16
|
Piping installation
Installer and user reference guide
76
LRYELRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit
4P605460-1 – 2020.08
Typical workflow
Connecting the refrigerant piping involves:
▪
Connecting refrigerant T-joints
▪
Connecting the refrigerant piping to the indoor units (see the installation manual
of the indoor units)
▪
Insulating the refrigerant piping
▪
Keeping in mind the guidelines for:
-
Pipe connections
-
Flaring pipe ends
-
Brazing
-
Using the stop valves
16.3.2 Precautions when connecting the refrigerant piping
INFORMATION
Also read the precautions and requirements in the following chapters:
▪
General safety precautions
▪
Preparation
DANGER: RISK OF BURNING/SCALDING
CAUTION
NEVER bend high pressure piping! Bending can reduce the pipe thickness and thus
weaken the piping. ALWAYS use K65 fittings.
NOTICE
Take adequate measures to prevent misuse of the piping. Some examples of misuse
of the piping: climbing on the piping, using the piping as storage, hanging tools on
the piping.