Drain piping work

Installation of drain piping

Install the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

Install the drain pipes.
- Keep piping as short as possible and slope it downwards at a 

gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

- Keep pipe size equal to or greater than that of the connecting 

pipe (vinyl pipe of 25 mm nominal diameter and 32 mm outer 
diameter).

- Push the supplied drain hose as far as possible over the 

drain socket.

- Tighten the metal clamp until the screw head is less than 

4 mm from the metal clamp part as indicated in the 
illustration.

- Wrap the supplied large sealing pad over the metal clamp 

and drain hose to insulate and fix it with clamps.

- Insulate the complete drain piping inside the building (field 

supply).

- If the drain hose cannot be sufficiently set on a slope, fit the 

hose with drain raising piping (field supply).

How to perform drain piping 

(See figure 10)

1

Connect the drain hose to the drain raising pipes, and insulate
them.

2

Connect the drain hose to the drain outlet on the indoor unit, and
tighten it with the clamp.

Precautions
- Install the drain raising pipes at a height of less than 625 mm.
- Install the drain raising pipes at a right angle to the indoor 

unit and no more than 300 mm from the unit.

- To prevent air bubbles, install the drain hose level or slightly 

tilted up (

75 mm).

- The drain pump mounted in this unit is the high lift type. The 

characteristic of this pump is that the higher the pump is the 
lower the drainage sound becomes. Therefore a drain pump 
height of 300mm is recommended.

Testing of drain piping

After piping work is finished, check if drainage flows smoothly.

Add approximately 1 l of water gradually through the air
discharge outlet. Check for water leaks.
Method of adding water. See 

figure 8

.

Indoor unit

T (kg)

Outdoor = RXYQ or 

RYYQ

T (kg)

Outdoor= REYQ

FXTQ50

0,3

0,3

FXTQ63

0,2

0,2

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)

4

Large sealing pad (supplied with the unit)

5

Drain piping (field supply)

1-1.5 m

1

2

1

5

2

3

4

4 mm

3

4

2

A

A'

A-A'

1

1

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe

5

Drain hose (supplied with the unit)

6

Clamp metal (supplied with the unit)

Installation

A (mm)

Rear suction installation

231

When canvas duct is installed

350-530

When air inlet panel is directly installed

231

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.

To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.

When unifying multiple drain pipes, install the
pipes as shown in 

figure 11

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

Water inlet

2

Portable pump

3

Water inlet cover

4

Bucket (adding water through water inlet)

5

Drain outlet for maintenance (with rubber drain plug)

6

Refrigerant pipes

Summary of Contents for FXTQ50A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXTQ50A2VEB FXTQ63A2VEB System air conditioners...

Page 2: ...1 2 4 5 3 6a 7c 6b 6c 8 9 10 11 2 1 3 5 4 5 2 1 1 2 2 3 680 1 3 4 2 680 200 45 1 5 6 3 4 2 680 1 5 3 4 2 7 800 630 A B 2 1 4 3 4 6 3 5 6 4 2 1 1 1 2 1 3 5 2 125 460 160 160 300 375 1 3 2 460 7a 7b 4...

Page 3: ...como se establece en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como esta...

Page 4: ...of salt such as air near the ocean and where voltage fluctuates a lot e g in factories Also in vehicles or vessels Do not install accessories on the casing directly Drilling holes in the casing may da...

Page 5: ...tance between wireless remote controller and indoor unit might be shorter if there are fluorescent lights who are electrically started in the room The indoor unit must be installed as far as possible...

Page 6: ...accessory screws 7 Wrap the intake side flange and duct connection area with aluminum tape or something similar to prevent air escaping 1 Ceiling surface 2 Ceiling opening 3 Service access panel opti...

Page 7: ...lacement or releasing nitrogen into the piping will create large quantities of oxidized film on the inside of the pipes adversely affecting valves and compressors in the refrigerating system and preve...

Page 8: ...ge of outdoor unit R additional refrigerant charge according to liquid piping diameter length and outdoor unit specific amount defined in outdoor unit manual P additional refrigerant charge due to use...

Page 9: ...pump mounted in this unit is the high lift type The characteristic of this pump is that the higher the pump is the lower the drainage sound becomes Therefore a drain pump height of 300mm is recommend...

Page 10: ...turned back on again Refer to the installation manual delivered with the outdoor unit for the size of power supply electric wire connected to the outdoor unit the capacity of the earth leakage breaker...

Page 11: ...or transmission wiring This mistake could damage the entire system 6 Use only specified wires and tightly connect wires to the terminals Be careful that wires do not place external stress on the termi...

Page 12: ...hermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote...

Page 13: ...ure to turn on the outdoor unit before performing the test operation on the outdoor unit If any other error display occurs on the display of the remote controller refer to Test operation on page 11 an...

Page 14: ...mpossible to clean change the air filter Air filter for exchange is optional 1 Open the suction grille Only for bottom suction Slide both knobs simultaneously as shown and then pull them downward Wire...

Page 15: ...ve any obstacle Check if the earth is connected Clean the air filter and outside panels After cleaning the air filter make sure to attach it Turn on the main power supply switch The control panel disp...

Page 16: ...ONNECTOR OPTIONAL ACCESSORY X28A CONNECTOR POWER SUPPLY FOR WIRING X33A CONNECTOR FOR WIRING X35A CONNECTOR POWER SUPPLY FOR WIRING X38A CONNECTOR FOR WIRING FIELD WIRING BLK BLACK PNK PINK CONNECTOR...

Page 17: ......

Page 18: ......

Page 19: ...F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 2 5 3 IN D OUT D F1 F2 F1 F2 Control box IN D OUT D F1 F2 F1 F2 Control box L N P1 P2 P1 P2 F1 F2 T1 T2 1 3 6 2 1 2 5 6 3 4...

Page 20: ...4P410034 1 2015 05 Copyright 2015 Daikin...

Reviews: