fan motor runs 

at high speed.

Three-Speed Fan Operations

Table 8: Three-Speed Fan

Continuous 

Fan

Compressor 

On

Electric Heat

Space Temp 

Satisfied

Low Speed

Off

Off

Compressor 

Heating/Cooling

Off

Med. Speed

Off

Electric Heat 

Enabled

Off

Off

High Speed

Two-Speed Fan Operations

Table 9: Two-Speed Fan

Continuous 

Fan

Compressor 

On

Electric Heat

Space Temp 

Satisfied

Low Speed

Off

Off

Compressor 

Heating/Cooling

Off

High Speed

Off

Electric Heat 

Enabled

Off

Off

High Speed

Circuit Two, Additional Operating 

Modes

The I/O Expansion Module controls the second circuit 

high pressure, low pressure, and low suction line 

temperature operating conditions in the same manner as 

the main board controls the first circuit.

Table 10: I/O Expansion Module LED & Fault Outputs

Mode / Fault

Status LED's

Thermostat 

Output 

Terminal “A”

Yellow Green

Red

Invalid Configuration Jumper 

Setting

Flash

Flash

Off

De-energized

Base Board Communication 

Failure

Off

Flash

Flash

N/A

High Pressure #2 Fault

Off

Off

Flash

De-energized

Low Pressure #2 Fault

Off

Off

On

De-energized

Low Suction Temp #2 Fault 

Flash

Off

Off

De-energized

Sensor Failures Low Suction 

Low Suction Temp #2, 

1

 EWT (w/ Boilerless EH only)

Flash

Flash

On

De-energized

2

 Service Test Mode Enabled

Flash

Flash

Flash

Energized

Unoccupied Mode

On

On

Off

Energized

Occupied, Bypass, Standby, 

or Tenant Override Modes

Off

On

Off

Energized

Note:  All conditions in table 10 are with configuration jumper JP4 open on the 

main control board. Mode / Faults are listed in order of priority. 

 

1

  Boilerless electric heat only

 

2

  Alarm/fault LED indications take precedence over service   

 

   test mode LED indication. The controller shall use service  

 

   test mode if the service test mode jumper is installed, even if  

 

   the LED’s indicate an alarm/fault.

Summary of Contents for MicroTech III

Page 1: ...ion Maintenance Manual MicroTech III Unit Controller for Water Source Heat Pump Units Used with Enfinity Models CCH CCW VFC VFW MHC MHW LVC LVW OM 931 6 Group WSHP Part Number 910157590 Date September...

Page 2: ...al Equipment 15 Appendix A 15 Operation and Maintenance of I O Expansion Module 15 Start up 16 Initial Power up 16 Operation 17 Electric Heat Controls 17 Multiple Speed Fan Control 17 Circuit Two Addi...

Page 3: ...ump LonWorks Communication Module IM 928 MicroTech III Water Source Heat Pump Unit Controller BACnet MS TP Communication Module IM 933 LonWorks Plug In Software for use with MicroTech III Unitary Cont...

Page 4: ...put H7 1 1 No Connection H7 2 No Connection MicroTech III Unit Controller H7 3 Red LED Output H7 4 Green LED Output H7 5 Yellow LED Output H7 6 Red Green Yellow LED Common H8 1 1 Isolation Valve Pump...

Page 5: ...M 931 6 MicroTech III Unit Controller for WSHP 5 www DaikinApplied com MicroTech III Unit Controller MicroTech III Unit Controller Connections Figure 1 MicroTech III Unit Controller Terminal Locations...

Page 6: ...ed Service Test Mode Fan Operation JP2 Open Continuous Fan Operation On when not operating in the unccupied mode Shorted Cycling Fan Operation Auto Loop Fluid JP3 see warning Open Water Loop Fluid wat...

Page 7: ...1 and Y1 respectively for single circuit units in occupied mode For information on W2 and Y2 for dual circuit units refer to Dual Circuit Units on page 17 The MicroTech III unit controller is configur...

Page 8: ...hen the Y1 terminal is de energized the following occurs 1 The compressor de energizes 2 The fan de energizes unless the G terminal is energized 24VAC or JP2 is open 3 The IV PR H8 control output ener...

Page 9: ...unit operation No faults or modes have higher priority than a brownout fault condition Remote shutdown and brownout conditions have the same level of priority See Priority of Faults and Modes on page...

Page 10: ...r LP circuit is closed the unit does not return to normal operation until the control board is reset The unit is locked out in this manner until the unit can be serviced The control board is reset by...

Page 11: ...ers an automatic lockout on the 3rd fault The retry count is reset to zero every 24 hours Refer to Table 3 Faults Tenant Override Note It is recommended that the Occupied Opera tion on page 7 and Unoc...

Page 12: ...figured with mode and fault priorities Table 4 illustrates that the lower the priority level number the higher the priority of the fault or mode There are some exceptions to this priority list For exa...

Page 13: ...y adhere to field wiring procedures regarding proper lockout and tagout of components Figure 6 MicroTech III Unit Controller LED Status and Faults Troubleshooting Reference Flash Yellow LED Read Outpu...

Page 14: ...pressor wiring for defective wiring or loose connection Check for faulty compressor capacitor Insufficient cooling or heating Check for lock rotor amp draw Check for defective compressor internal wind...

Page 15: ...evice to drive a mechanical relay not supplied by Daikin then use the mechanical relay s dry contacts to drive the desired MicroTech III unit controller input The MicroTech III unit controller s valve...

Page 16: ...R Dehumidification JP2 JP2 Open None default JP2 Shorted Hot Gas Water Reheat HGR Secondary Heating Options JP3 JP4 JP3 Open None JP4 Open JP3 Shorted Supplemental Electric Heat JP4 Open JP3 Open Boil...

Page 17: ...xpansion Module and no electric heat it is possible to configure the I O Expansion Module for a two speed fan If there is a call for continuous fan compressor off the fan motor runs in low speed If th...

Page 18: ...in 6 H8 Pin 1 Dual compressor compressor 2 normally open output all others fan medium speed normally open Pin 2 24 VAC common Pin 3 No connection Pin 4 Dual compressor reversing valve for circuit 2 al...

Page 19: ...nit mounted return air discharge air and leaving water temperature sensor Wall mounted temperature sensors include setpoint adjustment and tenant override The user has the capability of substituting t...

Page 20: ...he range 0 127 Four green status LEDs on the communication module indicate communication activity on the MS TP communication network and with the unit controller Figure 10 MicroTech III BACnet MS TP S...

Page 21: ...emperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS Condensate Ov...

Page 22: ...ering Water Temperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS...

Page 23: ...d Entering Water Temperature EWT sensor is included with ECM and or Secondary Electric Heat Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor...

Page 24: ...d with ECM and or Secondary Electric Heat Table B 208V RED 230V ORG 460V BLK RED Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor CDS Conden...

Page 25: ...able B 208V RED 230V ORG Notes Transformer Unused wire to be capped Legend Item Description C1 Capacitor Compressor C2 Capacitor Fan CC Compressor Contactor CM Compressor Motor COS Condensate Overflow...

Page 26: ...alve Capability Short Cycle Protection Random Start Unoccupied Mode Override Mode Pump Restart Loadshed Brownout Protection Unit Shutdown Condensate Overflow Protection Remote Reset 1 Intelligent Rese...

Page 27: ...OM 931 6 MicroTech III Unit Controller for WSHP 27 www DaikinApplied com This page left intentionally blank...

Page 28: ...o its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representative go...

Reviews: