15.3.9 About safety valves
When installing a safety valve, always keep the design pressure of the circuit in
mind. See
31].
WARNING
Serious injury and/or damage can result from the blow-off of the liquid receiver
safety valve (see
"25.2 Piping diagram: Outdoor unit"
▪
NEVER service the unit when the pressure at the liquid receiver is higher than the
set pressure of the liquid receiver safety valve (90 bar gauge ±3%). If this safety
valve releases refrigerant, it can cause serious injury and/or damage.
▪
If the pressure > set pressure, ALWAYS discharge from pressure relief devices
before servicing.
▪
It is recommended to install and secure blow-off piping to the safety valve.
▪
ONLY alter the safety valve if the refrigerant has been removed.
WARNING
All installed safety valves MUST ventilate to the outdoor space and NOT into a closed
area.
CAUTION
When installing a safety valve, ALWAYS add enough support to the valve. An
activated safety valve is under high pressure. If not installed securely, the safety valve
may cause damage to the piping or the unit.
NOTICE
The design pressure of high pressure side of the connected refrigeration parts MUST
be 9 MPaG (90 bar gauge).
NOTICE
If the design pressure of the gas piping of refrigeration parts is different from 90 bar
gauge (for example: 6 MPaG (60 bar gauge)), a safety valve MUST be installed on the
field piping according to this design pressure. It is NOT possible to connect
refrigeration parts with design pressure below 60 bar gauge.
NOTICE
When installing the safety valve provided in the accessory bag, we recommend to
apply 20 PTFE tape windings and tighten the safety valve in its correct position with a
torque between 35 and 60 N•m. Make sure that blow off piping can be installed
easily.
NOTICE
If the ability to close the stop valves for field piping is wanted, the installer MUST
install a pressure relief valve on the liquid piping between the outdoor unit and the
refrigeration indoor units.
Purpose
It is obligatory to install a safety valve that protects the pressure vessel.