Electrical Data
Electrical Data
Compressor and Condenser Motor
Table 15:
Compressor and Condenser Motor Data – 208/230 Volt
Data
MPS 007D
MPS 008D
MPS 010D
MPS 012D
Compressor Motor
Number.
1
1
1
2
Phase
3
RPM
3450
HP, Compressor 1
7
7.5
10
6
Amps (RLA), Comp. 1
25.3
28.8
32.6
25
Amps (LRA), Comp. 1
184.0
191
240
164
HP, Compressor 2
N/A
N/A
N/A
6
Amps (RLA), Comp. 2
N/A
N/A
N/A
25
Amps (LRA), Comp. 2
N/A
N/A
N/A
164
Condenser Motor
Number
2
Phase
1
HP
1/5
1/5
1/3
3/4
Amps (FLA, each)
1.2
1.2
2.4
4.2
Amps (LRA, each)
2.3
2.3
4.7
10.1
NOTE:
*Unit operating voltage range is 187 – 253
Table 16:
Compressor and Condenser Motor Data – 460 Volt
Data
MPS 007D
MPS 008D
MPS 010D
MPS 012D
Compressor Motor
Number.
1
1
1
2
Phase
3
RPM
3450
HP, Compressor 1
7
7.5
10
6
Amps (RLA), Comp. 1
9.6
12.5
14.8
12.8
Amps (LRA), Comp. 1
84
100
130
100
HP, Compressor 2
N/A
N/A
N/A
6
Amps (RLA), Comp. 2
N/A
N/A
N/A
12.8
Amps (LRA), Comp. 2
N/A
N/A
N/A
100
Condenser Motor
Number.
2
Phase
1
HP
1/5
1/5
1/3
3/4
Amps (FLA, each)
0.8
0.8
1.4
2.3
Amps (LRA, each)
1.4
1.4
2.4
4.9
NOTE:
*Unit operating voltage range is 414 – 506
MCA and MCOP
Table 17: Unit MCA and MCOP Data
MPS Model Drive Package
Voltage
208/230
460
575
Low*
Medium
High
Low*
Medium
High
Low*
Medium
High
007D
MCA
41.0
44.0
44.0
17.0
19.0
19.0
13.0
14.0
14.0
MCOP
60.0
60.0
60.0
25.0
25.0
25.0
15.0
20.0
20.0
008D
MCA
46.0
48.0
51.0
21.0
22.0
24.0
16.0
17.0
17.0
MCOP
70.0
70.0
70.0
30.0
30.0
35.0
25.0
25.0
25.
010D
MCA
54.0
56.0
58.0
26.0
32.0
34.0
19.0
20.0
20.0
MCOP
80.0
80.0
90.0
40.0
45.0
45.0
25.0
30.0
30.0
012D
MCA
70.0
75.0
—
34.0
37.0
—
25.0
27.0
—
MCOP
90.0
90.0
—
40.0
45.0
—
30.0
30.0
—
NOTE:
*Low static option is a direct drive motor for models 003 and 004