IM 972-2 • MAVERICK I ROOFTOP SYSTEMS 24 www.DaikinApplied.com
Physical Data
Auxiliary Heater Kit Performance
Table 13: Auxiliary Heater Kits Characteristics and Application: 208/240V — 3 Phase
Unit Model Number
MPS
Heater Kit
Model No . RXJJ
Heater Kw @
208/240 V/3 Phase
Heater Kit Fla
Unit Min . Ckt . Ampacity
Max . Fuse or Ckt . Bkr . Size
(Ckt . Bkr . Must Be HACR
Type For USA)
015 Low Static Drive
NONE
—
—
78/78
100/100
CE20C
14.4/19.2
40.0/46.2
78/78
100/100
CE40C
28.8/38.3
79.9/92.2
115/130
125/150
CE60C
43.2/57.5
119.9/138.3
165/188
175/200
CE75C
54/71.9
149.8/172.8
202/231
225/250
015 High Static Drive
NONE
—
—
81/81
100/100
CE20C
14.4/19.2
40.0/46.2
81/81
100/100
CE40C
28.8/38.3
79.9/92.2
119/134
125/150
CE60C
43.2/57.5
119.9/138.3
169/192
175/200
CE75C
54/71.9
149.8/172.8
206/235
225/250
020 Low Static Drive
NONE
—
—
101/101
125/125
CE20C
14.4/19.2
40.0/46.2
101/101
125/125
CE40C
28.8/38.3
79.9/92.2
119/134
125/150
CE60C
43.2/57.5
119.9/138.3
169/192
175/200
CE75C
54/71.9
149.8/172.8
206/235
225/250
020 High Static Drive
NONE
—
—
109/109
125/125
CE20C
14.4/19.2
40.0/46.2
109/109
125/125
CE40C
28.8/38.3
79.9/92.2
129/145
150/150
CE60C
43.2/57.5
119.9/138.3
179/202
200/225
CE75C
54/71.9
149.8/172.8
217/245
225/250
025 Low Static Drive
NONE
—
—
147/147
175/175
CE20C
14.4/19.2
40.0/46.2
147/147
175/175
CE40C
28.8/38.3
79.9/92.2
147/147
175/175
CE60C
43.2/57.5
119.9/138.3
181/204
200/225
CE75C
54/71.9
149.8/172.8
218/247
225/250
025 High Static Drive
NONE
—
—
149/149
175/175
CE20C
14.4/19.2
40.0/46.2
149/149
175/175
CE40C
28.8/38.3
79.9/92.2
149/151
175/175
CE60C
43.2/57.5
119.9/138.3
186/209
200/225
CE75C
54/71.9
149.8/172.8
223/252
225/300
Summary of Contents for Maverick I