background image

OUTDOOR UNIT 

INSTALLING THE OUTDOOR UNIT 

• When installing the outdoor unit, refer to 

"Precautions for Selecting a  Location" 

and the 

"Outdoor Unit 

Installation Diagram". 

i'..111 

FLARING THE PIPE END

it, 

WARNING

c"' '"'""• at 

[!] 

Incomplete flaring may result refrigerant gas leakage. 

��Remove burrs. 

Flaring 

1) Cut the pipe end with a pipe cutter. 

Set exactly at the position shown below. 

Flare 

tool 

Conventional 

flare tool 

2) Remove burrs with the cut surface facing downward, so that the fillings 

\  for 

R41 0AIR32 

Clutch-type  I  Wing-nut 

type 

do not enter the pipe. 

Clutch-type  (Rigid-type)  {Imperial-type) 

0-0.Smm 

Check 

1.0-1.smm  1.5-2.0mm 

3) Put the flare nut on the pipe. 
4) Flare the pipe. 
5) Check that the flaring has been done correctly. 

Tho"'"'''"""'"'""' 

i

Tho 

pip, 

aod m,st ·'' "'"'' 

must be flaw-free. 

flared in a per1ect circle. 

1� :�: ::: i

i

���

t

-

he 

ICII 

REFRIGERANT PIPING

1) To prevent gas leakage, apply refrigeration oil to the inner surface of the flare. 

2) Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully with the torque 

wrenches. 

• Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and escaping gas. 

Flare nut 

Valve cap 

Service port cap 

Piping size  I tightening torque  tightening torque  tightening torque 

32.7-39.9N • m 

21.6-27.4N • m 

0. D. 9.5mm 

(333-407 kgf • cm) 

(220-280 kgf • cm) 

Gas side 

0. D. 12.7mm 

49.5-60.3N • m 

48.1-59.7N • m 

(505-615 kgf • cmJ 

(490-61 O kgf • cm) 

10.8-14.7N  • m 

0. D. 15.9mm 

61.8-75.4N • m 

(110-150 kgf • cm) 

(630-770 kgf • cm) 

14.2-17.2N  • m 

21.6-27.4N • m 

Liquid side 

O. D. 6.4mm 

(144-175 kgf • cm) 

(220-280 kgf • cm) 

Cautions on Pipe Handling 

Table No. 7 

1) Protect the open end of the pipe against dust and moisture. 

2) All pipe bends should be as gentle as possible. Use a pipe bender for 

bending. 

Selection of Copper and Heat Insulation materials 

1!:

i:i 

Brn�to

,a 

R�in 

place a cap . 

II no flare cap is 

available.cover 

the flare mouth 

with tape to keep 

dirtor waterout � 

When using commercial copper pipes and fittings, observe the following: 

1) Insulation material : Polyethylene foam or equivalent. 

Heat transfer rate - Co-efficient :  0.041  to 0.052W/m'K 

( 0.035 to 0.045kcal/m'h'C) 

.  Im 

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below. 

Piping 

Minimum 

size 

bend radius  Piping thickness 

0.0. 

30 mm or 

9.5mm 

more 

Thickness, 0.7mm 

Gas 

0.0. 

40 mm or 

(C1220T-O) 

side 

12.7mm 

more 

0.D. 

50 mm or 

Thickness 0.8mm 

15.9mm 

more 

(C1220T-O) 

Liquid 

0.0. 

30 mm or 

Thickness 0.6mm 

side 

6.4mm 

more 

(C1220T-O) 

Thermal  I 

Thermal 

,I 

insulation 

insulation size  thickness 

I.D 

12-15mm 

I.D 

14-16mm 

Thickness 

I.D 

min.6.5mm 

16-20mm 

I.D 

8-10mm 

Table No. 8 

• Use separate thermal 

insulation pipes for gas and 

liquid refrigerant pipes. 

Heatkisulllionri.>e� 

� 

�� 

Collll'AlnlcalonMI 

oro�i-

�;.:= 

Go,� 

� 

.... 

Summary of Contents for GTL28UV16W1

Page 1: ...TIONER OPERATION MANUAL l D 1j r a 7c I MODELS F GTL28UV16W1 F GTL35UV16W1 F GTL35UV16W3 F GTL50UV16U3 F GTL50UV16V3 F GTL50UV16V7 F GTL50UV16V5 F GTE60UV16U2 F GTQ60UV16U5 F GTL50UV16U2 F GTL50UV16V2...

Page 2: ...e performance quality and or longevity of the object concerned Do not expose plants or animals directly to the airflow from the unit as this may cause adverse effects Do not place appliances that prod...

Page 3: ...1 Signal receiver Receives signals from the remote controller When the unit receives a signal you will hear a beep sound Case Sound type Operation start beep beep Settings changed beep Operation stop...

Page 4: ...ration mode DRY COOUFAN 9 ECONO button 10 TIMER CANCEL button It cancels the timer setting 11 ON TIMER button 12 OFF TIMER button 13 COANDA button COANDA operation 14 GOOD SLEEP button NOTE Notes on r...

Page 5: ...t get it wet The maximum transmission distance is about 7m To attach the accessory filters Set the accessory filters under the tabs of the filter frame on the indoor unit When attaching the accessory...

Page 6: ...remote the default set temperature will be set as mentioned in below table Mode Set temperature before remote switched OFF Set temperature after remote switched ON Cool If set temperature 24 C Defaul...

Page 7: ...1 minute after the operation is started However if the POWER CHILL operation is started air starts circulating immediately NOTE Note on airflow rate setting At smaller airflow rates the cooling effec...

Page 8: ...flaps reach the desired position The flaps will stop moving disappears from the LCD Right and left airflow direction To adjust the louvres at desired position Hold the knobs and move the louvres vert...

Page 9: ...again disappears from the LCD Notes on ECONO operation ECONO operation can only be set when the unit is running Pressing t1 causes the settings to be cancelled and disappears from the LCD ECONO operat...

Page 10: ...C O C OFF and the stop time default 2HR are displayed on the LCD ON OFF c J The TIMER lamp lights orange 0 1 TEMP ISP ay 2 Press v while C is blinking Each pressing of the button changes tempera ture...

Page 11: ...it toward you to disengage one of the front panel shafts Disengage the front panel shaft on the other side in the same manner After disengaging both front panel shafts pull the front panel toward your...

Page 12: ...nt panel Insert the filters into slots of the front grille Close the front panel slowly and push the panel at the 3 points g c A c i I Accessory filter I Filter type Ag ion filter Micro filter PM2 5 1...

Page 13: ...filter 1 set Anti Microbial filter 1 set Micro filter PM2 5 1 set Mirco filter PM1 0 1 set Operation with dirty filters 1 cannot deodorise the air 3 results in poor cooling Prior to a long period of...

Page 14: ...arge voltage fluctuations It automatically resumes operation in about 3 minutes A sound is heard A sound like flowing water This sound is generated because the refrigerant in the air conditioner is fl...

Page 15: ...ool down Is the airflow rate setting appropriate If the airflow rate setting is too low increase it Is the set temperature appropriate Is the adjustment of the airflow direction appropriate Are the ai...

Page 16: ...er and call your service centre The air conditioner automatically resumes operation in about 3 minutes You should just wait for a while If there is a risk lightning could strike in the neighbourhood s...

Page 17: ...R MAIN CIRCUIT OVERVOLTAGE U4 FAILURE OF TRANSMISSION BETWEEN INDOOR UNIT AND OUTDOOR UNIT A1 INDOOR PCB DEFECTIVENESS A5 FREEZE UP PROTECTOR INDOOR A6 FAN MOTOR FAULT UNIT C4 FAULTY HEAT EXCHANGER TE...

Page 18: ......

Page 19: ......

Page 20: ......

Page 21: ...tion noise No refrigerant gas leaks Incomplete cooling function Refrigerant gas and liquid pipes and indoor drain hose Water leakage extension are thermally insulated Draining line is properly install...

Page 22: ...asstop valve sservice port then fully openliquidand gasstop valves Do not attempt to turn valve rod beyond its stop 8 Tighten valve caps and service port caps for the liquid and gas stop valves with a...

Page 23: ...39 9N m 21 6 27 4N m 0 D 9 5mm 333 407 kgf cm 220 280 kgf cm Gas side 0 D 12 7mm 49 5 60 3N m 48 1 59 7N m 505 615 kgf cmJ 490 61O kgf cm I 10 8 14 7N m 0 D 15 9mm 61 8 75 4N m 110 150 kgf cm 630 770...

Page 24: ...When there is no work space because the unit is close to ceiling CAUTION 1 Push up Be sure to wear protection gloves Place both hands under the centre of the front grille and while pushing up pull it...

Page 25: ...s 3m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Dimensions of O...

Page 26: ...ed too much it may cause condensation or water dripping f Heat insulationpipe cover Slit 1111q11111J Slit Vinyl tape This illustration shows the case of the left rear piping Sectional view wire Insula...

Page 27: ...the unit it WARNING ____________________________________1_a1J_1 _N_ _ 4 Use a stabiliser if required by the voltage supply condition Do not use tapped wires extension cords or starburst connections as...

Page 28: ...oor unit to the A mounting plate with the E indoor unit fixing screws M4 x 12L 10 Caulk thegap between the pipe and the front grillewith putty 11 After completing refrigerant piping wiring and drain p...

Page 29: ...o 1100 610 Liquid pipeend Gaspipeend Drainhose position Applicable Unit Size Type H X W X D A B C i 298 X 800 X 229 800 116 5 116 5 298 X 821 X 229 821 128 126 5 298 X 885 X 229 885 116 5 116 5 298 X...

Page 30: ...the unit may cause interference with the picture or sound 9 the unit can be installed at the recommended height 1 8m 10 no laundry equipment is nearby fflGi l li11 114 The outdoor unit should be posi...

Page 31: ...nt gas leaks during installation ventilate the area immediately 0 Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leak...

Page 32: ...R INSTALLATION MANUAL l J ffi 1 i i J MODELS F GTL28UV16W1 F GTL35UV16W1 F GTL35UV16W3 F GTL50UV16U3 F GTL50UV16V3 F GTL50UV16V7 F GTL50UV16V5 F GTE60UV16U2 F GTQ60UV16U5 F GTL50UV16U2 F GTL50UV16V2 F...

Reviews: