background image

Installation and operation manual

18

125A7V1B

VRV IV System indoor unit

4P325971-1B – 2012.07

6

Repeat step 

2

 through 

4

 to change other field settings as

required.

7

When finished, press the 

z

 button to exit FIELD SET MODE.

8.3.2.

Detailed description

For a summary of all field settings refer to 

"8.4. Field setting list for

Installation Manual" on page 22

.

[0] Remote control setup

[0-00]

 User permission level

The user interface can be programmed to make certain buttons
and functions unavailable for the user. There are 2 permission
levels defined. Both levels (level 2 and level 3) are basically the
same, the only difference is that for level 3 no water temperature
settings are possible (see table below).

By default no level is defined so all buttons and functions are
operable.
The actual permission level is determined by field setting. For
permission level 2, set field setting [0-00] to 2, for permission
level 3, set field setting [0-00] to 3.
Once the field setting is set, the chosen permission level is not
yet active. Enabling the selected permission level is done by
simultaneously pressing buttons 

pi

 and 

pj

 immediately

followed by simultaneously pressing buttons 

s

 and 

ba

, and

keeping all 4 buttons pressed for at least 5 seconds. Note that
no indication on the user interface is given. After the procedure
the blocked buttons will not be available anymore.
Deactivating the selected permission level is done in the same
way.

[0-01]

 Room temperature compensation value

If needed, it is possible to adjust some thermistor value of the
unit by a correction value. This can be used as countermeasure
for thermistor tolerances or capacity shortage.
The compensated temperature (= measured temperature plus
compensation value) is then used for controlling the system and
will be displayed in the temperature read-out mode. See also

"[9] Automatic temperature compensation" on page 21

 for

compensation values for leaving water temperature.

[0-02] 

Setting not applicable

[0-03]

 Status: defines whether the ON/OFF instruction can be

used in the schedule timer for space heating.
Refer to the operation manual for details how to program the
schedule timer.
The schedule timer for space heating can be programmed in
2 different ways: based on the temperature set point (both
leaving water temperature and room temperature) and based on
the ON/OFF instruction.

In the following tables both methods on how to interpret the schedule
timer are shown.

INFORMATION

Changes made to a specific field setting are only
stored when the 

pr

 button is pressed. Navigating to

a new field setting code or pressing the 

z

 button will

discard the change made.

The field settings are grouped by their field setting first
code.

For example, field settings [0-00]; [0-01]; [0-02]; [0-03]
are defined as "Group 0".

When different values are changed within the same
group, pressing the 

pr

 button will save all the values

changed within this group.

Be aware of this when changing field settings within
the same group and pressing on the 

pr

 button.

INFORMATION

Before shipping, the set values have been set as
shown under 

"8.4. Field setting list for Installation

Manual" on page 22

.

When exiting FIELD SET MODE, "

88

" may be

displayed on the user interface LCD while the unit
initializes itself.

NOTICE

When running through the field settings you may notice
that there are some more field settings as there are
mentioned in the 

"8.4. Field setting list for Installation

Manual" on page 22

These field settings are not appli-

cable and may not be changed!

Permission

level 2

level 3

Operation ON/OFF

Operable

Operable

Setting the leaving water temperature

Operable

Setting the room temperature

Operable

Operable

Weather dependent set point operation 

ON/OFF

Operable

Setting the clock

Programming the schedule timer

Schedule timer operation ON/OFF

Operable

Operable

Field settings

malfunction code display

Operable

Operable

Test operation

INFORMATION

By default space heating based on temperature set point
(method 1) is enabled, so only temperature shifts are
possible (no ON/OFF instruction).

Method 1

Space heating based on temperature set point

(a)

(a) For leaving water temperature and/or room temperature

During operation

During schedule timer operation the operation LED is lit 

continuously.

When pushing 

the 

y

 button

The schedule timer for space heating will stop and will 

not start again.

The controller will be switched off (operation LED will 

stop working).

When pushing 

the 

pr

 button

The schedule timer for space heating will be stopped and 

will not start again.

The schedule timer icon will not be displayed anymore.

Summary of Contents for HXY080A7V1B

Page 1: ...VRV IV System indoor unit INSTALLATION AND OPERATION MANUAL HXY080A7V1B HXY125A7V1B System indoor unit ...

Page 2: ...o positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B сог...

Page 3: ...on 16 7 4 1 To fix the user interface cover to the indoor unit 16 7 4 2 To close the indoor unit 16 8 Commissioning 17 8 2 Final air purging 17 8 3 Field settings 17 8 3 1 Procedure 17 8 3 2 Detailed description 18 8 4 Field setting list for Installation Manual 22 8 5 Final check and test run 24 8 5 1 Final check 24 8 5 2 System test run 24 8 5 3 Indoor unit individual test run 24 8 6 Service and ...

Page 4: ...gerant of oil and of other parts must be done by an authorized installer and must comply with applicable legislation Units must be treated at a specialized treatment facility for reuse recycling and recovery By ensuring this product is disposed of correctly you will help to prevent potential negative consequences for the environment and human health For more information contact your installer or l...

Page 5: ...erant gas comes into contact with fire WARNING Always recover the refrigerants Do NOT release them directly into the environment Use a refrigerant reclaim unit to evacuate the installation NOTICE Make sure water quality complies with EU directive 98 83 EC DANGER RISK OF ELECTROCUTION Turn OFF all power supply before removing the switch box cover connecting electrical wiring or touching electrical ...

Page 6: ...s and or codes that are relevant and applicable for a certain product or domain Service company Qualified company which can perform or coordinate the required service to the product Installation manual Instruction manual specified for a certain product or application explaining how to install configure and maintain it Operation manual Instruction manual specified for a certain product or applicati...

Page 7: ...h Control close to the indoor unit Room thermostat functionality in the principal space to be heated Room thermostat EKRTWA EKRTR1 You can connect an optional room thermostat to the indoor unit This thermostat can either be wired EKRTWA or wireless EKRTR1 For installation instructions see the installation manual of the room thermostat Remote sensor for wireless thermostat EKRTETS You can use a wir...

Page 8: ...nit i Bypass valve field supply j User interface slave The under floor heating or heat pump connection is directly connected to the indoor unit The room temperature is controlled by the user interface which is used as room thermostat Possible installations User interface standard equipment installed in the room and used as room thermostat User interface standard equipment installed at the indoor u...

Page 9: ...nal capacity in case of heat pump capacity shortage See 9 Installing the optional EKBUHAA 6V3 6W1 heater kit on page 26 for details 6 Preparation 6 1 Preparing installation site Do NOT install the unit in places often used as work place In case of construction works e g grinding works where a lot of dust is created the unit must be covered Choose the installation location with sufficient place for...

Page 10: ... high humidity max RH 85 for example a bathroom In places where frost is possible Ambient temperature around the indoor unit should be 5 C The indoor unit is designed for indoor installation only and for indoor ambient temperatures ranging 5 35 C in cooling mode and 5 30 C in heating mode 6 2 Preparing water circuit 6 2 1 Selection of the type of heat emitters The selection of the heat emitter is ...

Page 11: ...ent galvanic corrosion Never use Zn coated parts in the water circuit Because the unit s internal water circuit uses copper piping excessive corrosion may occur Only use appropriate tooling to handle brass which is a soft material If NOT pipes will get damaged Select the water piping diameter in relation to the required water flow and the available external static pressure of the pump See 14 Techn...

Page 12: ...uit is 100 l No actions or adjustments are required Example 2 The indoor unit is installed at the highest point in the water circuit The total water volume in the water circuit is 350 l Actions Because the total water volume 350 l is more than the default water volume 280 l the pre pressure must be decreased The required pre pressure is Pg 0 3 H 10 bar 0 3 0 10 bar 0 3 bar The corresponding maximu...

