Unit Controller
www.DaikinApplied.com 37
IOM 1322-1 • WATER-COOLED SCROLL COMPRESSOR
Trigger
: Sensor shorted or open AND Expansion Valve Type =
Electronic
Action
Taken
: Rapid stop circuit
Reset
: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.
Evaporator Pressure Sensor Fault
Alarm description:
EvapP Sensor Fail N
Trigger
: Sensor shorted or open. If failing high (open),
logic has been added that requires the Leaving Evaporator
Temperature to be below 75°F. This will prevent nuisance trips
due to conditions where the evaporator water temperature is
high which could cause false alarms.
Action
Taken
: Rapid stop circuit
Reset
: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.
Condenser Pressure Sensor Fault
Alarm description:
CondP Sensor Fail N
Trigger
: Sensor shorted or open
Action
Taken
: Rapid stop circuit
Reset
: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range.
Condenser Entering or Outdoor Air
Temperature Sensor Fault
Alarm description:
OAT Sensor Fault
Trigger
: Sensor shorted or open
Action
Taken
: Normal stop all circuits
Reset
: This alarm can be cleared manually via the keypad, but
only if the sensor is back in range
Evaporator Water Freeze Protect
Alarm description:
Evap Water Freeze
Trigger
: Evaporator LWT drops below evaporator freeze
protect set point AND Unit State = Auto
Action
Taken
: Rapid stop all circuits
Reset
: This alarm can be cleared manually via the keypad
or via the BAS clear alarm signal, but only if the alarm trigger
conditions no longer exist.
No Pressure Change at Start
Alarm description:
NoPressChgAtStartN
Trigger
: Circuit has failed twice on a No Pressure Change
at Start Condition. A No Pressure Change at Start Condition
indicates that after the start of the first compressor on the
circuit, at least a 1 psi drop in evaporator pressure OR a 1
psi increase in condenser pressure has not occurred after 15
seconds of compressor operation.
Action
Taken
: Rapid stop circuit
Reset
: This alarm can be cleared manually via the keypad.
EXB Comm Failure on CP1
Alarm description:
No EXB comm CP1
Trigger
: CP1 does not have communication with either EXB1
for 60 seconds after power up. This alarm will only occur if 10
Fan , evaporator pump #2, or condenser pump #2 operation
is selected. After communication is established, when
communication is lost to either EXB an immediate shutdown
occurs.
Action
Taken
: Rapid stop all circuits
Reset
: Auto clear when EXB1 is communicating with CP1.
Alarm Log
An alarm log stores the last 25 alarms and/or events to occur.
When an alarm or event occurs, it is put into the first slot in the
alarm log and all others are moved down one, dropping the last
entry. In the alarm log, the date and time the alarm occurred
are stored, as well as a list of other parameters. These
parameters include compressor states, evaporator pressure,
condenser pressure, number of fans on, OAT, and evaporator
LWT.
Active Alarms
When an alarm occurs, it appears in the active alarm list. The
active alarm list holds a record of all active alarms, which
includes the date and time each occurred.
Clearing Alarms
A password is NOT required to clear an active alarm. Active
alarms must be cleared at the unit controller. To clear active
alarms scroll down to the end of the Active Alarm list press
Enter to clear all active alarms. If the user attempts to clear an
alarm while the alarm condition still exists, a new alarm will be
generated immediately.
Limit Events
The following events do not cause a rapid stop but limit
operation of the chiller in some way as described in the Action
Taken. All limit events do NOT appear in the Active Alarm
window and are NOT logged in the Alarm Log
Low Evaporator Pressure - Hold
Event description:
Evap Press Low HoldN
Trigger
:
This event is triggered if all of the following are true:
• Circuit state = Run
• Circuit is not currently in a low OAT start
•
Has been at least 30 seconds since a compressor has
started on the circuit.
•
Evaporator pressure <= Low Evaporator Pressure - Hold
set point
Action
Taken
: Inhibit staging on of additional compressors on
the circuit.
Summary of Contents for IOM 1322-1
Page 4: ......
Page 57: ...Unit Controller Operation www DaikinApplied com 57 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 71: ...Unit Maintenance www DaikinApplied com 71 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 74: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 74 www DaikinApplied com Troubleshooting Chart...
Page 75: ...Troubleshooting Chart www DaikinApplied com 75 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 76: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 76 www DaikinApplied com Troubleshooting Chart...
Page 77: ...Troubleshooting Chart www DaikinApplied com 77 IOM 1322 1 WATER COOLED SCROLL COMPRESSOR...
Page 78: ...IOM 1322 1 WATER COOLED SCROLL COMPRESSOR 78 www DaikinApplied com Troubleshooting Chart...