Performance Data

www.DaikinApplied.com 63 

IM 971-3 • MAVERICK I

Figure 43: 

Side Airflow Performance – MPS 010D

Air 

Flow 

CFM 

[L/s]

Model MPS 010D

External Static Pressure—Inches of Water [kPa]

0  .1 [  .02] 0 .2 [ .05]  0 .3 [ .07] 0 .4 [ .10] 0 .5 [ .12] 0 .6 [ .15] 0 .7 [ .17] 0 .8 [ .20] 0 .9 [ .22] 1 .0 [ .25] 1 .1 [ .27] 1 .2 [ .30] 1 .3 [ .32] 1 .4 [ .35] 1 .5 [ .37] 1 .6 [ .40] 1 .7 [ .42] 1 .8 [ .45] 1 .9 [ .47] 2 .0 [ .50]

RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W RPM W

3200 

[1510]

575 1018 607 1057 637 1099 667 1143 697 1191 727 1240 756 1293 785 1348 814 1406 842 1466 870 1529 897 1595 924 1664 951 1735 978 1809 1004 1885 1030 1965 1055 2047 1080 2131 1105 2219

3300 

[1557]

588 1060 618 1101 649 1146 679 1192 708 1242 737 1294 766 1349 795 1406 823 1466 850 1529 878 1595 905 1663 932 1734 958 1808 984 1884 1010 1963 1035 2045 1060 2129 1085 2216 1109 2306

3400 

[1604]

600 1106 630 1150 660 1196 690 1245 719 1297 748 1352 776 1409 804 1469 832 1531 859 1597 886 1664 913 1735 939 1808 965 1884 990 1963 1016 2044 1040 2128 1065 2215 1089 2305 1113 2397

3500 

[1652]

613 1156 643 1202 672 1251 701 1302 730 1357 758 1413 786 1473 814 1535 841 1600 868 1668 894 1738 920 1811 946 1887 972 1965 997 2046 1022 2130 1046 2217 1070 2306 1094 2397 1117 2492

3600 

[1699]

626 1210 655 1258 684 1310 713 1364 741 1420 769 1479 796 1541 823 1606 850 1673 877 1743 903 1816 929 1892 954 1970 979 2050 1004 2134 1028 2220 1052 2309 1076 2400 1099 2494 1122 2591

3700 

[1746]

639 1268 668 1319 696 1373 724 1429 752 1488 779 1550 806 1614 833 1681 860 1751 886 1823 911 1898 937 1976 962 2056 986 2140 1011 2225 1035 2314 1058 2405 1081 2499 1104 2596 1127 2695

3800 

[1793]

652 1330 680 1384 708 1440 736 1498 763 1560 790 1624 817 1690 843 1760 869 1832 895 1907 920 1984 945 2064 970 2147 994 2233 1018 2321 1041 2412 1064 2505 1087 2602 1110 2701 1132 2802

3900 

[1840]

665 1397 693 1452 721 1511 748 1572 775 1636 801 1702 828 1771 854 1843 879 1917 904 1995 929 2075 954 2157 978 2242 1001 2330 1025 2421 1048 2514 1071 2610 1093 2709 1115 2810 1137 2914

4000 

[1888]

678 1467 706 1525 733 1586 760 1650 787 1716 813 1785 839 1856 864 1930 889 2007 914 2087 938 2169 962 2254 986 2341 1009 2432 1032 2525 1055 2620 1077 2719 1099 2820 1121 2923 1142 3030

4100 

[1935]

692 1542 719 1602 746 1666 772 1731 798 1800 824 1871 850 1945 875 2022 899 2101 923 2183 947 2267 971 2355 994 2445 1017 2537 1040 2633 1062 2731 1084 2831 1105 2935 1126 3041 1147 3150

4200 

[1982]

706 1621 732 1684 759 1749 785 1817 810 1888 836 1962 861 2038 885 2117 909 2199 933 2283 957 2370 980 2460 1003 2552 1025 2647 1047 2745 1069 2845 1091 2948 1112 3054 1132 3163 1153 3274

4300 

[2029]

720 1704 746 1769 772 1837 797 1907 823 1981 847 2057 872 2135 896 2217 920 2301 943 2387 966 2477 989 2569 1012 2664 1034 2761 1055 2861 1077 2964 1098 3069 1118 3178 1139 3288 1158 3402

4400 

[2076]

734 1791 760 1858 785 1928 810 2001 835 2077 859 2155 883 2237 907 2320 931 2407 954 2496 976 2587 999 2682 1020 2779 1042 2879 1063 2981 1084 3087 1105 3195 1125 3305 1145 3418 —

4500 

[2123]

748 1882 773 1952 798 2024 823 2100 847 2178 871 2259 895 2342 918 2428 941 2517 964 2608 986 2702 1008 2799 1030 2899 1051 3001 1071 3106 1092 3214 1112 3324 1132 3437 1151 3552 —

4600 

[2171]

762 1977 787 2049 812 2124 836 2202 860 2283 884 2366 907 2451 930 2540 952 2631 974 2725 996 2822 1018 2921 1039 3023 1059 3127 1080 3235 1100 3345 1120 3457 1139 3573 1158 3691 —

4700 

[2218]

777 2076 801 2151 826 2228 849 2309 873 2391 896 2477 919 2565 941 2656 963 2750 985 2846 1006 2945 1027 3046 1048 3151 1068 3258 1088 3367 1108 3480 1127 3595 1146 3712 —

4800 

[2265]

792 2180 816 2257 840 2337 863 2419 886 2504 909 2592 931 2683 953 2776 975 2872 996 2971 1017 3072 1037 3176 1058 3283 1077 3392 1097 3504 1116 3619 1135 3736 1153 3856 —

NOTE: 

A/F-Drive left of 1st bold line, B/G-Drive in middle of bold lines, C/H-Drive right of 2nd bold line.

Drive Package

A/F

B/G

C/H

Motor H .P . [W]

2.0 [1491.4]

3.0 [2237.1]

3.0 [2237.1]

Blower Sheave

AK79H

AK79H

AK79H

Motor Sheave

1VL40*7/8

1VP50*7/8

1VP56*7/8

Turns Open

0

1

2

3

4

5

0

1

2

3

4

5

0

1

2

3

4

5

RPM

798

753

707

663

616

556 1041 998

955

912

867

824

1155 1119 1078 1037 994

951

NOTES: 

 

1. Factory sheave settings are shown in bold type. 

2. Do not set motor sheave below minimum or maximum turns open shown. 

3. Re-adjustment of sheave required to achieve rated airflow at AHRI minimum External Static Pressure

 

4. Add component resistance (below) to duct resistance to determine total External Static Pressure.

Airflow Correction Factors – 10.5 Ton [35.1 kW]

Actual 

CFM [L/s]

2700 

[1274]

2900 

[1368]

3100 

[1463]

3300 

[1557]

3500 

[1652]

3700 

[1746]

3900 

[1840]

4100 

[1935]

Total MBH

0.97

0.98

0.99

1.01

1.02

1.03

1.04

1.05

Sensible 

MBH

0.93

0.96

0.99

1.01

1.04

1.07

1.10

1.13

Power kW

0.99

0.99

1.00

1.00

1.01

1.02

1.02

1.03

NOTES: 

[ ] Designates Metric Conversions 

1.  Multiply correction factor times gross performance data.
2.  Resulting sensible capacity cannot exceed total capacity.
3.  Add component resistance to duct resistance to 

determine total external static pressure.

4.  DNA = Data not Available.

Component Air Resistance, IWC – 10 .5 Ton [35 .1 kW]

Component

2700 

[1274]

2900 

[1368]

3100 

[1463]

3300 

[1557]

3500 

[1652]

3700 

[1746]

3900 

[1840]

4100 

[1935]

Resistance – Inches Water [kPa]

Wet Coil

0.07 

[0.02]

0.08 

[0.02]

0.09 

[0.02]

0.10 

[0.03]

0.11 

[0.03]

0.13 

[0.03]

0.14 

[0.04]

0.15 

[0.04]

Vertical 

Economizer 

100% R.A. 

Damper Open

0.03 

[0.01]

0.04 

[0.01]

0.06 

[0.01]

0.08 

[0.02]

0.10 

[0.02]

0.12 

[0.03]

0.15 

[0.04]

0.17 

[0.04]

Summary of Contents for Maverick I MPSA07D

Page 1: ...tion and Maintenance IM 971 3 Group Controls Part Number IM 971 Date October 2018 Maverick I Commercial Package Rooftop Systems Heating and Cooling Models MPSA07D MPSA12D 7 through 12 Tons R 410A Refr...

Page 2: ...er Motor 54 MCA and MCOP 54 Auxiliary Heater Data 55 Dimensional Data 56 Unit Dimensions 56 Duct Dimensions 57 Curb Dimensions 57 Performance Data 58 Airflow Performance 58 Accessories 66 Non DDC Econ...

Page 3: ...the manufacturer into onto or in conjunction with the air conditioner you should be aware that the use of unauthorized components accessories or devices may adversely affect the operation of the air c...

Page 4: ...noise and vibration away from bedroom windows Location Considerations WARNING This unit may be used to heat the building or structure during construction if the following installation requirements ar...

Page 5: ...bustion air inlet hood properly installed This hood is shipped in a carton in the blower compartment inside the unit and must be attached when the unit is installed See Figure 46 on page 67 To attach...

Page 6: ...installed Rooftop Installation 1 Before locating the unit on the roof make sure that the roof structure is adequate to support the weight involved See Electrical Physical Tables in this manual THIS IS...

Page 7: ...y Tons kW Corner Weights by Percentage A B C D 7 5 12 5 21 1 44 0 26 34 17 23 Figure 6 Shipping Board Removal Figure 7 Roof Curb SPREADER BAR LIFTING BEAM CABLE OR CHAIN CENTER OF GRAVITY CENTER OF GR...

Page 8: ...carbon monoxide poisoning that could result in personal injury or death HGRH System The HGRH system controls both cooling and humidity loads In addition to two stages of cooling the unit includes two...

Page 9: ...75 to close fan proving switch before ramping to the desired speed Since the VFD operates on 24VDC control voltage a blower relay with 24VAC across the coil is used to turn the VFD on Blower speeds a...

Page 10: ...ory specified or approved parts In the commonwealth of Massachusetts installation must be performed by a licensed plumber or gas fitter for appropriate fuel Figure 9 Backup Wrench Location Figure 10 S...

Page 11: ...Natural Gas 5 10 5 3 5 LP Gas 11 13 10 Supply and manifold pressure taps are located on the gas valve body 1 8 N P T and on the manifold Use a properly calibrated manometer gauge for accurate gas pre...

Page 12: ...ng the furnace input make certain that all other gas units are shut OFF with the exception of pilot burners Time the meter with only the furnace in operation IMPORTANT NOTE FOR ALTITUDES ABOVE 2 000 F...

Page 13: ...n the unit rating plate 4 For through the base wiring entry reference Figure 13 All fittings and conduit are field supplied for this application Reference the chart with Table 10 on page 14 for proper...

Page 14: ...rise 35 C when installed in accordance with the manufacturer s instructions Internal Wiring A diagram of the internal wiring of this unit is located on the inside of control access panel and in this m...

Page 15: ...ptable to most residential 24 volt forced air multi stage systems with electric or fossil fuel auxiliary and is the ultimate for comfort convenience and performance See Figure 16 on page 16 for an opt...

Page 16: ...5 ton units a terminal block is not supplied Use a wirenut to extend from the leads provided in the unit to the thermostat W1 W2 and Y2 are optional depending upon the size and selected options of th...

Page 17: ...Wiring Diagrams www DaikinApplied com 17 IM 971 3 MAVERICK I Figure 17 MPS 012D 208 230 460 Volt Constant Volume Gas Heat Electromechanical Controls...

Page 18: ...IM 971 3 MAVERICK I 18 www DaikinApplied com Wiring Diagrams Figure 17 continued MPS 012D 208 230 460 Volt Constant Volume Gas Heat Electromechanical Controls...

Page 19: ...Wiring Diagrams www DaikinApplied com 19 IM 971 3 MAVERICK I Figure 18 MPS 007 010D 208 230 460 Volt Constant Volume Gas Heat DDC Controls...

Page 20: ...IM 971 3 MAVERICK I 20 www DaikinApplied com Wiring Diagrams Figure 18 continued MPS 007 010D 208 230 460 Volt Constant Volume Gas Heat DDC Controls...

Page 21: ...Wiring Diagrams www DaikinApplied com 21 IM 971 3 MAVERICK I Figure 19 MPS 007 010D 208 230 460 Volt Two Speed SAF Gas Heat Electromechanical Controls...

