4P605460-1 – 2020.08
17.7.2 High voltage wiring – Capacity up unit
Connections/routing/fixing
3N~ 50 Hz
380-415 V
L1 L2 L3
L1 L2 L3 N
N
X1M
PE
c
b
a
d e
f
X2M
C C1 W1 R P1 P2
X2M
X1M
PE
a d/e/f
1
2
X1M
Power supply:
a: Power supply cable
b: Overcurrent fuse
c: Earth leakage circuit breaker
PE
Protective earth (screw)
X2M
Output signals:
d: Caution
e: Warning
f: Run
X2M
PE
X1M
1
2
g
g
Wiring intake (knockout hole) for high voltage. See
"17.3 Guidelines when knocking out knockout
Details – Output signals
NOTICE
Output signals
. The outdoor unit is provided with a terminal (X2M) that can output 3
different signals. The signal is 220~240 V AC. The maximum load for all signals is
0.5 A. The unit outputs a signal in the following situations:
▪
C/C1:
caution
signal – connection recommended – when an error occurs that
does not stop unit operation.
▪
C/W1:
warning
signal – connection recommended – when an error occurs that
causes unit operation to stop.
▪
R/P2:
run
signal – connection optional – when the compressor is running.
Wiring output signals: