background image

11 

TRAIL OPERATION AND TESTING 

1. Trial operation and testing

•  Check that the inter-unit wire is correctly connected. 
•  Trial  operation  should be carried out in COOL operation. 

1-1 Measure the supply voltage and make sure that it is within the specified range. 

1-2  Select the lowest programmable temperature. 

1-3  Carry out the trial operation following the instructions in the operation manual to ensure that all functions and parts, 

such as the movement of the flaps, are working properly. 

• To protect the air conditioner, restart operation is disabled  for 3 minutes after the system has been turned off. 

1-4 After trial operation is complete, set the temperature to a normal level (26

°

C to 2a•c in COOL operation, 2o•c to 24

°

in HEAT operation). 

When operating the air conditioner in COOL operation in winter,  or HEAT operation in summer, set it to the trial operation mode using the following method. 

1)  Press "MODE" button and select the cooling or heating mode. 

2)  Press "ON/OFF" button to turn on the system. 

3)  Press both of "TEMP" button and "MODE" button at the same time. 
4)  Press "TEMP" button, select 

"7', 

and press "MODE" button for confirmation. 

• Trial operation will stop automatically after about 30 minutes. To stop the operation press "ON/OFF"button. 

• The air conditioner draws a small amount of power in its standby mode. If the system is not to be used for some time after installation, shut off the circuit breaker to 

eliminate unnecessary power consumption. 

• If the circuit breaker trips to shut off the power to the air conditioner, the system  will restore the original operation mode when the circuit  breaker  is 

turned on again. 

2. Items to Check

Test  Items 

Symptom 

Check 

Indoor  and  outdoor  units  are  installed  securely. 

Fall,  vibration,  noise 

No  refrigerant  gas  leaks. 

Incomplete  cooling  function 

Refrigerant  gas  and  liquid  pipes  and  indoor  drain  hose 

Water leakage 

extension  are  thermally  insulated. 

Draining  line  is  properly  installed. 

Water  leakage 

System  is  properly earthed. 

Electrical leakage 

Only  specified  wires  are  used  for  all  wiring,  and  all 

No  operation  or  burn  damage 

wires  are  connected  correctly. 
Indoor or  outdoor unit's air intake  or  exhaust has  clear path of  air. 

Incomplete  cooling  function 

Stop  valves are  opened. 

Incomplete cooling function 

Indoor unit properly  receives  remote  controller  commands. 

No  operation 

PUMP DOWN OPERATION 

it 

WARNING---------------

• Make sure that air or any matter other than refrigerant (R32) does not get into the refrigeration cycle. 

• When performing a pump down, turn off the compressor before detaching the refrigerant pipes.  {II the refrigerant pipes are detached when 

the compressor is operating and the stop valves are open, air will be drawn in leading to abnormally high pressure in the 

refrigeration cycle. This may result in rupturing and bodily injury.) 

In order to protect the environment, be sure to pump down when relocating or disposing of the unit. 

1)  Remove the valve cap from the liquid stop valve and gas stop valve. 

2)  Begin forced cooling operation. 
3)  After 5 to  10 minutes, close the liquid stop valve with a hexagonal wrench. 

4)  After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation. 

Hexagonal 
wrench 

5)  Attach the valve cap once procedures are complete. 

Forced cooling operation 

Liquid stop valve  ....., 

X. 

Gas stop valve  !�Valve cap 

Service port-. 

■  Using the indoor unit ON/OFF switch 

Press and hold the indoor unit ON/OFF switch for at least 5 seconds. (The operation will  start) 

•  Forced cooling operation will stop automatically after about  15 minutes. 

To stop the operation, press the indoor unit ON/OFF switch. 

Disclaimer: Appearance of indoor & outdoor unit may differ 

between different models. 

Summary of Contents for GTL28UV16W1

Page 1: ...TIONER OPERATION MANUAL l D 1j r a 7c I MODELS F GTL28UV16W1 F GTL35UV16W1 F GTL35UV16W3 F GTL50UV16U3 F GTL50UV16V3 F GTL50UV16V7 F GTL50UV16V5 F GTE60UV16U2 F GTQ60UV16U5 F GTL50UV16U2 F GTL50UV16V2...

Page 2: ...e performance quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that prod...

Page 3: ...1 Signal receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop...

Page 4: ...ration mode DRY COOUFAN 9 ECONO button 10 TIMER CANCEL button It cancels the timer setting 11 ON TIMER button 12 OFF TIMER button 13 COANDA button COANDA operation 14 GOOD SLEEP button NOTE Notes on r...

Page 5: ...t get it wet The maximum transmission distance is about 7m To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor unit When attaching the accessory...

Page 6: ...remote the default set temperature will be set as mentioned in below table Mode Set temperature before remote switched OFF Set temperature after remote switched ON Cool If set temperature 24 C Defaul...

Page 7: ...1 minute after the operation is started However if the POWER CHILL operation is started air starts circulating immediately NOTE Note on airflow rate setting At smaller airflow rates the cooling effec...

Page 8: ...flaps reach the desired position The flaps will stop moving disappears from the LCD Right and left airflow direction To adjust the louvres at desired position Hold the knobs and move the louvres vert...

Page 9: ...again disappears from the LCD Notes on ECONO operation ECONO operation can only be set when the unit is running Pressing t1 causes the settings to be cancelled and disappears from the LCD ECONO operat...

Page 10: ...C O C OFF and the stop time default 2HR are displayed on the LCD ON OFF c J The TIMER lamp lights orange 0 1 TEMP ISP ay 2 Press v while C is blinking Each pressing of the button changes tempera ture...

Page 11: ...it toward you to disengage one of the front panel shafts Disengage the front panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward your...

Page 12: ...nt panel Insert the filters into slots of the front grille Close the front panel slowly and push the panel at the 3 points g c A c i I Accessory filter I Filter type Ag ion filter Micro filter PM2 5 1...

Page 13: ...filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Mirco filter PM1 0 1 set Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Prior to a long period of...

Page 14: ...arge voltage fluctuations It automatically resumes operation in about 3 minutes A sound is heard A sound like flowing water This sound is generated because the refrigerant in the air conditioner is fl...

Page 15: ...ool down Is the airflow rate setting appropriate If the airflow rate setting is too low increase it Is the set temperature appropriate Is the adjustment of the airflow direction appropriate Are the ai...

Page 16: ...er and call your service centre The air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood s...

Page 17: ...R MAIN CIRCUIT OVERVOLTAGE U4 FAILURE OF TRANSMISSION BETWEEN INDOOR UNIT AND OUTDOOR UNIT A1 INDOOR PCB DEFECTIVENESS A5 FREEZE UP PROTECTOR INDOOR A6 FAN MOTOR FAULT UNIT C4 FAULTY HEAT EXCHANGER TE...

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ...tion noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Draining line is properly install...

Page 22: ...asstop valve sservice port then fully openliquidand gasstop valves Do not attempt to turn valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas stop valves with a...

Page 23: ...39 9N m 21 6 27 4N m 0 D 9 5mm 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 48 1 59 7N m 505 615 kgf cmJ 490 61O kgf cm I 10 8 14 7N m 0 D 15 9mm 61 8 75 4N m 110 150 kgf cm 630 770...

Page 24: ...When there is no work space because the unit is close to ceiling CAUTION 1 Push up Be sure to wear protection gloves Place both hands under the centre of the front grille and while pushing up pull it...

Page 25: ...s 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of O...

Page 26: ...ed too much it may cause condensation or water dripping f Heat insulationpipe cover Slit 1111q11111J Slit Vinyl tape This illustration shows the case of the left rear piping Sectional view wire Insula...

Page 27: ...the unit it WARNING ____________________________________1_a1J_1 _N_ _ 4 Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as...

Page 28: ...oor unit to the A mounting plate with the E indoor unit fixing screws M4 x 12L 10 Caulk thegap between the pipe and the front grillewith putty 11 After completing refrigerant piping wiring and drain p...

Page 29: ...o 1100 610 Liquid pipeend Gaspipeend Drainhose position Applicable Unit Size Type H X W X D A B C i 298 X 800 X 229 800 116 5 116 5 298 X 821 X 229 821 128 126 5 298 X 885 X 229 885 116 5 116 5 298 X...

Page 30: ...the unit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby fflGi l li11 114 The outdoor unit should be posi...

Page 31: ...nt gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leak...

Page 32: ...R INSTALLATION MANUAL l J ffi 1 i i J MODELS F GTL28UV16W1 F GTL35UV16W1 F GTL35UV16W3 F GTL50UV16U3 F GTL50UV16V3 F GTL50UV16V7 F GTL50UV16V5 F GTE60UV16U2 F GTQ60UV16U5 F GTL50UV16U2 F GTL50UV16V2 F...

Reviews: