![background image](http://html1.mh-extra.com/html/daikin/lxe10e-a4/lxe10e-a4_service-manual_2460254119.webp)
4-17
4.2.7 Solenoid valve
Two kinds of solenoid valves are employed for
the unit.
Coil is common and replacement procedure is
also almost the same for all types of valves.
NEV-803DXF
Fig. 1
NEV-202DXF
Fig. 2
Valve name
Symbol
Valve type
Type of coil
Economizer
Solenoid valve.
ESV
NEV-202DXF
NEV-
MOAB507C
Injection Solenoid
valve.
ISV
Liquid Solenoid
valve.
LSV
NEV-803DXF
Discharge gas
by-pass Solenoid
valve.
BSV
Defrosting Solenoid
valve.
DSV
Hot gas Solenoid
valve.
HSV
Reheat Solenoid
valve.
RSV
(1) Replacing the coil
q
Remove the lead wire connector from the inside
of the control box, and cut and recover the binding
band which fastens the lead wire.
w
Remove the hexagonal head bolt on the top of the
coil to pull the coil out.
e
Replace the coil with a new one and restore the
hexagonal head bolt, the binding band and
connector on the original position.
When reassembling the coil, the tightening torque
should be 2.9 N
m (30 kg
cm).
(2) Replacement of valve body
q
Remove the hexagonal head bolt on the top of the
coil to pull the coil out.
w
Remove the hexagonal head bolt of the fixing
plate, and cut the two pipes at the side of the
valve body.
Disconnect the remaining pipes at the brazed joint
sections.
e
Insert the new valve body into the pipe and
conduct brazing while keeping the temperature of
the valve body below 120 ˚C (248 ˚F) by cooling.
r
Install the coil and restore the hexagonal head bolt
of the fixing plate and the connector into their
original position.
w
Hexagon
head bolt
e
Coil
q
Lead wire
r
Valve body
t
Hexagon head
bolt for fixing plate
q
Hexagon
head bolt
w
Coil
e
Valve body
r
Fixing plate