Page 13: ...lectrical connections to the fixed wiring All components procured on the site and all electrical construction must comply with the applicable legislation WARNING The indoor unit should have a dedicated power supply The optional heater kit EKBUH should have a dedicated power supply 580 1 50 0 0 a b 1 a Normal power supply b Fuse 1 Power supply for indoor unit INFORMATION The following illustration ...

Page 14: ...nection Ø9 52 mm b Refrigerant gas connection Ø15 9 mm 1 Connect the liquid piping from the outdoor unit to the refrigerant liquid connection of the indoor unit 2 Connect the gas piping from the outdoor unit to the refrigerant gas connection of the indoor unit INFORMATION Installation shall be done by an installer the choice of materials and installation shall comply with the applicable legislatio...

Page 15: ...educe capacity losses during heating and cooling operations If the temperature is higher than 30 C and the humidity is higher than RH 80 the thickness of the sealing materials should be at least 20 mm to prevent condensation on the surface of the sealing NOTICE Do NOT put power on the unit before vacuuming is completed In case this happened refer to the instructions in the installation manual of t...

Page 16: ...cable legislation Use only copper wires All field wiring must be carried out in accordance with the wiring diagram supplied with the unit and the instructions given below Never squeeze bundled cables and be sure that it does not come in contact with the non insulated piping and sharp edges Be sure no external pressure is applied to the terminal connections Power supply wires must be attached secur...

Page 17: ...ce Fixation of the user interface to the indoor unit 1 Fix the wallplate of the user interface to the frontplate of the unit For installation of the frontplate see 7 4 1 To fix the user interface cover to the indoor unit on page 16 2 Cut off a 2 wire conductor 3 Connect the wires to the user interface as shown below From the rear 4 Reinstall the faceplate onto the wallplate First begin fitting fro...

Page 18: ...tening the mounting screws INFORMATION If next to the standard remote controller the optional remote controller is installed as well Connect the electrical wires of both remote controllers in the same way like described above Select a master and a slave remote controller by switching the SS1 selector switch Only the remote controller set as master can work as room thermostat INFORMATION For multip...

Page 19: ...ke sure that the shut off valves are correctly installed and fully open Once all checks are fulfilled the unit must be closed only then can the unit be powered on When the power supply to the indoor unit is turned on 88 is displayed on the user interface during its initialization which might take up to 30 seconds During this process the user interface can not be operated 8 2 Final air purging To g...

Page 20: ...g can be programmed in 2 different ways based on the temperature set point both leaving water temperature and room temperature and based on the ON OFF instruction In the following tables both methods on how to interpret the schedule timer are shown INFORMATION Changes made to a specific field setting are only stored when the pr button is pressed Navigating to a new field setting code or pressing t...

Page 21: ...D will stop working When pushing the y button The schedule timer for space heating will stop when active at that moment and will start again at the next scheduled ON function The last programmed command overrules the preceding programmed command and will remain active until the next programmed command occurs Example imagine the actual time is 17 30 and actions are programmed at 13 00 16 00 and 19 ...

Page 22: ... is installed its operation must be enabled by field setting Default 6 01 0 which means no external room thermostat is installed Set 6 01 2 if the optional external room thermostat is installed The external room thermostat only gives an ON OFF signal to the heat pump based on the room temperature Set 6 01 1 in case a heating thermostat ON or cooling thermostat ON function is required when using op...

Page 23: ...ccount influence of high ambient temperatures in the measurement 9 02 Setting is not applicable 9 03 Leaving water temperature compensation value for cooling operation 9 04 Setting not applicable A Option setup A 00 Setting is not applicable A 01 Setting is not applicable A 02 Pump target T setting heating Depending on the systems emitter type the T over the emitter can be modified within the rang...

