IM 972-2 • MAVERICK I ROOFTOP SYSTEMS 26 www.DaikinApplied.com
Physical Data
Table 15: Auxiliary Heater Kits Characteristics and Application: 600V — 3 Phase
Unit Model Number
MPS
Heater Kit
Model No . RXJJ
Heater Kw @ 600V
Heater Kit Fla
Unit Min . Ckt . Ampacity
Max . Fuse or Ckt . Bkr . Size
(Ckt . Bkr . Must Be HACR
Type For USA)
015 Low Static Drive
NONE
—
—
28
35
CE20Y
19.2
18.5
28
35
CE40Y
38.4
37
51
60
CE60Y
57.6
55.4
74
80
CE75Y
72
69.3
92
100
015 High Static Drive
NONE
—
—
30
35
CE20Y
19.2
18.5
30
35
CE40Y
38.4
37
53
60
CE60Y
57.6
55.4
76
80
CE75Y
72
69.3
94
100
020 Low Static Drive
NONE
—
—
40
50
CE20Y
19.2
18.5
40
50
CE40Y
38.4
37
53
60
CE60Y
57.6
55.4
76
80
CE75Y
72
69.3
94
100
020 High Static Drive
NONE
—
—
42
50
CE20Y
19.2
18.5
42
50
CE40Y
38.4
37
56
60
CE60Y
57.6
55.4
80
80
CE75Y
72
69.3
97
100
025 Low Static Drive
NONE
—
—
47
60
CE20Y
19.2
18.5
47
60
CE40Y
38.4
37
53
60
CE60Y
57.6
55.4
76
80
CE75Y
72
69.3
94
100
025 High Static Drive
NONE
—
—
50
60
CE20Y
19.2
18.5
50
60
CE40Y
38.4
37
59
60
CE60Y
57.6
55.4
82
90
CE75Y
72
69.3
100
100
Summary of Contents for Maverick I