background image

1

2

3

Installation Check (electrical test of the outdoor unit)

Installation Procedure (7)

1.

Check the following before powering on the unit.

1) Check whether the drain pan heater has been properly 

installed, wiring has been properly performed, and the removed 
components have been returned to the original positions.

2) Check the insulation resistance of the drain pan heater.

• Use the tester (500 VDC) to check that the insulation 

resistance between  1  terminal and the ground terminal 
and between  2  terminal and the ground terminal is equal 
to or higher than 1M

.

3) Check the continuity of the outdoor unit.

• Use the tester to check that the continuity between the 

screw on the front grille and the ground terminal reads 0

.

• When there is no continuity, retighten the screws securing 

the front plate and the bottom frame to increase the area 
of contact with the screw. Then, carry out the continuity 
test again.

2.

Check the following after powering on the unit.

• Turn on the power supply and check that the temperature of the 

drain pan heater will rise.

• Touch the bottom of the outdoor unit by hand and check 

the temperature rise.

• If the outdoor temperature is high, the heater will not be 

energized which is not a failure.
(Operation of thermo sensor: Turned on at 23˚F (–5˚C) 
and off at 34˚F (1˚C).)

3.

Install the remaining components to the original 
positions.

• Be careful not to confuse screw types. 

See 

Installation Procedure (1)

.

1) Install the shield plate.

• Only when  

KEH041A43

  is installed to the multi outdoor unit.

2) Install the right side plate.

• The drain pan heater is hot; do not touch it with bare hands.

CAUTION

1

2

Appearance of the outdoor 
unit may differ from some 
models.

2P326981-3

KEH041A43

Ground terminal 

 1  terminal

1

 2  terminal

2

Screw of the front grille

5.

Install each component to the original position.

• Be careful not to confuse screw types. See 

Installation Procedure (1)

1) Install the front plate (1).

2) Install the front plate (2).

3) Install the anti-drip cover, if provided.

4) Install the top plate.

Summary of Contents for KEH041A43

Page 1: ...erminal overheating an electrical shock or fire Wear protective gloves at the time of installation Touching the suction mouth or aluminum fin of the outdoor unit may result in injury Do not install the product in places where there is danger of exposure to inflammable gas leakage If the gas leaks and builds up around the unit it may catch fire Do not grab the top plate of the outdoor unit careless...

Page 2: ...rial long E Sealing material square F Installation manual G Electric wiring diagram label H Information label J Fixing plate K Panhead tapping screw with spring washer L Hexagon Nut M Earth plate N The appearance of the outdoor unit and the number of screws may differ from some models Number and type of screws to be removed Parts name Right side plate Top plate Anti drip cover Front plate 1 Front ...

Page 3: ...s to ensure positioning is correct before drilling holes The hole can be made with the included piercing screw as well 3 Install the drain pan heater Insert the plate under the heat exchanger 4 Install K fixing plate 5 Fix the drain pan heater with B piercing screw 6 Install the motor mounting plate for the fan motor base KEH041A43 only B K Installation Procedure 2 KEH041A43 KEH041A43 KEH041A43 Pa...

Page 4: ...ew B Piercing screw View A Plate Insert the plate under the heat exchanger Installation Procedure 3 Partition plate Ground plate Make the ground plate closely adhere to the partition Hole Partition plate Ground plate Make the ground plate closely adhere to the partition Hole K Fixing plate K Fixing plate K Fixing plate K Fixing plate Heat exchanger Heat exchanger Hole Fix with B piercing screw B H...

Page 5: ...binding band F E KEH041A43 Installation Procedure 4 3 Route the harnesses When drilling a hole be careful not to damage the soundproofing material and other components on the back side When drilling a hole in the partition plate be careful not to let chippings drop on the electrical components particularly the reactor Operating the unit with chippings attached on the reactor may cause electrical s...

Page 6: ...ion 5 Insert the snap band into the hole in the electrical wiring box to fix it Any of the holes can be used 6 Fix the harness on the electrical wiring box with the D binding band Cut the tip of binding band KEH041A44 F Hole Drill a hole in alignment with the actual component and at a position where the harness will not become loose or too tense D Binding band Snap band View E View D Anti bypass p...

Page 7: ...er s ground to the shield plate using L panhead tapping screw with spring washer and M hexagon nut KEH041A43 only 7 Drill a ø5 32 ø4mm hole in the rear plate and insert the snap band into the drilled hole 1 location 8 Drill a ø1 8 ø3 2mm hole in the stop valve mounting plate and fix N earth plate with B piercing screw and C hexagon tapping screw KEH041A49 only D L M N C B KEH041A43 KEH041A43 KEH04...

Page 8: ... again 2 Check the following after powering on the unit Turn on the power supply and check that the temperature of the drain pan heater will rise Touch the bottom of the outdoor unit by hand and check the temperature rise If the outdoor temperature is high the heater will not be energized which is not a failure Operation of thermo sensor Turned on at 23 F 5 C and off at 34 F 1 C 3 Install the rema...