Page 24: ...20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default value 1 01 Not applicable Do not change the default value Fri 02 Not applicable Do not change the default value 23 00 5 Automatic setback and disinfection set point 00 Not applicable Do not change the...

Page 25: ...2 1 C 03 Set point cooling leaving water minimum temperature 10 5 18 1 C 04 Not applicable Do not change the default value 0 d Settings are not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do not change the default value 15 04 Not applicable Do not change t...

Page 26: ...l and u are blinking 3 Push the ba button again to leave this mode If no button is pressed the user interface leaves the display mode after 10 seconds Procedure for space heating cooling 1 Check the leaving water and entering water temperature through the user interface read out mode and write down the displayed values See Temperature read out mode on page 24 2 Push the z button 4 times so the t i...

Page 27: ...t Make sure you do not touch a conductive section Do not rinse the unit This may cause electric shocks or fire Play it safe Touch a metal part by hand such as piping sheet metal in order to eliminate static electricity and to protect the PCB before performing service Malfunction code Failure cause Corrective action A1 Failure of writing memory EEPROM malfunction Contact your local dealer A6 Malfun...

Page 28: ... heater Refer to 8 3 Field settings on page 17 how to make field settings for field settings related to the EKBUHAA heater kit Other field settings which are explained in the EKBUHAA manual are not applicable in combination with HXY 080 125 hydrobox The default values should be kept as mentioned in the installation field setting list of the HXY 080 125 hydrobox Other information which is explained...

Page 29: ...RV DX Indoor Unit Refer to outdoor unit manual for further information Push the bi or bj button Display 88 8 starts blinking Display n Set desired room temperature e g 22 C The user interface room thermostat function is not active Push the ébi or ébj button You have room temperature based control of your system user interface room thermostat is installed You have leaving water temperature based co...

Page 30: ...he system is active 16 PUMP ICON é This icon indicates that the circulation pump is active 17 OUTDOOR TEMPERATURE DISPLAY u When this icon is flashing the outdoor ambient temperature is displayed Refer to 11 3 7 Temperature read out mode on page 31 for more information 18 WEATHER DEPENDENT SET POINT ICON a This icon indicates that the controller will adapt the leaving water temperature set point a...

Page 31: ...ated as required by the room temperature set point The set point can be set manually or through the schedule timer Selecting space cooling operation 1 Use the y button to switch ON OFF space cooling c Icon c appears on the display as well as the corresponding actual room temperature The operation LED 0 lights up 2 Use the bi and bj buttons to set the desired room temperature Temperature range for ...

Page 32: ...ng set point Activating this operation will result in a lower power consumption than use with a manually fixed leaving water set point During weather dependent operation the user has the possibility to shift up or down the target water temperature by a maximum of 5 C This shift value is the temperature difference between the temperature set point calculated by the controller and the real set point...

Page 33: ...etback is started 2 02 Stop time time at which setback is stopped 5 02 Leaving water setback temperature temperature drop A Normal leaving water temperature set point B Leaving water setback temperature A 5 02 t Time T Temperature 11 3 6 Other operation modes Start up operation d During start up the d icon displays indicating that the heat pump is starting up and is not working in a steady state c...

Page 34: ...Time T Temperature set point Room temperature Leaving water temperature INFORMATION By default space cooling based on temperature set point method 1 is enabled so only temperature shifts are possible no ON OFF instruction INFORMATION By default space heating based on temperature set point method 1 is enabled so only temperature shifts are possible no ON OFF instruction Method 1 0 03 1 default Spac...

Page 35: ...t action and end with the highest number for the last action This is not a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the first programmed action will be executed Example You can always alter add or remove the programmed actions later INFORMATION When power returns after a power supply failure...

Page 36: ...me 8 Use the ébi and ébj buttons to set the leaving water temperature 9 Use the bi and bj buttons to set the room temperature 10 Use the ba button to select x to switch cooling and the user interface off 11 Repeat steps 6 to 10 to program the other actions When all actions have been programmed make sure that the display shows the highest action number you would like to save 12 Press the button for...

