![background image](http://html2.mh-extra.com/html/daikin/maverick-i-mpsa07d/maverick-i-mpsa07d_installation-and-maintenance-manual_5693281058.webp)
IM 971-3 • MAVERICK I 58 www.DaikinApplied.com
Performance Data
Performance Data
Airflow Performance
Figure 38:
Airflow Performance – MPS 007D
Air
Flow
CFM
[L/s]
Model MPS 007D
External Static Pressure—Inches of Water [kPa]
0 .1 [ .02] 0 .2 [ .05] 0 .3 [ .07] 0 .4 [ .10] 0 .5 [ .12] 0 .6 [ .15] 0 .7 [ .17] 0 .8 [ .20] 0 .9 [ .22] 1 .0 [ .25] 1 .1 [ .27] 1 .2 [ .30] 1 .3 [ .32] 1 .4 [ .35] 1 .5 [ .37] 1 .6 [ .40] 1 .7 [ .42] 1 .8 [ .45] 1 .9 [ .47] 2 .0 [ .50]
RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W
2400
[1133]
—
— 551 782 585 814 619 848 652 885 684 926 717 969 748 1016 780 1065 810 1118 841 1174 870 1233 900 1294 929 1359 957 1427 985 1498 1012 1572 1039 1649 1065 1729 1091 1813
2500
[1180]
—
— 562 816 596 848 629 884 661 923 693 964 725 1009 756 1057 787 1108 817 1162 846 1219 876 1279 904 1343 933 1409 960 1478 987 1550 1014 1626 1040 1704 1066 1786 1092 1870
2600
[1227]
—
— 574 851 607 885 639 922 671 962 702 1006 733 1052 764 1101 794 1153 823 1209 852 1267 881 1329 909 1393 937 1461 964 1531 990 1605 1016 1682 1042 1762 1067 1844 1092 1930
2700
[1274]
553 857 585 889 618 925 650 963 681 1004 712 1049 742 1096 772 1147 801 1201 830 1258 858 1317 886 1380 914 1446 941 1515 967 1587 993 1662 1019 1740 1044 1821 1068 1905 1092 1993
2800
[1321]
565 896 597 930 629 966 660 1006 691 1049 721 1095 751 1144 780 1196 808 1251 837 1309 864 1370 892 1434 919 1501 945 1572 971 1645 996 1721 1021 1801 1045 1883 1069 1969 1093 2057
2900
[1368]
577 937 609 972 640 1010 670 1051 701 1096 730 1143 759 1193 788 1246 816 1303 843 1362 871 1425 897 1490 923 1559 949 1630 974 1705 999 1783 1023 1864 1047 1948 1070 2035 1093 2124
3000
[1416]
590 981 621 1017 651 1057 681 1099 710 1145 739 1193 768 1245 796 1300 823 1357 850 1418 877 1482 903 1549 928 1619 953 1692 978 1768 1002 1847 1026 1929 1049 2014 1072 2103 1094 2194
3100
[1463]
602 1027 633 1065 662 1105 692 1149 720 1196 749 1246 777 1299 804 1355 831 1414 857 1476 883 1541 908 1610 933 1681 958 1755 982 1833 1005 1913 1028 1997 1051 2083 1073 2173 1094 2266
3200
[1510]
615 1075 645 1114 674 1157 702 1202 731 1250 758 1301 785 1356 812 1413 838 1473 864 1537 889 1603 914 1673 938 1746 962 1821 986 1900 1008 1982 1031 2067 1053 2155 1074 2246 1095 2340
3300
[1557]
628 1126 657 1166 685 1210 713 1256 741 1306 768 1359 794 1414 820 1473 846 1535 871 1600 896 1668 920 1739 944 1813 967 1890 989 1970 1012 2053 1033 2139 1055 2229 1075 2321 1096 2416
3400
[1604]
640 1179 669 1221 697 1266 724 1314 751 1365 777 1419 803 1476 829 1536 854 1599 878 1665 902 1734 926 1807 949 1882 971 1960 993 2042 1015 2126 1036 2214 1057 2305 1077 2398 1097 2495
3500
[1652]
653 1235 681 1278 708 1324 735 1373 761 1425 787 1481 812 1539 837 1601 861 1665 885 1733 909 1803 932 1877 954 1954 976 2034 997 2116 1018 2202 1039 2291 1059 2383 1078 2478 1097 2576
3600
[1699]
666 1292 693 1337 720 1384 746 1435 771 1489 797 1545 821 1605 845 1668 869 1734 892 1803 915 1875 938 1950 959 2028 981 2109 1001 2193 1022 2280 1042 2371 1061 2464 1080 2560 1098 2660
NOTE:
A/F-Drive left of 1st bold line, B/G-Drive in middle of bold lines, C/H-Drive right of 2nd bold line
Drive Package
A/F
B/G
C/H
Motor H .P . [W]
2.0 [1491.4]
3.0 [2237.1]
3.0 [2237.1]
Blower Sheave
AK84H
AK84H
AK84H
Motor Sheave
1VL40*7/8
1VP50*7/8
1VP56*7/8
Turns Open
0
1
2
3
4
5
0
1
2
3
4
5
0
1
2
3
4
5
RPM
767
721
678
635
590
548
992
949
908
866
823
782
1108 1067 1029 987
946
905
NOTES:
1. Factory sheave settings are shown in bold type.
2. Do not set motor sheave below minimum or maximum turns open shown.
3. Re-adjustment of sheave required to achieve rated airflow at AHRI minimum External Static Pressure
4. Add component resistance (below) to duct resistance to determine total External Static Pressure.
Airflow Correction Factors – 7.5 Ton [26.4 kW]
Actual CFM [L/s] 2400
[1133]
2600
[1227]
2800
[1321]
3000
[1416]
3200
[1510]
3400
[1605]
3600
[1699]
Total MBH
0.96
0.97
0.98
0.99
1.00
1.01
1.02
Sensible MBH
0.89
0.92
0.95
0.97
1.00
1.03
1.06
Power kW
0.98
0.99
0.99
1.00
1.01
1.01
1.02
NOTES:
[ ] Designates Metric Conversions
1. Multiply correction factor times gross performance data.
2. Resulting sensible capacity cannot exceed total capacity.
3. Add component resistance to duct resistance to
determine total external static pressure.
4. DNA = Data not Available.
Component Air Resistance, IWC – 7 .5 TON [26 .4 kW]
Component
2400
[1133]
2600
[1227]
2800
[1321]
3000
[1416]
3200
[1510]
3400
[1605]
3600
[1699]
Resistance – Inches Water [kPa]
Wet Coil
0.04
[0.01]
0.05
[0.01]
0.06
[0.01]
0.07
[0.02]
0.07
[0.02]
0.08
[0.02]
0.09
[0.02]
Vertical
Economizer 100%
R.A. Damper
Open
0.01
[0.00]
0.02
[0.01]
0.04
[0.01]
0.05
[0.01]
0.07
[0.02]
0.09
[0.02]
0.11
[0.03]