Component name
Pull-down
Capacity
Heat-up
Overcool
control
protection
Compressor
CC
ON
ON
ON
OFF
Evaporator fan. High speed
EFH
ON
ON
ON
ON
Evaporator fan. Low speed
EFL
OFF
OFF
OFF
OFF
Condenser fan
CF
ON / OFF
※
1 ON / OFF
※
4 ON / OFF
※
1
OFF
Liquid solenoid valve
LSV
ON
ON
OFF
OFF
Economizer solenoid valve
ESV
OFF
OFF
OFF
OFF
Injection solenoid valve
ISV
ON / OFF
※
2 ON / OFF
※
4 ON / OFF
※
3
OFF
Hot-gas solenoid valve
HSV
OFF
ON / OFF
※
4
ON
OFF
Defrost solenoid valve
DSV
OFF
ON / OFF
※
4
ON
OFF
Discharge gas by-pass solenoid valve
BSV
OFF
ON / OFF
※
4
OFF
OFF
Suction, modulating valve
SMV
100%
3 to 100%
100%
100%
Electronic expansion valve
EV
10 to 100%
10 to 100%
0%
50%
2-17
2.5.2 Chilled and partial frozen mode
Control state transition and common control
START
TS<SP+1.5˚C
TS
≧
SP+1.5˚C
Overcool protection
Capacity control
Pull-down
Heat-up
TS : Control temperature (supply air sensor or return air sensor)
SP: Set point temperature
TS
≦
SP+1.5˚C RS
≧
SP+1.0˚C
TS
≧
SP+5.0˚C
TS
≧
SP+1.0˚C
and 3-minutes
elapse
(TS
≦
SP–3.0˚C
and 3-minutes elapse)
or (
TS
≦
SP–0.5˚C
and 30-minutes elapse)
TS
≦
SP–0.5˚C
and 3-minutes elapse
Magnetic
contactor
Operation of magnetic conductor and solenoid valve
Note)
※
1: High pressure control
※
2: Discharge gas temperature control
※
3: Charge control
※
4: Capacity control and hot gas by-pass
Solenoid
valve