Page 37: ...e 10 Use the bi and bj buttons to set the room temperature 11 Use the ba button to select x to switch heating and the user interface off a to select automatic temperature calculation for leaving water temperature Use the ébi and ébj buttons to set the appropriate shift value refer to Setting the schedule timer on page 29 for more information about weather dependent set point 12 Repeat steps 7 to 1...

Page 38: ...lected mode is blinking You can leave programming by pressing the pr button 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to copy to the next day by means of the pi and pj buttons The selected day is blinking You can return to step 2 by pressing the pr button 5 Press the and pr buttons simultaneously for 5 seconds After 5 seconds the dis...

Page 39: ...ltered field settings at variance with the default value 11 4 1 Procedure To change one or more field settings proceed as follows 1 Press the z button for a minimum of 5 seconds to enter FIELD SET MODE The icon 3 will be displayed The current selected field setting code is indicated 2 with the set value displayed to the right 1 2 Press the ébi button to select the appropriate field setting first c...

Page 40: ...bient temperature Hi_A 15 10 20 1 C 02 Set point at low ambient temperature Lo_Ti 40 25 80 1 C 03 Set point at high ambient temperature Hi_Ti 25 25 80 1 C 4 Settings are not applicable 00 Not applicable Do not change the default value 1 01 Not applicable Do not change the default value Fri 02 Not applicable Do not change the default value 23 00 5 Automatic setback and disinfection set point 00 Not...

Page 41: ...are not applicable 00 Not applicable Do not change the default value 10 01 Not applicable Do not change the default value 30 02 Not applicable Do not change the default value 15 03 Not applicable Do not change the default value 15 04 Not applicable Do not change the default value 40 E Service mode 00 Not applicable Do not change the default value 0 01 Not applicable Do not change the default value...

Page 42: ...utton In case this procedure for resetting the safety is not successful contact your local dealer For other malfunction codes which may be displayed during the system test run or operation see the installation manual of the outdoor unit 14 Technical Data 14 1 Piping diagram a Shut off valve with drain fill valve field installed b Expansion vessel c Water filter d Safety valve 3 bar e Manometer f P...

Page 43: ...ite YLW Yellow Notes PC L N X2M C COM X1M H H20 R1H X1M X1M only for EKRTR only for EKRTETS only for EKRTW 1 C COM H 1 A6P A6P A7P X801M 4 5 1 2 3 A4P 1 A1P WHT YLW ORG BLU RED BRN BLU BRN RED BLK WHT T1R Z1F PS HAP SS1 NORM EMG HAP 3 4 X1M 5 6 X1M X1M 11 12 Cooling heating output max 0 3A 230V AC Operation on off output max 0 3A 230V AC Error output max 0 3A 230V AC L X1M N 5 X2M 6 A3P only for E...

Page 44: ...ence on DX cooling cold draft and total efficiency Heating operation a Outdoor Ta CDB WB b Indoor LWC C c Warming up zone d Normal operation range 14 5 ESP curve ESP External Static Pressure Flow Waterflow through the unit Unit ESP at 4000 rpm T 5 C Unit ESP at 3800 rpm T 8 C Maximum ESP if T 5 C heating nominal Maximum ESP if T 5 C cooling nominal NOTICE When LWE is selected 18 C optional drain p...

Page 45: ...a 79 43 Power input W 110 135 Water side Heat exchanger Type Brazed plate Quantity 1 Minimal water flow rate d d Flow switch setting l min 15 Nominal water flow rate Cooling a l min 22 9 35 8 Heating e e The sound pressure level is measured at 1 m from the unit It is a relative value depending on the distance and acoustic environment l min 25 8 40 1 Insulation material Elastomeric foam Expansion v...

Page 46: ......

Page 47: ......

Page 48: ...4P325971 1B 2012 07 Copyright 2012 Daikin ...

Reviews: