background image

English 4

•  Tap M4 screw holes in the metal 
plate (fi eld supplies) as shown in the 
right drawing and mount the switch 
box on the metal plate.

Holes to be tapped in the metal plate 
on site (unit: mm)

32

21

2-M4

(1

2

0)

(70)

42

Cautions:

 

■ When wiring the extension cable, the air holes will not be blocked.

 

■ When the extension cable is longer than necessary, cut it to the appropri-
ate lenght, peel the insulation, attach the round crimp terminal for M3 (fi eld 
supplied) and carry out the wiring. The lenght of insulation to be peeled off  
is as shown. (Work carefully so that the connector side may not be cut.)

45

For M3 
Round crimp terminal

Wiring method

Connect the extension cable connector side to the indoor unit PCB (printed 
circuit board).
For connection to the indoor unit, follow the procedure shown below.

Cautions:

 

■ Make sure to turn off  the power supply before starting the wiring work and 
do not turn on until all the work is completed.
Read also the installation manual and the wiring diagram of the indoor unit 
when carrying out the work.

 

■ When wiring the extension cable, do not pass where the extension cable 
may be aff ected by the power line or noise.

 

■ Make sure to securely connect the connectors.
Defective connection may result in incorrect detection of room temperature 
on malfunction.

 

■ Do not splice wires.