Page 22: ...IM 971 3 MAVERICK I 22 www DaikinApplied com Wiring Diagrams Figure 19 continued MPS 007 010D 208 230 460 Volt Two Speed SAF Gas Heat Electromechanical Controls...

Page 23: ...Wiring Diagrams www DaikinApplied com 23 IM 971 3 MAVERICK I Figure 20 MPS 012D 208 230 460 Volt Two Speed SAF Gas Heat Electromechanical Controls...

Page 24: ...IM 971 3 MAVERICK I 24 www DaikinApplied com Wiring Diagrams Figure 20 continued MPS 012D 208 230 460 Volt Two Speed SAF Gas Heat Electromechanical Controls...

Page 25: ...Wiring Diagrams www DaikinApplied com 25 IM 971 3 MAVERICK I Figure 21 MPS 007 010D 208 230 460 Volt Two Speed SAF Gas Heat DDC Controls...

Page 26: ...IM 971 3 MAVERICK I 26 www DaikinApplied com Wiring Diagrams Figure 21 continued MPS 007 010D 208 230 460 Volt Two Speed SAF Gas Heat DDC Controls...

Page 27: ...Wiring Diagrams www DaikinApplied com 27 IM 971 3 MAVERICK I Figure 22 MPS 012D 208 230 460 Volt Two Speed SAF Gas Heat DDC Controls...

Page 28: ...IM 971 3 MAVERICK I 28 www DaikinApplied com Wiring Diagrams Figure 22 continued MPS 012D 208 230 460 Volt Two Speed SAF Gas Heat DDC Controls...

Page 29: ...Wiring Diagrams www DaikinApplied com 29 IM 971 3 MAVERICK I Figure 23 MPS 007 010D 208 230 460 Volt Constant Volume Electromechanical Controls...

Page 30: ...IM 971 3 MAVERICK I 30 www DaikinApplied com Wiring Diagrams Figure 23 continued MPS 007 010D 208 230 460 Volt Constant Volume Electromechanical Controls...

Page 31: ...Wiring Diagrams www DaikinApplied com 31 IM 971 3 MAVERICK I Figure 24 MPS 012D 208 230 460 Volt Constant Volume Gas Heat DDC Controls...

Page 32: ...IM 971 3 MAVERICK I 32 www DaikinApplied com Wiring Diagrams Figure 24 continued MPS 012D 208 230 460 Volt Constant Volume Gas Heat DDC Controls...

Page 33: ...Wiring Diagrams www DaikinApplied com 33 IM 971 3 MAVERICK I Figure 25 MPS 007 010D 208 230 460 Volt Constant Volume Cooling Only Electromechanical Controls...

Page 34: ...IM 971 3 MAVERICK I 34 www DaikinApplied com Wiring Diagrams Figure 25 continued MPS 007 010D 208 230 460 Volt Constant Volume Cooling Only Electromechanical Controls...

Page 35: ...Wiring Diagrams www DaikinApplied com 35 IM 971 3 MAVERICK I Figure 26 MPS 012D 208 230 460 Volt Constant Volume Cooling Only Electromechanical Controls...

Page 36: ...IM 971 3 MAVERICK I 36 www DaikinApplied com Wiring Diagrams Figure 26 continued MPS 012D 208 230 460 Volt Constant Volume Cooling Only Electromechanical Controls...

Page 37: ...Wiring Diagrams www DaikinApplied com 37 IM 971 3 MAVERICK I Figure 27 MPS 007 010D 208 230 460 Volt Two Speed SAF Cooling Only Electromechanical Controls...

Page 38: ...IM 971 3 MAVERICK I 38 www DaikinApplied com Wiring Diagrams Figure 27 continued MPS 007 010D 208 230 460 Volt Two Speed SAF Cooling Only Electromechanical Controls...

Page 39: ...Wiring Diagrams www DaikinApplied com 39 IM 971 3 MAVERICK I Figure 28 MPS 012D 208 230 460 Volt Two Speed SAF Cooling Only Electromechanical Controls...

Page 40: ...IM 971 3 MAVERICK I 40 www DaikinApplied com Wiring Diagrams Figure 28 continued MPS 012D 208 230 460 Volt Two Speed SAF Cooling Only Electromechanical Controls...

