Troubleshooting
SiENBE28-901
102
Air Cooled Refrigeration Condensing Unit
Troubleshooting
*1.List of relevant malfunction codes and connectors
Malfunction
code
Relevant thermistor
LRMEQ5, 6AY1
LRLEQ5, 6AY1
LRMEQ8, 10, 12AY1
LRLEQ8, 10, 12AY1
LRMEQ15, 20AY1
LRLEQ15, 20AY1
Electrical
symbol
Connector
Electrical
symbol
Connector
Electrical
symbol
Connector
H9
Outdoor air thermistor
R1T
X18A
R1T
X18A
R1T
X18A
J3
Discharge pipe (M1C)
thermistor
R31T
X29A
R31T
X29A
R31T
X29A
Discharge pipe (M2C)
thermistor
—
—
R32T
R32T
Discharge pipe (M3C)
thermistor
—
—
—
—
R33T
J5
Suction pipe thermistor
R2T
X30A
R2T
X30A
R2T
X30A
J8
Heat exchanger outlet
thermistor
R5T
R5T
R5T
J9
Heat exchanger inlet
thermistor
R6T
R6T
R6T
JA
High pressure sensor
S1NPH
X32A
S1NPH
X32A
S1NPH
X32A
JC
Low pressure sensor
S1NPL
X31A
S1NPL
X31A
S1NPL
X31A
Caution
Be sure to turn off power switch before connect or disconnect connector,
or parts damage may be occurred.
*Three or more sensors malfunction.
Check for the malfunction
history (malfunction code) on
the remote controller to identify
three or more malfunctioning
sensors. (See*1)
Check the malfunctioning
sensor identified for their
connector connection.
Is the resistance
normal? (*1)
YES
NO
Troubleshoot according to the
malfunction code of each
malfunction sensor. (See the
flowchart corresponding to
each malfunction code.)
Is the resistance
normal?
NO
Properly connect it.
Replace the relevant sensor.
Replace the outdoor unit PCB
(control PCB).