Page 41: ...Wiring Diagrams www DaikinApplied com 41 IM 971 3 MAVERICK I Figure 29 MPS 007 010D 208 230 460 Volt Constant Volume Cooling Only DDC Controls...

Page 42: ...IM 971 3 MAVERICK I 42 www DaikinApplied com Wiring Diagrams Figure 29 continued MPS 007 010D 208 230 460 Volt Constant Volume Cooling Only DDC Controls...

Page 43: ...Wiring Diagrams www DaikinApplied com 43 IM 971 3 MAVERICK I Figure 30 MPS 012D 208 230 460 Volt Constant Volume Cooling Only DDC Controls...

Page 44: ...IM 971 3 MAVERICK I 44 www DaikinApplied com Wiring Diagrams Figure 30 continued MPS 012D 208 230 460 Volt Constant Volume Cooling Only DDC Controls...

Page 45: ...Wiring Diagrams www DaikinApplied com 45 IM 971 3 MAVERICK I Figure 31 MPS 007 010D 208 230 460 Volt Two Speed SAF Cooling Only DDC Controls...

Page 46: ...IM 971 3 MAVERICK I 46 www DaikinApplied com Wiring Diagrams Figure 31 continued MPS 007 010D 208 230 460 Volt Two Speed SAF Cooling Only DDC Controls...

Page 47: ...Wiring Diagrams www DaikinApplied com 47 IM 971 3 MAVERICK I Figure 32 MPS 012D 208 230 460 Volt Two Speed SAF Cooling Only DDC Controls...

Page 48: ...IM 971 3 MAVERICK I 48 www DaikinApplied com Wiring Diagrams Figure 32 continued MPS 012D 208 230 460 Volt Two Speed SAF Cooling Only DDC Controls...

Page 49: ...Wiring Diagrams www DaikinApplied com 49 IM 971 3 MAVERICK I Figure 33 MPS 007 010D 208 230 460 Volt Two Speed SAF with HGRH DDC Controls...

Page 50: ...IM 971 3 MAVERICK I 50 www DaikinApplied com Wiring Diagrams Figure 33 continued MPS 007 010D 208 230 460 Volt Two Speed SAF with HGRH DDC Controls...

Page 51: ...Wiring Diagrams www DaikinApplied com 51 IM 971 3 MAVERICK I Figure 34 MPS 012D 208 230 460 Volt Two Speed SAF with HGRH DDC Controls...

Page 52: ...IM 971 3 MAVERICK I 52 www DaikinApplied com Wiring Diagrams Figure 34 continued MPS 012D 208 230 460 Volt Two Speed SAF with HGRH DDC Controls...

Page 53: ...1 01 10 9 1 01 13 8 1 28 Rows fpi fpcm 1 20 8 1 20 8 1 20 8 2 18 7 Refrigerant control TX valves TX valves TX valves TX valves Drain connection in mm 1 0 75 19 05 1 0 75 19 05 1 0 75 19 05 1 0 75 19...

Page 54: ...50 HP Compressor 1 7 7 5 10 6 Amps RLA Comp 1 9 6 12 5 14 8 12 8 Amps LRA Comp 1 84 100 130 100 HP Compressor 2 N A N A N A 6 Amps RLA Comp 2 N A N A N A 12 8 Amps LRA Comp 2 N A N A N A 100 Condenser...

Page 55: ...P 14 4 17 3 26 30 DD20CP 19 8 23 8 35 35 DD30CP 28 8 34 6 48 50 DD40CP 39 6 47 6 64 70 MPS 008D Medium High Static Drive NONE 22 24 30 35 DD10CP 9 9 11 9 27 30 DD15CP 14 4 17 3 33 35 DD20CP 19 8 23 8...

Page 56: ...NEL BLOWER ACCESS PANEL HEAT EXCHANGER 150 MODEL 60 1524 mm 090 THRU 120 MODELS 50 1270 mm 89 2261 mm 577 8 1470 mm CONTROL ACCESS SERVICE DISCONNECT KNOCKOUT ACCESS PANEL COMPRESSOR FILTER ACCESS PAN...

Page 57: ...89 mm 371 2 953 mm 51 8 130 mm 197 8 505 mm 217 8 555 mm 593 8 1510 mm 57 8 149 mm 51 4 133 mm 15 381 mm 291 2 749 mm 13 330 mm Designates Metric Conversions 901 8 2289 mm 281 2 724 mm 63 4 171 mm 51...

Page 58: ...1095 2340 3300 1557 628 1126 657 1166 685 1210 713 1256 741 1306 768 1359 794 1414 820 1473 846 1535 871 1600 896 1668 920 1739 944 1813 967 1890 989 1970 1012 2053 1033 2139 1055 2229 1075 2321 1096...

Page 59: ...700 1746 663 1332 694 1393 724 1456 754 1521 783 1587 811 1654 838 1723 865 1793 891 1865 916 1938 941 2013 965 2089 988 2167 1010 2246 1032 2326 1053 2408 1073 2491 1092 2576 1111 2662 1129 2750 3800...

Page 60: ...1456 754 1521 783 1587 811 1654 838 1723 865 1793 891 1865 916 1938 941 2013 965 2089 988 2167 1010 2246 1032 2326 1053 2408 1073 2491 1092 2576 1111 2662 1129 2750 3800 1793 678 1400 708 1464 738 15...

Page 61: ...725 1447 753 1504 780 1563 807 1625 833 1690 860 1759 886 1830 911 1905 937 1982 961 2063 986 2146 1010 2233 1034 2322 1057 2415 1081 2510 1103 2609 1126 2711 3800 1793 653 1360 681 1409 709 1460 737...

Page 62: ...090 1130 3192 1147 3296 1164 3402 4300 2029 751 1784 779 1861 806 1939 832 2019 858 2100 883 2184 908 2269 932 2356 955 2445 978 2536 1000 2629 1022 2723 1043 2819 1063 2917 1082 3017 1101 3118 1119 3...

Page 63: ...54 1132 3163 1153 3274 4300 2029 720 1704 746 1769 772 1837 797 1907 823 1981 847 2057 872 2135 896 2217 920 2301 943 2387 966 2477 989 2569 1012 2664 1034 2761 1055 2861 1077 2964 1098 3069 1118 3178...

Page 64: ...54 958 2944 980 3036 1000 3135 1020 3239 1039 3349 1057 3465 1074 3588 1090 3716 1105 3849 1120 3989 1133 4135 1146 4287 1158 4444 1168 4608 1178 4777 1187 4953 1196 5134 1203 5321 1209 5514 1215 5713...

Page 65: ...0 1015 3256 1034 3354 1053 3453 1070 3552 1087 3653 1104 3754 1120 3856 1135 3959 1149 4063 1162 4167 1175 4273 1188 4379 1199 4486 1210 4594 1220 4703 5300 2501 991 3217 1010 3315 1030 3415 1048 3515...

Page 66: ...9 OA damper 6 12 ton Manual MXRF ADA1 26 12 21 10 OA damper Electromechanical Controls 6 12 ton Motorized MXRF ADB1 43 19 38 17 OA damper DDC Controls 6 12 ton Motorized MXRF ADC4 43 19 38 17 Power E...

Page 67: ...damper Single enthalpy CO2 input sensor available Field assembled hood ships with economizer Economizer ships complete for downflow duct application Field installed power exhaust available Prewired fo...

Page 68: ...bled hood ships with economizer Economizer ships complete for horizontal duct application Field installed power exhaust available If connected to a Building Automation System BAS all economizer functi...

Page 69: ...Single enthalpy CO2 input sensor available Field assembled hood ships with economizer Economizer ships complete for downflow duct application Field installed power exhaust available Prewired for smok...

Page 70: ...ilable Field assembled hood ships with economizer Economizer ships complete for horizontal duct application Field installed power exhaust available If connected to a Building Automation System BAS all...

Page 71: ...Exhaust Power exhaust kit for RXRD 01MDDAM3 RXRD 01MDDBM3 RXRD 01MDHAM3 RXRD 01MDHBM3 economizers RXRX CDF01 Figure 50 Vertical Airflow Power Exhaust Economizer MPS 007D 012D POWER EXHAUST BAROMETRIC...

Page 72: ...eed FLA ea LRA ea CFM L s RPM RXRX CDF01C 2 208 230 1 0 47 2200 1038 3000 1 55 1 1 RXRX CDF01D 2 460 3 0 40 1970 930 2750 0 51 1 9 NOTE 1 CFM is at 0 W C external static pressure 373 8 949 3 mm 16 406...

Page 73: ...ized 12 pin and 4 pin electrical connections Pre configured no field adjustments necessary CO2 sensor input available for Demand Control Ventilation DCV All fresh air damper functions can be viewed at...

Page 74: ...ilable for Demand Control Ventilation DCV All fresh air damper functions can be viewed at the RTU C unit controller display If connected to a Building Automation System BAS all fresh air damper functi...

Page 75: ...uick assembly corners for easy installation Insulating panels provided Opening provided in bottom pan to match the Thru the Curb electrical connection opening provided on the unit base pan Sealing gas...

Page 76: ...ol de energizes inducer blower 18 Control de energizes indoor blower 19 Control in the stand by mode with solid red LED Call For Second Stage After First Stage Established Starting from A 11 1 If a ca...

Page 77: ...W signal 5 Flash Over temperature switch open Operating Instructions DANGER Never test for gas leaks with an open flame It can cause an explosion or fire resulting in property damage personal injury o...

Page 78: ...rols are located on the burner shield These devices sense blockage in the heat exchanger or insufficient combustion air This shuts off the main burners if excessive temperatures occur in the burner co...

Page 79: ...lowed by a qualified installer service agency or gas supplier 1 Turn OFF the electrical power to the unit and set the thermostat to the lowest temperature 2 Shut OFF the gas supply to the unit either...

Page 80: ...t use excessive water pressure Excessive water pressure can bend the fins and tubing of the coil and lead to inadequate unit performance Be careful not to splash water excessively into unit 1 The coil...

Page 81: ...Maintenance www DaikinApplied com 81 IM 971 3 MAVERICK I System Charging Charts Figure 55 System Charging Charts 7 5 Ton Two Stage AC...

Page 82: ...IM 971 3 MAVERICK I 82 www DaikinApplied com Maintenance Figure 56 System Charging Charts 8 5 Ton Two Stage AC...

Page 83: ...Maintenance www DaikinApplied com 83 IM 971 3 MAVERICK I Figure 57 System Charging Charts 10 Ton Two Stage AC...

Page 84: ...IM 971 3 MAVERICK I 84 www DaikinApplied com Maintenance Figure 58 System Charging Charts 12 5 Ton AC...

Page 85: ...Maintenance www DaikinApplied com 85 IM 971 3 MAVERICK I Figure 59 System Charging Charts 7 5 Tons Two Stage with Reheat...

Page 86: ...IM 971 3 MAVERICK I 86 www DaikinApplied com Maintenance Figure 60 System Charging Charts 8 5 Tons Two Stage with Reheat...

Page 87: ...Maintenance www DaikinApplied com 87 IM 971 3 MAVERICK I Figure 61 System Charging Charts 10 0 Tons Two Stage with Reheat...

Page 88: ...IM 971 3 MAVERICK I 88 www DaikinApplied com Maintenance Figure 62 System Charging Charts 12 5 Tons Two Stage with Reheat...

Page 89: ...ttached to unit service panel Recover refrigerant evacuate recharge add filter drier At compressor terminals voltage must be within 10 of rating plate volts when unit is operating Compressor short cyc...

Page 90: ...UT CONTROLS CHECK FOR OPEN LIMIT CHECK IGNITION CONTROL CHASSIS GROUND WIRE CHECK WIRING CHECK INLET GAS PRESSURE CHECK 24 VOLTSTO GAS VALVE CHECK FOR GAS FLOWTO AND FROM VALVE CHECK BURNER CARRYOVER...

Page 91: ...ION REMOVE VALVE LEAD AT GAS VALVE IF VALVE CLOSES RECHECKTHETHERMOSTAT AND WIRING IF OK THEN REPLACE VALVE YES NO SYSTEM RUNS UNTIL CALL FOR HEAT ENDS TROUBLESHOOTING ENDS REPEAT PROCEDURE UNTIL TROU...

Page 92: ...IM 971 3 MAVERICK I 92 www DaikinApplied com Warranty Warranty Replacement Parts To find your local Daikin Certified Parts Distributor go to www DaikinApplied com and select Parts Locator...

Page 93: ......

Page 94: ...nt to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Applied Representative for warranty details To find your local Daikin Applied Representativ...

Reviews: